| Class B | Open | 3Q | Mar 19, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ESCUTCHEON PLATE AT HEAT RISER IN THE KITCHEN LOCATED AT APT 3Q, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Open | 3Q | Mar 19, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 4th ROOM FROM NORTH LOCATED AT APT 3Q, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Open | 4P | Mar 17, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 11 SQ FT AROUND WINDOW FRAME AT EAST WALL IN THE BATHROOM LOCATED AT APT 4P, 5th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION AT WEST |
| Class B | Open | 4P | Mar 17, 2026 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ESCUTCHEON PLATE AT HEAT RISER IN THE KITCHEN LOCATED AT APT 4P, 5th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION AT WEST |
| Class B | Open | 4O | Feb 26, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 4O, 4th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 4F | Feb 12, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WEST WALL AT CLOSET IN THE PRIVATE HALLWAY LOCATED AT APT 4F, 5th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 4F | Feb 12, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQFT AT CEILING, SOUTH, EAST AND WEST WALLS IN THE BATHROOM LOCATED AT APT 4F, 5th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 3Q | Feb 5, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ. FT AT WINDOW SASH FROM SOUTH AT WEST WALL IN THE BATHROOM LOCATED AT APT 3Q, 3rd STORY, 3rd APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 18281034 ISSUED 07-OCT-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b). |
| Class B | Closed | 3H | Jan 20, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 3H, 4th STORY, 4th APARTMENT FROM EAST AT SOUTH , SECTION AT EAST |
| Class B | Closed | 3H | Jan 20, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER WINDOW SASH, THE 1ST WINDOW FROM SOUTH AT WEST WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 3H, 4th STORY, 4th APARTMENT FROM EAST AT SOUTH , SECTION AT EAST |
| Class B | Closed | 3H | Jan 20, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 3H, 4th STORY, 4th APARTMENT FROM EAST AT SOUTH , SECTION AT EAST |
| Class B | Closed | — | Jan 5, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT VESTIBULE DOOR , 2nd STORY, SECTION ''230'' |
| Class B | Closed | 4M | Nov 20, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4M, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''BLDG230'' |
| Class B | Closed | 4M | Nov 20, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4M, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''BLDG230'' |
| Class B | Closed | 5P | Nov 5, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES IN THE BATHROOM LOCATED AT APT 5P, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 5P | Nov 5, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERMIC FLOOR TILES IN THE BATHROOM LOCATED AT APT 5P, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | E | Oct 30, 2025 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT DOOR IN THE ENTRANCE LOCATED AT APT E, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5P | Oct 30, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL AND BUZZER INTERCOM SYSTEM FROM BUILDING FRONT TO PANEL AT WEST WALL IN THE FOYER LOCATED AT APT 5P, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Open | E | Oct 30, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE UPPER ESCUTCHEON PLATE AT RISER IN THE KITCHEN LOCATED AT APT E, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | E | Oct 30, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE UPPER ESCUTCHEON PLATE AT RISER IN THE 1st ROOM FROM NORTH LOCATED AT APT E, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | E | Oct 30, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE UPPER ESCUTCHEON PLATE AT RISER IN THE BATHROOM LOCATED AT APT E, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 5P | Oct 30, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE UPPER ESCUTCHEON PLATE AT RISER IN THE BATHROOM LOCATED AT APT 5P, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Open | 5P | Oct 30, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE UPPER ESCUTCHEON PLATE AT RISER IN THE KITCHEN LOCATED AT APT 5P, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Open | E | Oct 30, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT E, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3Q | Oct 10, 2025 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE CERAMIC TILE AT FLOOR IN THE BATHROOM LOCATED AT APT 3Q, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3Q | Oct 10, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE DOOR AT ENTRANCE IN THE BATHROOM LOCATED AT APT 3Q, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3Q | Oct 10, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3Q, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3Q | Oct 10, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3Q, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2B | Oct 9, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES FLOOR IN THE KITCHEN LOCATED AT APT 2B, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | — | Oct 9, 2025 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT DOOR AT BULKHEAD , SECTION ''EAST'' |
| Class B | Closed | — | Oct 9, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 3Q | Oct 8, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3Q, 3rd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 4B | Oct 8, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 4B, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3Q | Oct 8, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3Q, 3rd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3S | Sep 26, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 3S, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3S | Sep 26, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 3S, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3S | Sep 26, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 3S, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3S | Sep 26, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE PRIVATE HALLWAY LOCATED AT APT 3S, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | — | Sep 12, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF MATTRESS AND BED FRAMES AT BASEMENT |
| Class B | Closed | — | Sep 12, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE FLOOR AT BASEMENT |
| Class B | Closed | — | Sep 9, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT NORTH WALL EAST BUILDING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | K | Sep 9, 2025 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT K, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | — | Sep 9, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION MATERIALS AT EAST BUILDING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 4E | Aug 13, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH WINDOW IN THE BATHROOM LOCATED AT APT 4E, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 4E | Aug 13, 2025 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT 4E, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1P | Jul 7, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND NORTH WALL IN THE KITCHEN LOCATED AT APT 1P, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Open | 1A | Jun 27, 2025 | CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD · LEAD-BASED PAINT§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 1A, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''230'', 1st FROM NORTH AT EAST |
| Class B | Open | 5C | Jun 27, 2025 | CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD · LEAD-BASED PAINT§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 5C, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH , SECTION ''230'', 1st FROM NORTH AT EAST |
| Class B | Open | 1Q | Jun 27, 2025 | CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD · LEAD-BASED PAINT§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 1Q, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH , SECTION ''230'', 1st FROM SOUTH AT WEST |
| Class B | Open | G | Jun 27, 2025 | CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD · LEAD-BASED PAINT§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT G, 1st STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''230'', 1st FROM SOUTH AT WEST |