| Class B | Open | 3E | Nov 13, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 3E, 4th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 3E | Nov 13, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND SOUTH WALL IN THE KITCHEN LOCATED AT APT 3E, 4th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Open | 3G | Oct 30, 2025 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF KEY OPERATED LOCK AT DOOR LEADING TO ROOM WITH FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST LOCATED AT APT 3G, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class C | Closed | 3G | Oct 30, 2025 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1, WG TO REPLACE = 0, WG TO REPAIR = 0 IN THE ENTIRE APARTMENT LOCATED AT APT 3G, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class A | Open | 3G | Oct 30, 2025 | FILE PLANS OR RESTORE · ALTERATIONS§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION CONSISTING OF DRY WALL PARTITION ERECTED FROM FLOOR TO CEILING AND HENCE CREATING ADDITIONAL ROOM AND REDUCING NATURAL LIGHT AND VENTILATION IN THE 2nd ROOM FROM EAST AT NORTH LOCATED AT APT 3G, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class A | Open | — | Oct 22, 2025 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT SOUTH WALL AT PUBLIC HALL, 1st STORY |
| Class B | Open | — | Oct 22, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT SOUTH WALL AT PUBLIC HALL, 1st STORY |
| Class C | Open | — | Oct 20, 2025 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY |
| Class B | Open | 4C | Oct 20, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 4C, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 4B | Oct 20, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4B, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 4B | Oct 20, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4B, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | OpenRENT IMPAIRING | 4C | Oct 20, 2025 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 4C, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class C | Open | — | Oct 20, 2025 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM LOCKED DOOR AT BOILER ROOM |
| Class B | OpenRENT IMPAIRING | 4C | Oct 20, 2025 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 4C, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class C | ClosedRENT IMPAIRING | 4B | Oct 20, 2025 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 4B, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | OpenRENT IMPAIRING | 1E | Oct 17, 2025 | INADEQUATE HOT WATER SUPPLY (VOLUME) · WATER SUPPLY§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES AT SINK IN THE KITCHEN LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 17, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT WEST WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class A | Open | 1E | Oct 17, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SASH LOCK AT FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 17, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGHT FIXTURE AT CEILING IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT EAST, SOUTH, AND WEST WALLS IN THE PRIVATE HALLWAY LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT NORTH AND SOUTH WALLS IN THE BATHROOM LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Open | — | Oct 14, 2025 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH AT 2ND WINDOW FROM NORTH AT EAST IN THE 4th ROOM FROM EAST AT SOUTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH AT 1ST WINDOW FROM NORTH AT EAST IN THE 4th ROOM FROM EAST AT SOUTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH AT 1ST WINDOW FROM NORTH AT EAST IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Open | 1E | Oct 14, 2025 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Open | 1E | Oct 14, 2025 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR AT BASE CABINET AT SINK IN THE KITCHEN LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH AT 2ND WINDOW FROM WEST AT NORTH IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | OpenRENT IMPAIRING | 1E | Oct 14, 2025 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE KITCHEN LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT NORTH WALL IN THE BATHROOM LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH AT 1ST WINDOW FROM SOUTH AT WEST IN THE 2nd ROOM FROM EAST AT NORTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT EAST AND SOUTH WALL IN THE 2nd ROOM FROM EAST AT NORTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT WASHBASIN IN THE BATHROOM LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING, SOUTH, AND WEST WALLS IN THE FOYER LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BUZZER AND RETURN VOICE SYSTEM FROM BUILDING VESTIBULE UP TO PANEL AT SOUTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1E | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH AT 2ND WINDOW FROM SOUTH AT WEST IN THE 2nd ROOM FROM EAST AT NORTH LOCATED AT APT 1E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | — | Oct 9, 2025 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PLEXIGLASS INSTALLED AT BUILDING ENTRANCE DOOR (FROM STREET TO VESTIBULE) , 1st STORY |
| Class B | Open | — | Oct 9, 2025 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE APPROVED GLASS AT BUILDING ENTRANCE DOOR (FROM STREET TO VESTIBULE) , 1st STORY |
| Class A | Open | — | Oct 9, 2025 | IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR , FRAME MISSING AT PUBLIC HALL, 1st STORY |
| Class B | Open | — | Oct 9, 2025 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE APPROVED GLASS AT DOOR (FROM VESTIBULE TO PUBLIC HALL) , 1st STORY |
| Class A | Open | — | Oct 9, 2025 | POST SIGN INDICATING NAME AND ADDRESS OF JANITOR, ETC. · POSTING/SIGNAGE§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORY |
| Class C | Open | — | Oct 9, 2025 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM , SIGN MISSING AT PUBLIC HALL, 1st STORY |
| Class B | Open | — | Oct 9, 2025 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PLEXIGLASS INSTALLED AT DOOR (FROM VESTIBULE TO PUBLIC HALL) , 1st STORY |
| Class B | Open | — | Oct 9, 2025 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF HOUSEHOLD ITEMS AT FIRE ESCAPE, NORTH EXTERIOR WALL AT 5TH STORY |
| Class C | OpenRENT IMPAIRING | 2D | Oct 8, 2025 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2D, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Open | 3G | Oct 8, 2025 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF KEY OPERATED LOCK AT DOOR LEADING TO ROOM WITH FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST LOCATED AT APT 3G, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class A | Open | 3G | Oct 8, 2025 | FILE PLANS OR RESTORE · ALTERATIONS§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION CONSISTING OF DRY WALL PARTITION ERECTED FROM FLOOR TO CEILING AND HENCE CREATING ADDITIONAL ROOM AND REDUCING NATURAL LIGHT AND VENTILATION IN THE 2nd ROOM FROM EAST AT NORTH LOCATED AT APT 3G, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |