| Class C | ClosedRENT IMPAIRING | 5A | Feb 25, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Feb 23, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET AT FIRE STAIR DOOR A AT PUBLIC HALL, 5th STORY |
| Class C | Open | 8E | Feb 23, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 8E, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Open | 8E | Feb 23, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 8E, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 15F | Feb 20, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 10 SQFT AND LESS THAN 30 SQFT AT CEILIING IN THE BATHROOM LOCATED AT APT 15F, 14th STORY, SECTION ''530'' |
| Class C | ClosedRENT IMPAIRING | 16C | Feb 20, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 16C, 15th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''530'' |
| Class C | Closed | 15F | Feb 20, 2026 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF UNCAPPED GASLINE AT EAST WALL IN THE KITCHEN LOCATED AT APT 15F, 14th STORY, SECTION ''530'' |
| Class B | Open | 8J | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 8J, 8th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 8G | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8G, 8th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class C | Open | — | Feb 10, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE ARM CLOSER DEVICE AT BUILDING ENTRANCE DOOR (FROM ENTRANCE TO VESTIBULE) , 1st STORY, SECTION ''540'' |
| Class B | Open | 10J | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 10J, 10th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 10J | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 10J, 10th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class B | Open | 9D | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 9D, 9th STORY, 4th APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class B | Open | 9E | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 9E, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class B | Open | 8B | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''540'' |
| Class C | Closed | — | Feb 10, 2026 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF GAS POWERED MOTORCYCLE AT PUBLIC HALL, 8th STORY, SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 9F | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 9F, 9th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class B | Closed | 9D | Feb 10, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ.FT. AT CEILING AND NORTH WALL IN THE BATHROOM LOCATED AT APT 9D, 9th STORY, 4th APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 9E | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 9E, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class C | Open | 9J | Feb 10, 2026 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 9J, 9th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 9J | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 9J, 9th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 9D | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 9D, 9th STORY, 4th APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class C | Closed | 9K | Feb 10, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MORTISE LOCK AT DOOR IN THE ENTRANCE LOCATED AT APT 9K, 9th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | Open | 9F | Feb 10, 2026 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 9F, 9th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class B | Open | 9J | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 9J, 9th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class B | Open | 9F | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 9F, 9th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class C | Closed | 9F | Feb 10, 2026 | PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 9F, 9th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class C | Closed | 8J | Feb 10, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 8J, 8th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 9K | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 9K, 9th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | Closed | 8B | Feb 10, 2026 | PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''540'' |
| Class B | Open | 8G | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 8G, 8th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class C | Closed | 8K | Feb 10, 2026 | PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 8K, 8th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | Open | 8G | Feb 10, 2026 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 8G, 8th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 8B | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 8K | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8K, 8th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | Closed | 8G | Feb 10, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 8G, 8th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''540'' |
| Class B | Open | 9K | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 9K, 9th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | Open | 9K | Feb 10, 2026 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 9K, 9th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | ClosedRENT IMPAIRING | 8J | Feb 10, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8J, 8th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class B | Open | 8K | Feb 10, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 8K, 8th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540'' |
| Class C | Open | 8B | Feb 10, 2026 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''540'' |
| Class B | Open | 18H | Feb 4, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ.FT. AT EAST WALL IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 18H, 18th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''540'' ORIGINAL VIOLATION 18283510 ISSUED 01-OCT-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b). |
| Class B | Open | 18H | Feb 4, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ,FT. AST EAST WALL IN THE 3rd ROOM FROM NORTH LOCATED AT APT 18H, 18th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''540'' ORIGINAL VIOLATION 18283513 ISSUED 01-OCT-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b). |
| Class C | Closed | — | Feb 4, 2026 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM |
| Class C | ClosedRENT IMPAIRING | 4G | Feb 4, 2026 | INADEQUATE HEAT · HEAT AND HOT WATER§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 4G, 4th STORY, 4th APARTMENT FROM SOUTH AT WEST |
| Class C | ClosedRENT IMPAIRING | 4G | Feb 4, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 4G, 4th STORY, 4th APARTMENT FROM SOUTH AT WEST |
| Class C | Open | 12B | Feb 3, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 14 SQ FT AT SOUTH ,EAST WALL AND CEILING IN THE BATHROOM LOCATED AT APT 12B, 12th STORY, 1st APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 18487780 ISSUED 29-NOV-25 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE 27-2017.3a(5)(a) or (b). |
| Class C | ClosedRENT IMPAIRING | 18C | Feb 3, 2026 | INADEQUATE HOT WATER SUPPLY (VOLUME) · WATER SUPPLY§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES .. IN THE ENTIRE APARTMENT LOCATED AT APT 18C, 17th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | ClosedRENT IMPAIRING | 18C | Feb 3, 2026 | INADEQUATE COLD WATER · WATER SUPPLY§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF COLD WATER FOR THE FIXTURES ... IN THE ENTIRE APARTMENT LOCATED AT APT 18C, 17th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Jan 30, 2026 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM |