| Class B | OpenRENT IMPAIRING | 5D | Nov 21, 2025 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK ABOVE THE CEILING IN THE KITCHEN LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 5D | Nov 21, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AND ALL WALLS IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | OpenRENT IMPAIRING | 5D | Nov 21, 2025 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING IN THE FOYER LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 5D | Nov 21, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND NORTH WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 5B | Nov 10, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOM SYSTEM FROM VESTIBULE TO NORTH WALL IN THE FOYER LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 5B | Nov 10, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 5B | Nov 10, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGGHT FIXTURE AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | OpenRENT IMPAIRING | 5B | Nov 10, 2025 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | OpenRENT IMPAIRING | 5B | Nov 10, 2025 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE 4th ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 5B | Nov 10, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE PRIVATE HALLWAY LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 5B | Nov 10, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE 4th ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | OpenRENT IMPAIRING | 5B | Nov 10, 2025 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | OpenRENT IMPAIRING | 5B | Nov 10, 2025 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 5B | Nov 10, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT ALL WALLS AND CEILING IN THE KITCHEN LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 5B | Nov 10, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE 1st ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3M | Oct 31, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT SOUTH WALL IN THE KITCHEN LOCATED AT APT 3M, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | — | Oct 29, 2025 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF FLOWER POTS AT THE 2ND STACK FROM NORTH AT EAST, 4TH STORY BALCONY AT FIRE ESCAPE |
| Class B | Open | 2D | Oct 16, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE 4th ROOM FROM EAST LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 3C | Oct 16, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3C, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 2J | Oct 16, 2025 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF SLIDEBOLT CAPABLE OF BEING PADLOCKED AT APARTMENT ENTRANCE DOOR IN THE ENTRANCE LOCATED AT APT 2J, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 3M | Oct 16, 2025 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 3M, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Open | 3C | Oct 16, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3C, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 2D | Oct 16, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE KITCHEN LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 2D | Oct 16, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT SOUTH AND WEST WALLS IN THE FOYER LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 5F | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALENCE AT LOWER WINDOW SASH AT THE 1ST WINDOW FROM SOUTH AT WEST IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5F | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALENCE AT UPPER WINDOW SASH AT NORTH IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5F | Oct 14, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5F | Oct 14, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5F | Oct 14, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Sep 29, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FT AT SOUTH WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 17922416 ISSUED 28-MAY-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b). |
| Class B | Closed | 2D | Sep 22, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING, NORTH AND WEST WALLS IN THE PRIVATE HALLWAY LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Closed | 1D | Sep 22, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 1D, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Closed | 1D | Sep 22, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILNG IN THE 1st ROOM FROM EAST LOCATED AT APT 1D, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Closed | 2D | Sep 22, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AND WEST WALL IN THE KITCHEN LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Closed | 2D | Sep 22, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND EAST WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Closed | 2D | Sep 22, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | — | Sep 12, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE DOOR AT MAILBOX #5D , 1st STORY |
| Class B | Open | — | Sep 12, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE 4TH MARBLE TREAD FROM BOTTOM AT INTERMEDIATE LANDING AT PUBLIC HALL STAIRS, 1st STORY |
| Class B | Closed | — | Sep 11, 2025 | PROVIDE GARGABE CANS · COLLECTION OF WASTE§ 27-2021 ADM CODE PROVIDE SUFFICIENT, PROPER AND SEPARATE METAL RECEPTACLES FOR THE DEPOSIT OF GARBAGE, RUBBISH AND OTHER WASTE MATERIAL AND ARRANGE FOR COLLECTION AND DISPOSAL OF SUCH MATERIAL. |
| Class B | Open | 5D | Sep 8, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL AND RETURN BUZZER INTERCOM SYSTEM FROM BUILDING FRONT ENTRANCE TO PANEL AT NORTH WALL AT FOYER LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Sep 8, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE SOUTH, WEST AND NORTH WALL IN THE 3rd ROOM FROM EAST AT NORTH LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Sep 8, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE WEST AND NORTH WALL IN THE KITCHEN LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Sep 8, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING, SOUTH AND WEST WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Sep 8, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER WINDOW SASH AT WEST WALL IN THE 3rd ROOM FROM EAST AT NORTH LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Sep 8, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING AND SOUTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Sep 8, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE DOOR KNOB IN THE BATHROOM LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Aug 28, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Aug 28, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS IN THE 3rd ROOM FROM EAST AT NORTH LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Aug 28, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5D | Aug 28, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL-BUZZER SYSTEM AT SOUTH WALL IN THE FOYER LOCATED AT APT 5D, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST |