| Class C | Closed | — | Jun 3, 2016 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING GLASS PANE AT BUILDING ENTRANCE DOOR TO PUBLIC HALL AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Jun 3, 2016 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE WATER TUBES AT BOILER AT BOILER ROOM |
| Class C | Closed | — | Mar 18, 2016 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (PUBLIC AREA) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) THROUGHOUT THE PUBLIC AREAS IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. AT PUBLIC HALL |
| Class C | Closed | — | Mar 18, 2016 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING FIXED WIRE GLASS WINDOW PANE AT PUBLIC HALL, 4th STORY |
| Class C | Closed | 1B | Mar 7, 2016 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR AT BATHTUB IN THE BATHROOM LOCATED AT APT 1B, 1st STORY, 4th APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 1B | Mar 7, 2016 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE AIR VALVE AT RADIATOR (HEAT SEASON, STEAM LEAKS) IN THE 3rd ROOM FROM EAST AT NORTH LOCATED AT APT 1B, 1st STORY, 4th APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 2A | Nov 24, 2015 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | — | Sep 30, 2015 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM BOILER ROOM DOOR LOCKED AT BASEMENT |
| Class C | ClosedRENT IMPAIRING | 5C | Sep 30, 2015 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 5C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 5D | Sep 23, 2015 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE BATHROOM LOCATED AT APT 5D, 5th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Closed | 5D | Sep 23, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK ,, CEILING IN THE BATHROOM LOCATED AT APT 5D, 5th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Closed | 5G | Aug 17, 2015 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF SCALDING HOT WATER EXCEEDING 130 DEGREES IN THE KITCHEN LOCATED AT APT 5G, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH'' |
| Class C | Closed | 5G | Aug 17, 2015 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF LOCKABLE SLIDE BOLT INSTALLED INTERIOR IN THE ENTRANCE LOCATED AT APT 5G, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH'' |
| Class C | Closed | 5G | Aug 17, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 5G, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH'' |
| Class C | Closed | 4C | Jul 23, 2015 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 0; WG TO REPLACE = 0; WG TO REPAIR = 3; SECURE AIR CONDITIONAR WITH ONE WAY SCREW TOTAL=3 IN THE ENTIRE APARTMENT LOCATED AT APT 4C, 4th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH |
| Class C | Closed | 1E | Jul 23, 2015 | REMOVE DOUBLE CYLINDER LOCK · EGRESS§ 27-2005, 2007 HMC: REMOVE THE ILLEGAL DOUBLE CYLINDER KEY OPERATED LOCKING DEVICE AT DOOR .. IN THE ENTIRE APARTMENT LOCATED AT APT 1E, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTH |
| Class C | Closed | — | Jul 10, 2015 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF DISCARTED REFRIGERATOR WITH DOORS INTACT , 1st STORY, SECTION AT SOUTH |
| Class C | Closed | — | Jun 11, 2015 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM BOILER ROOM DOOR LOCKED AT BASEMENT |
| Class C | ClosedRENT IMPAIRING | 5E | Jun 11, 2015 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 5E, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | ClosedRENT IMPAIRING | 4G | May 18, 2015 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT GAS RANGE IN THE KITCHEN LOCATED AT APT 4G, 4th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class C | Closed | — | Apr 13, 2015 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE 1 BROKEN WIRE GLASS LITE AT THE STATIONARY WINDOW AT PUBLIC HALL, 3rd STORY, SECTION AT NORTH |
| Class C | Closed | 6C | Mar 13, 2015 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... ON THE CEILING,NORTH,SOUTH,EAST AND WEST WALLS IN THE BATHROOM FROM EAST LOCATED AT APT 6C, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH |
| Class C | Closed | — | Feb 5, 2015 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING HANDRAIL AT PUBLIC HALL STAIRS, 1st STORY, SECTION AT SOUTH |
| Class C | Closed | — | Feb 5, 2015 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING HANDRAILS AT PUBLIC HALL STAIRS, 1st STORY, SECTION AT NORTH |
| Class C | ClosedRENT IMPAIRING | 2D | Jan 28, 2015 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Closed | 2D | Jan 28, 2015 | PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | ClosedRENT IMPAIRING | 2C | Jan 28, 2015 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 2C | Jan 28, 2015 | PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 5H | Dec 29, 2014 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | ClosedRENT IMPAIRING | 3D | Dec 26, 2014 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Closed | 3D | Dec 26, 2014 | PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Closed | — | Nov 19, 2014 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE LEAKY BOILER IN THE BOILER ROOM AT BASEMENT |
| Class C | ClosedRENT IMPAIRING | — | Nov 19, 2014 | REMOVE ACCUMULATION OF RUBBISH, WATER & DISINFECT · CLEANING§ 27-2010, 2011, 2012 ADM CODE CLEANSE AND DISINFECT TO THE SATISFACTION OF THIS DEPARTMENT AFTER REMOVING THE ACCUMULATION OF WATER ON THE FLOOR AT BOILER ROOM AT BASEMENT |
| Class C | Closed | 6H | Nov 19, 2014 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF SCALDING HOT WATER EXCEEDING 130 DEGREES AT KITCHEN AND BATHROOM FIXTURES LOCATED AT APT 6H, 6th STORY, APARTMENT AT SOUTH , SECTION AT SOUTH |
| Class C | Closed | — | Oct 27, 2014 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCK AT VESTIBULE ENTRANCE DOOR , 1st STORY |
| Class C | Closed | — | Oct 15, 2014 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE CRACKED GLASS ENTRANCE DOOR TO THE BUILDING AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Jul 30, 2014 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE DOOR LOCK AT BUILDING ENTRANCE , 1st STORY |
| Class C | Closed | — | May 30, 2014 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE HEAVY DUTY LOCK AND LATCH SET AT THE VESTIBUL DOOR TO THE BUILDING , 1st STORY |
| Class C | ClosedRENT IMPAIRING | 4C | May 30, 2014 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 4C, 4th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH |
| Class C | Closed | — | May 30, 2014 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM BOILER ROOM DOOR LOCKED AT BASEMENT |
| Class C | ClosedRENT IMPAIRING | 5C | May 30, 2014 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 5C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH |
| Class C | Closed | — | May 8, 2014 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE BUILDING ENTRANCE DOOR LOCK ASSEMBLY ; FROM VESTIBULE INTO THE PUBLIC HALL , 1st STORY |
| Class C | Closed | 5C | Mar 25, 2014 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING IN THE BATHROOM LOCATED AT APT 5C, 5th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Closed | — | Mar 25, 2014 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCK AT BUILDING ENTRANCE DOOR , 1st STORY |
| Class C | Closed | 5C | Mar 20, 2014 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE KITCHEN LOCATED AT APT 5C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH |
| Class C | Closed | 5C | Mar 20, 2014 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF SCALDING HOT WATER EXCEEDING 130 DEG. IN THE ENTIRE APARTMENT LOCATED AT APT 5C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH |
| Class C | Closed | 4C | Mar 13, 2014 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT 1st CLOSET FROM SOUTH AT WEST WALL CEILING, 1st CLOSET FROM SOUTH AT WEST WALL WALL IN THE 1st PRIVATE HALLWAY FROM NORTH LOCATED AT APT 4C, 4th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 4C | Mar 13, 2014 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 3; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 4C, 4th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | ClosedRENT IMPAIRING | 3E | Mar 6, 2014 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 3E | Mar 6, 2014 | PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH |