| Class B | Closed | — | Jul 23, 2025 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE RE-ENTRY BY MEAND OF UNLOCKABLE SLIDE BOLT OR HOOK INSTALLED ON DOOR THAT ALLOWS RE-ENTRY FROM ROOF TO PUBLIC HALL AT 1st PUBLIC HALL BULKHEAD FROM NORTH, 5th STORY, SECTION ''NORTH'' |
| Class B | OpenRENT IMPAIRING | 4F | Jul 23, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF DRESSER BLOCKING EGGRESS TO FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''NORTH'' |
| Class B | Closed | — | Jul 23, 2025 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE RE-ENTRY BY MEAND OF UNLOCKABLE SLIDE BOLT OR HOOK INSTALLED ON DOOR THAT ALLOWS RE-ENTRY FROM ROOF TO PUBLIC HALL AT 2nd PUBLIC HALL BULKHEAD FROM NORTH, 5th STORY, SECTION ''SOUTH'' |
| Class B | Closed | 2E | Jul 18, 2025 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF KEY OPERATED LOCK AT DOOR LEADING TO FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST LOCATED AT APT 2E, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | SN | Jul 17, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT SN, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | SN | Jul 17, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT SN, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | — | May 30, 2025 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE WIRE MESH AT SKYLIGHT AT 1st PUBLIC HALL FROM NORTH, 5th STORY |
| Class B | Closed | 2A | Apr 29, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 2A | Apr 29, 2025 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING SADDLE AT ENTRANCE IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 2A | Apr 29, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Open | 2A | Apr 29, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE NORTH WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 5H | Apr 23, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE FOYER LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Closed | 5H | Apr 23, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE RUBBER GASKETS AT REFRIGERATOR IN THE KITCHEN LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Open | 5H | Apr 23, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE 4th ROOM FROM EAST LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | ClosedRENT IMPAIRING | 5H | Apr 23, 2025 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK ABOVE CEILING IN THE FOYER LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Closed | 5H | Apr 23, 2025 | ADJUST DOOR TO PREVENT GAP - FIRE CODE/EGRESS · EGRESS28 RCNY § 25-171; & 67 (7)(B) MDL; NYC FIRE CODE § 703.1.3; NYC FIRE CODE § 703.2: ADJUST DOOR TO PREVENT GAPS BETWEEN THE TOP AND SIDE EDGES OF DOOR AND DOOR JAMB EXCEEDING THE MAXIMUM ALLOWABLE CLEARANCE OF 1/8 OF AN INCH AND MAXIMUM ALLOWABLE CLEARANCE OF 3/4 OF AN INCH BETWEEN THE DOOR BOTTOM AND SILL AT 2 INCH GAP AT BOTTOM OF DOOR IN THE ENTRANCE LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Closed | 5H | Apr 23, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Closed | 5H | Apr 23, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Closed | — | Apr 18, 2025 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE WIRED MESH UNDER SKYLIGHT AT 1st PUBLIC HALL BULKHEAD FROM NORTH |
| Class B | Open | 2A | Feb 10, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THEN 10 SQ FT AT WEST WALL CEILING IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 17337693 ISSUED 10-OCT-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 5E | Jan 6, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CRACKED AND LOOSE MARBLE SADDLE AT ENTRANCE THRESHOLD IN THE KITCHEN LOCATED AT APT 5E, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Closed | 5E | Jan 6, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE SEPARATING WOOD FLOOR ( BY RADIATOR) IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 5E, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Closed | 4F | Dec 17, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 3D | Nov 26, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THEN 10 SQ FEET AT CEILING IN THE KITCHEN LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 17139563 ISSUED 24-JUL-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Open | 3D | Nov 26, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THEN 10 SQ FT AT WEST WALL IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 17139558 ISSUED 24-JUL-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 2E | Nov 4, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 2E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Closed | 2E | Nov 4, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 2E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Closed | 2E | Nov 4, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 2E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Closed | 2E | Nov 4, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2E, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 4F | Oct 25, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC WALL TILES AT BATHTUB IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''NORTH'' |
| Class B | Closed | 2A | Oct 15, 2024 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE SINK/BASE CABINET IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 2A | Oct 11, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 2F | Oct 9, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 2F, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2F | Oct 9, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 2F, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | — | Aug 29, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING 4TH METAL BALUSTER UP FROM BOTTOM AT PUBLIC HALL STAIRS, 5th STORY |
| Class B | Open | — | Aug 29, 2024 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE NORTH NEWEL POST CAP AT PUBLIC HALL STAIRS, 3rd STORY |
| Class B | Closed | — | Aug 29, 2024 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF A HANGING WINDOW GUARD AT 4TH WINDOW FROM SOUTH, 3RD STORY.(OVER BUILDING FRONT ENTRANCE) |
| Class B | Closed | — | Aug 29, 2024 | PROVIDE LIGHT - Not Less that 60 Watt incadescent · ARTIFICIAL LIGHTING§ 27-2039 ADM CODE PROVIDE ADEQUATE LIGHT OF NOT LESS THAN 60 WATTS INCANDESCENT OR EQUIVALENT ILLUMINATION LIGHT FIXTURE AT CEILING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 4G | Aug 20, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4G, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''NORTH'' |
| Class B | Closed | 5F | Aug 20, 2024 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT DOOR IN THE ENTRANCE LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''NORTH'' |
| Class B | Closed | — | Aug 20, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE THE FIRE RETARDANT PLASTER AT CEILING NORTH SECTION AT PUBLIC HALL, 5th STORY |
| Class B | Closed | 4G | Aug 20, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4G, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''NORTH'' |
| Class B | Closed | 2A | Aug 19, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR .. IN THE ENTIRE APARTMENT LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 2A | Aug 19, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 2A | Aug 19, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE ROTTED WOOD FLOOR IN THE KITCHEN LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 2A | Aug 19, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE ROTTED WOOD FLOOR IN THE PRIVATE HALLWAY LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 2A | Aug 19, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). .. IN THE ENTIRE APARTMENT LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 2A | Aug 19, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CONCEALED AT CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Open | 3D | Jul 29, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND SOUTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 3D | Jul 29, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND NORTH WALL IN THE KITCHEN LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |