| Class C | Closed | — | Aug 22, 2025 | DOOR NOT SELF-CLOSING · EGRESS§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING CONSISTING OF METAL STRING AT BUILDING ENTRANCE DOOR |
| Class A | Closed | — | Aug 20, 2025 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING AND ALL WALLS IN BULKHEAD |
| Class C | Closed | — | Aug 20, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR AND FRAME AT VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Aug 20, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOCKING DEVICE AT BUILDING FRONT ENTRANCE DOOR , 1st STORY |
| Class B | Closed | — | Aug 20, 2025 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF FLOWER POTS AT 2ND AND 3RD STORY BALCONY AT BUILDING REAR |
| Class B | Closed | — | Aug 20, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS IN BULKHEAD |
| Class C | Closed | — | Aug 20, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT BULKHEAD DOOR |
| Class B | Closed | — | Aug 15, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT BUILDING ENTRANCE DOOR |
| Class C | Closed | — | Aug 15, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET AT BUILDING ENTRANCE DOOR |
| Class B | Closed | 2C | Aug 8, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | AB | Aug 8, 2025 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT AB, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | AB | Aug 8, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE LOCATED AT APT AB, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 2C | Aug 8, 2025 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | AB | Aug 8, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WARPED AND ROTTED WOOD FLOOR IN THE PRIVATE HALLWAY LOCATED AT APT AB, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | C | Aug 8, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT SOUTH WALL IN THE BATHROOM LOCATED AT APT C, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | AB | Aug 8, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE LOCATED AT APT AB, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2C | Aug 8, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 2C | Aug 8, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 2C | Aug 8, 2025 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | C | Aug 8, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE KITCHEN LOCATED AT APT C, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | C | Aug 8, 2025 | REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED WIRES AT BREAKER BOX AT WEST WALL IN THE KITCHEN LOCATED AT APT C, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | C | Aug 8, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT C, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | — | Aug 6, 2025 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES FLOWER POTS AT 2ND STORY AND 4TH STORY BALCONIES AT REAR YARD AT FIRE ESCAPE |
| Class C | Closed | — | Aug 6, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE THE LOCK AND ASSEMBLY AT STREET ENTRANCE DOOR TO VESTIBULE , 1st STORY |
| Class B | Closed | 2B | Aug 4, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER WINDOW SHASH IN THE KITCHEN LOCATED AT APT 2B, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Aug 4, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT BUILDING ENTRANCE , 1st STORY |
| Class B | Closed | — | Aug 4, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AT BUILDING ENTRANCE DOOR , 1st STORY |
| Class B | Closed | BASEME | Jul 31, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE DOOR AT WASH BASIN CABINET IN THE BATHROOM LOCATED AT BSMT-APT BASEME, 1st BSMT-APT FROM NORTH AT EAST |
| Class B | Closed | — | Jul 31, 2025 | REMOVE VERMIN · EXTERMINATION & RODENT ERADICATION566 (B) 27-2021.4 HMC: ABATE THE NUISANCE CONSISTING OF PESTS. EVIDENCE OF FLIES 1st YARD FROM EAST |
| Class C | Closed | BASEME | Jul 31, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILE IN THE 1st ROOM FROM NORTH LOCATED AT BSMT-APT BASEME, 1st BSMT-APT FROM NORTH AT EAST |
| Class A | Closed | — | Jul 31, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ... AT LOBBY |
| Class B | ClosedRENT IMPAIRING | — | Jul 31, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF GARBAGE BAGS AND CARDBOARD BOXES 1st YARD FROM EAST |
| Class C | Closed | BASEME | Jul 31, 2025 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT BSMT-APT BASEME, 1st BSMT-APT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | 2C | Jul 28, 2025 | DISCONTINUE SINGLE ROOM OCCUPANCY · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS§ 27-2077, 2078 ADM CODE DISCONTINUE UNLAWFUL USE FOR SINGLE ROOM OCCUPANCY PURPOSES , IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 2C | Jul 28, 2025 | DISCONTINUE SINGLE ROOM OCCUPANCY · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS§ 27-2077, 2078 ADM CODE DISCONTINUE UNLAWFUL USE FOR SINGLE ROOM OCCUPANCY PURPOSES , IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 2C | Jul 28, 2025 | DISCONTINUE SINGLE ROOM OCCUPANCY · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS§ 27-2077, 2078 ADM CODE DISCONTINUE UNLAWFUL USE FOR SINGLE ROOM OCCUPANCY PURPOSES , IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 2C | Jul 28, 2025 | DISCONTINUE SINGLE ROOM OCCUPANCY · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS§ 27-2077, 2078 ADM CODE DISCONTINUE UNLAWFUL USE FOR SINGLE ROOM OCCUPANCY PURPOSES , IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 2C | Jul 24, 2025 | DISCONTINUE SINGLE ROOM OCCUPANCY · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS§ 27-2077, 2078 ADM CODE DISCONTINUE UNLAWFUL USE FOR SINGLE ROOM OCCUPANCY PURPOSES AT TIME OF INSPECTION,INSPECTOR OBSERVED THAT A CLASS ''A'' APARTMENT WITH FOUR BEDROOMS WAS CONVERTED AND BEING OCCUPIED AS AN ILLEGAL SROTENANT STATED THAT ALL FOUR BEDROOMS WERE RENTED TO INDIVIDUALS THAT WERE NOT RELATED, EACH PAY THIER RENT WEEKLY, THERE WAS NO POWER SUPPLIED TO ENTIRE APARTMENT. INSPECTOR RECOMMENDS ECB ACTIONS, BUT NO VACATE IS WARRANTED DUE TO 2ND MEANS OF EGRESS BEING ACCESSIBLE TO ALL OCCUPANTS. DOB WAS COTACTED BY INSPECTOR COMPLAINT NUMBER 2420591 IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 2C | Jul 24, 2025 | DISCONTINUE SINGLE ROOM OCCUPANCY · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS§ 27-2077, 2078 ADM CODE DISCONTINUE UNLAWFUL USE FOR SINGLE ROOM OCCUPANCY PURPOSES AT TIME OF INSPECTION,INSPECTOR OBSERVED THAT A CLASS ''A'' APARTMENT WITH FOUR BEDROOMS WAS CONVERTED AND BEING OCCUPIED AS AN ILLEGAL SROTENANT STATED THAT ALL FOUR BEDROOMS WERE RENTED TO INDIVIDUALS THAT WERE NOT RELATED, EACH PAY THIER RENT WEEKLY, THERE WAS NO POWER SUPPLIED TO ENTIRE APARTMENT. INSPECTOR RECOMMENDS ECB ACTIONS, BUT NO VACATE IS WARRANTED DUE TO 2ND MEANS OF EGRESS BEING ACCESSIBLE TO ALL OCCUPANTS. DOB WAS COTACTED BY INSPECTOR COMPLAINT NUMBER 2420591 IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 2C | Jul 24, 2025 | DISCONTINUE SINGLE ROOM OCCUPANCY · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS§ 27-2077, 2078 ADM CODE DISCONTINUE UNLAWFUL USE FOR SINGLE ROOM OCCUPANCY PURPOSES AT TIME OF INSPECTION,INSPECTOR OBSERVED THAT A CLASS ''A'' APARTMENT WITH FOUR BEDROOMS WAS CONVERTED AND BEING OCCUPIED AS AN ILLEGAL SROTENANT STATED THAT ALL FOUR BEDROOMS WERE RENTED TO INDIVIDUALS THAT WERE NOT RELATED, EACH PAY THIER RENT WEEKLY, THERE WAS NO POWER SUPPLIED TO ENTIRE APARTMENT. INSPECTOR RECOMMENDS ECB ACTIONS, BUT NO VACATE IS WARRANTED DUE TO 2ND MEANS OF EGRESS BEING ACCESSIBLE TO ALL OCCUPANTS. DOB WAS COTACTED BY INSPECTOR COMPLAINT NUMBER 2420591 IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 2C | Jul 24, 2025 | DISCONTINUE SINGLE ROOM OCCUPANCY · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS§ 27-2077, 2078 ADM CODE DISCONTINUE UNLAWFUL USE FOR SINGLE ROOM OCCUPANCY PURPOSES AT TIME OF INSPECTION,INSPECTOR OBSERVED THAT A CLASS ''A'' APARTMENT WITH FOUR BEDROOMS WAS CONVERTED AND BEING OCCUPIED AS AN ILLEGAL SROTENANT STATED THAT ALL FOUR BEDROOMS WERE RENTED TO INDIVIDUALS THAT WERE NOT RELATED, EACH PAY THIER RENT WEEKLY, THERE WAS NO POWER SUPPLIED TO ENTIRE APARTMENT. INSPECTOR RECOMMENDS ECB ACTIONS, BUT NO VACATE IS WARRANTED DUE TO 2ND MEANS OF EGRESS BEING ACCESSIBLE TO ALL OCCUPANTS. DOB WAS COTACTED BY INSPECTOR COMPLAINT NUMBER 2420591 IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 2C | Jul 23, 2025 | PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES TO ALL OUTLETS SWITCHES AND LIGHT FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2C | Jul 21, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER THE CEILING IN THE BATHROOM LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class A | Closed | 2C | Jul 21, 2025 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE BATHROOM , THE BATHROOM , THE KITCHENETTE LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2C | Jul 21, 2025 | PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES ,,, IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2C | Jul 21, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MORTISE LOCK AT DOOR IN THE ENTRANCE LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2C | Jul 21, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THEN 10 SQ. FT. AT NORTH WALL IN THE BATHROOM LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2C | Jul 21, 2025 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION DRAIN PIPE AT WASH BASIN IN THE BATHROOM LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2C | Jul 18, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCES LOWER SASH IN THE BATHROOM LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 2C | Jul 18, 2025 | PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT CEILING,OUTLETS AND WALL SWITCHES THROUGH-OUT IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |