| Class B | Closed | 64 | Feb 9, 2018 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... WEST WALL AND SOUTH WALL IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 64, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | ClosedRENT IMPAIRING | 64 | Feb 9, 2018 | REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN WASHBASIN IN THE BATHROOM LOCATED AT APT 64, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 30 | Feb 9, 2018 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 30, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 44 | Feb 7, 2018 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 44, 4th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 56 | Feb 7, 2018 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING, 1st DOOR FROM EAST AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 56, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 56 | Feb 7, 2018 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 56, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 44 | Feb 5, 2018 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSIING LOCATED AT APT 44, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | — | Feb 5, 2018 | POST AND MAINTAIN A NOTICE · POSTING/SIGNAGE§27-2153 ADM CODE POST AND MAINTAIN A NOTICE, WRITTEN IN ENGLISH AND IN SPANISH, ON THE BUILDING ENTRANCE DOOR OR OTHER CONSPICUOUS LOCATION IN THE BUILDING COMMON AREA, STATING THAT: (1) THE BUILDING IS IN THE ALTERNATIVE ENFORCEMENT PROGRAM, (2) THAT OCCUPANTS MAY CALL 311 OR THE AEP AT 212-863-8262 TO REPORT HOUSING MAINTENANCE COMPLAINTS, (3) THE NAME, TELEPHONE, AND ADDRESS OF THE OWNER, AND, (4) THE IDENTITY OF ANY FINANCIAL INSTITUTION THAT HOLDS A MORTGAGE ON THE PROPERTY. POST |
| Class B | ClosedRENT IMPAIRING | — | Jan 2, 2018 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION MATERIAL AT PUBLIC HALL, 1st STORY |
| Class B | ClosedRENT IMPAIRING | — | Jan 2, 2018 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION MATERIAL AT PUBLIC HALL, 5th STORY |
| Class C | Closed | — | Dec 29, 2017 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING WINDOW AT INTERMEDIATE LANDING AT PUBLIC STAIR EAST SECTION AT 4TH STORY |
| Class C | Closed | 56 | Dec 22, 2017 | LEAD-BASED PAINT HAZARD- PRESUMED PAINT · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING, 1st DOOR FROM EAST AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 56, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 56 | Dec 22, 2017 | LEAD-BASED PAINT HAZARD- PRESUMED PAINT · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 56, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 56 | Dec 19, 2017 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... ON THE CEILING IN THE BATHROOM LOCATED AT APT 56, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 47 | Dec 19, 2017 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR (MISSING) LOCATED AT APT 47, 4th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 60 | Dec 19, 2017 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 1st ROOM FROM NORTH LOCATED AT APT 60, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 56 | Dec 19, 2017 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING IN THE BATHROOM LOCATED AT APT 56, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 47 | Dec 19, 2017 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). (MISSING) LOCATED AT APT 47, 4th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 56 | Dec 19, 2017 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING IN THE BATHROOM LOCATED AT APT 56, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | — | Dec 19, 2017 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING UPPER AND LOWER WINDOW GLASS AT PUBLIC HALL STAIRS, 5th STORY |
| Class C | Closed | — | Nov 29, 2017 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF DISCARDED RADIATOR AT PUBLIC HALL, 5th STORY |
| Class C | Closed | — | Nov 29, 2017 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING MISSING UPPER AND LOWER WINDOW SASHES AT PUBLIC HALL STAIRS, 4th STORY, SECTION ''EAST'' |
| Class B | ClosedRENT IMPAIRING | — | Nov 29, 2017 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION DEBRIS AT PUBLIC HALL, 5th STORY |
| Class B | Closed | — | Oct 2, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONER AT 4TH STORY BALCONY AT EAST STACK AT BUILDING FRONT |
| Class B | Closed | — | Oct 2, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONER AT 4TH STORY BALCONY AT WEST STACK AT BUILDING FRONT |
| Class B | Closed | — | Oct 2, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONER AT 3RD STORY BALCONY AT WEST STACK AT BUILDING FRONT |
| Class B | Closed | — | Oct 2, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES FLOWER POTS AT 6TH STORY BALCONY AT EAST STACK AT BUILDING FRONT |
| Class B | Closed | — | Oct 2, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONER AT 5TH STORY BALCONY AT WEST STACK AT BUILDING FRONT |
| Class B | Closed | — | Sep 7, 2017 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE MASONARY AT EAST WALL AT FIRE PASSAGE WAY AT WEST YARD |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 5TH STORY BALCONY AT NORTHEAST STACK AT REAR YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 6TH STORY BALCONY AT NORTHEAST STACK AT REAR YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE MASONARY AT CEILING AT FIRE PASSAGE WAY AT EAST YARD |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 4TH STORY BALCONY AT NORTHEAST STACK AT REAR YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 6TH STORY BALCONY AT EAST STACK AT EAST YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF DROP LADDER FULLY EXTENDED AT NORTH EAST STACK AT REAR YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 2ND STORY BALCONY AT EAST STACK AT EAST YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 3RD STORY BALCONY AT EAST STACK AT EAST YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 4TH STORY BALCONY AT EAST STACK AT EAST YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 5TH STORY BALCONY AT EAST STACK AT EAST YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 3RD STORY BALCONY AT NORTHEAST STACK AT REAR YARD AT FIRE ESCAPE |
| Class C | Closed | — | Sep 7, 2017 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT BOILER ROOM DOOR AND AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONER AT 1ST STORY BALCONY AT NORTHEAST STACK AT REAR YARD AT FIRE ESCAPE |
| Class B | Closed | — | Sep 7, 2017 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES HOUSE HOLD ITEMS AT 2ND STORY BALCONY AT NORTHEAST STACK AT REAR YARD AT FIRE ESCAPE |
| Class A | Closed | 50 | Aug 23, 2017 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING, EAST WALL, WEST WALL IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 50, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 50 | Aug 23, 2017 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 50, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Aug 14, 2017 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING SIGN AT PUBLIC HALL, 1st STORY |
| Class B | ClosedRENT IMPAIRING | — | Aug 14, 2017 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION MATERIAL AND HOUSEHOLD ITEMS AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Aug 14, 2017 | POST GAS LEAK NOTICE · POSTING/SIGNAGE§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Aug 14, 2017 | POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Aug 14, 2017 | IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR WRONG FRAME AT PUBLIC HALL, 1st STORY |