| Class B | Closed | 5MN | Nov 6, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLETS AT WEST AND SOUTH WALL IN THE KITCHEN LOCATED AT APT 5MN, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5MN | Nov 6, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RUBBER GASKET AT REFRIGERATOR DOOR. IN THE KITCHEN LOCATED AT APT 5MN, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6AN | Nov 6, 2023 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING NORTH AND WEST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 6AN, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTH |
| Class B | ClosedRENT IMPAIRING | 6AN | Nov 6, 2023 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE FOYER LOCATED AT APT 6AN, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTH |
| Class B | ClosedRENT IMPAIRING | 6AN | Nov 6, 2023 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT 6AN, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTH |
| Class B | Closed | — | Nov 6, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BROKEN AND CRACKED CLASS AT WINDOW AT WEST AT LOBBY, 1st STORY |
| Class B | Closed | — | Nov 6, 2023 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT BUILDING ENTRANCE VESIBULE DOOR (FROM VESTIBULE TO 1ST STORY PUBLIC HALL) AT LOBBY, 1st STORY |
| Class B | Closed | — | Nov 6, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MISSING LOWER WINDOW SASH AT 2ND WINDOW FROM NORTH. AT LOBBY, 1st STORY |
| Class B | Closed | 5MN | Nov 6, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE HOLE A SINK BASE CABINET IN THE KITCHEN LOCATED AT APT 5MN, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2BN | Oct 30, 2023 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... NORTH WALL (APPRX 4 SQ FT) AND CEILING (APPROXIMATELY 4 SQ FT) CLOSET IN THE PRIVATE HALLWAY LOCATED AT APT 2BN, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 16067214 ISSUED 29-JUN-23 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 6DS | Oct 26, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE OUTLET AND SWITCH ( SWITCH AND OUTLET ARE CONNECTED IN THE ENTIRE APARTMENT LOCATED AT APT 6DS, 6th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTH |
| Class B | Closed | 6DS | Oct 26, 2023 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 6DS, 6th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTH |
| Class B | Closed | 6DS | Oct 26, 2023 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 6DS, 6th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTH |
| Class B | Closed | 6DS | Oct 26, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOM RETURN SYSTEM FROM VESTIBULE (VESTIBULE TO 1ST STORY PUBLIC HALL) TO EAST WALL IN THE FOYER LOCATED AT APT 6DS, 6th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTH |
| Class B | Closed | 6CN | Oct 18, 2023 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT NORTH WALL APPRX 12 SQ FT IN THE 1st ROOM FROM NORTH LOCATED AT APT 6CN, 6th STORY, 6th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | — | Oct 17, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT MAIL ROOM AT PUBLIC HALL, 1st STORY, SECTION ''SOUTH'' |
| Class B | ClosedRENT IMPAIRING | — | Oct 17, 2023 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING AT PUBLIC HALL, 6th STORY, SECTION ''NORTH/WEST'' |
| Class B | Closed | — | Oct 17, 2023 | NO LIGHT AT ENTRANCE TO BUILDING · ARTIFICIAL LIGHTING§ 27-2040 ADM CODE PROVIDE ADEQUATE LIGHTING AT OR NEAR THE OUTSIDE OF THE FRONT ENTRANCEWAY OF THE BUILDING AND KEEP SAME BURNING FROM SUNSET EVERY DAY TO SUNRISE ON THE DAY FOLLOWING 200 WATTS INCANDESCENT OR EQUIVALENT |
| Class B | ClosedRENT IMPAIRING | — | Oct 17, 2023 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING AT PUBLIC HALL, 6th STORY, SECTION ''SOUTH/WEST'' |
| Class B | Closed | — | Oct 17, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE THE FIRE RETARDANT MATEERIAL AT CEILING AT PUBLIC HALL, 6th STORY, SECTION ''SOUTH/WEST'' |
| Class B | Closed | — | Oct 17, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FLASHING AT PARAPET WALL AT ROOF AT NORTH , SECTION ''SOUTH'' |
| Class B | Closed | 1AS | Oct 17, 2023 | REMOVE BARS OR GATES FROM NON FIRE ESCAPE WINDOW · EGRESS§ 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM AT LEAST 1 WINDOW OR PROVIDE APPROVED TYPE GATE IN THE ENTIRE APARTMENT LOCATED AT APT 1AS, 1st STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH/EAST'' |
| Class B | Closed | — | Oct 17, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 2nd STORY, SECTION ''SOUTH/WEST'' |
| Class B | Closed | — | Oct 17, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT 2ND BULKHEAD FROM NORTH AT PUBLIC HALL, 6th STORY, SECTION ''NORTH/WEST'' |
| Class B | Closed | — | Oct 17, 2023 | REPAIR BROKEN PAYING · PAVING AND GRADING§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE PAVING AT SOUTH YARD |
| Class B | Closed | — | Oct 17, 2023 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 2nd STORY, SECTION ''SOUTH/WEST'' |
| Class B | Closed | 3FS | Oct 17, 2023 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE HANDLE AT WATER DIVERTER IN BATHTUB IN THE BATHROOM LOCATED AT APT 3FS, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''SOUTH/WEST'' |
| Class B | Closed | 3AS | Oct 17, 2023 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 2nd BATHROOM FROM NORTH LOCATED AT APT 3AS, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''SOUTH/EAST'' |
| Class B | Closed | 6NS | Oct 17, 2023 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT LOWER SASH AT WINDOW IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 6NS, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''SOUTH/WEST'' |
| Class B | ClosedRENT IMPAIRING | — | Oct 17, 2023 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT 2ND BULKHEAD FROM NORTH AT PUBLIC HALL, 6th STORY, SECTION ''NORTH/WEST'' |
| Class B | Closed | — | Oct 17, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FLASHING AT 2ND PARAPET WALL FROM NORTH AT ROOF , SECTION ''NORTH/WEST'' |
| Class B | Closed | — | Oct 17, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE THE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 6th STORY, SECTION ''NORTH/WEST'' |
| Class B | Closed | — | Oct 17, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY, SECTION ''NORTH/EAST'' |
| Class B | Closed | — | Oct 17, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FLASHING AT PARAPET WALL AT ROOF AT EAST , SECTION ''SOUTH'' |
| Class B | Closed | 6RS | Oct 16, 2023 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING AND NORTH WALL IN THE 4th ROOM FROM EAST LOCATED AT APT 6RS, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''SOUTH/EAST'' |
| Class B | Closed | 6CS | Oct 16, 2023 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND EAST WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 6CS | Oct 16, 2023 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND EAST WALL IN THE 1st ROOM FROM EAST AT CENTER LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 6CS | Oct 16, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WINDOW LOWER SASH COUNTER BALANCE IN THE 4th ROOM FROM EAST LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 6CS | Oct 16, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES AT SHOWER STALL IN THE 1st BATHROOM FROM EAST LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | 6CS | Oct 16, 2023 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING IN THE 1st BATHROOM FROM EAST LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1FN | Oct 16, 2023 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 1FN, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION AT NORTH |
| Class B | Closed | 6CS | Oct 16, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WINDOW LOWER SASH COUNTER BALANCE IN THE 3rd BATHROOM FROM EAST LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 6CS | Oct 16, 2023 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR NORTH CLOSET CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | 6RS | Oct 16, 2023 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING IN THE 4th ROOM FROM EAST LOCATED AT APT 6RS, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''SOUTH/EAST'' |
| Class B | Closed | 6CS | Oct 16, 2023 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | 6CS | Oct 16, 2023 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1LN | Oct 16, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE THE ROTTED WOOD VANITY BASE CABINET IN THE BATHROOM LOCATED AT APT 1LN, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH/WEST'' |
| Class B | Closed | 1LN | Oct 16, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WOOD DOOR AT ENTRANCE IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 1LN, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH/WEST'' |
| Class B | Closed | 1LN | Oct 16, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT FLOOR IN THE KITCHEN LOCATED AT APT 1LN, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH/WEST'' |
| Class B | Closed | 6CS | Oct 16, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WINDOW LOWER SASH COUNTER BALANCE IN THE 1st ROOM FROM EAST AT CENTER LOCATED AT APT 6CS, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |