| Class B | Closed | 6K | Feb 20, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 6K, 6th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Feb 18, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT BUILDING DOOR (STREET TO VESTIBULE) AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Feb 18, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE ARM CLOSING DEVICE AT BUILDING ENTRANCE DOOR (FROM ENTRANCE TO VESTIBULE) , 1st STORY |
| Class A | Closed | — | Feb 5, 2025 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING SAFETY CAPS/ COVERS FOR ELECTRICAL OUTLETS AT WEST WALL AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 1C | Jan 28, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING AND NORTH WALL (LESS THAN 10 SQ.FT.) IN THE 2nd BATHROOM FROM NORTH LOCATED AT APT 1C, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT WEST ORIGINAL VIOLATION 17305868 ISSUED 27-SEP-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 1C | Jan 22, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... (LESS THAN 10 SQFT) 4 SQFT AT CEILING AND 1 SQFT AT NORTH WALL IN THE BATHROOM LOCATED AT APT 1C, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 17295769 ISSUED 23-SEP-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 5J | Jan 16, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FT ON CEILING AND WEST WALL IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 17277453 ISSUED 17-SEP-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class C | ClosedRENT IMPAIRING | 6K | Jan 16, 2025 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 6K, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3D | Jan 15, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING LESS THAN 10 SQ. FT IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 17276919 ISSUED 16-SEP-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | ClosedRENT IMPAIRING | — | Jan 6, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CHRISTMAS TREE WITH EXTENSION CORD CONNECTED AT 1ST STORY AT PUBLIC HALL |
| Class A | Closed | — | Jan 6, 2025 | IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING FRAME AT 1ST STORY AT PUBLIC HALL |
| Class C | Closed | — | Jan 6, 2025 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING NOTICE AT 1ST STORY AT PUBLIC HALL |
| Class A | Closed | — | Jan 6, 2025 | POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. |
| Class A | Closed | — | Jan 6, 2025 | POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL |
| Class A | Closed | — | Jan 6, 2025 | POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL |
| Class A | Closed | — | Jan 6, 2025 | POST SIGN INDICATING NAME AND ADDRESS OF JANITOR, ETC. · POSTING/SIGNAGE§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL |
| Class A | Closed | — | Jan 6, 2025 | POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING NOTICE AT 1ST STORY AT PUBLIC HALL |
| Class A | Closed | — | Dec 24, 2024 | POST SIGN INDICATING NAME AND ADDRESS OF JANITOR, ETC. · POSTING/SIGNAGE§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Dec 24, 2024 | POST GAS LEAK NOTICE · POSTING/SIGNAGE§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Dec 24, 2024 | POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. |
| Class C | Closed | — | Dec 24, 2024 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Dec 24, 2024 | POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Dec 24, 2024 | POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Dec 24, 2024 | POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Dec 24, 2024 | IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING AT PUBLIC HALL, 1st STORY |
| Class C | ClosedRENT IMPAIRING | 2F | Dec 16, 2024 | INADEQUATE HEAT · HEAT AND HOT WATER§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 2F, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | — | Dec 11, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT BUILDING VESTIBULE DOOR , 1st STORY |
| Class B | Closed | — | Dec 11, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AT BUILDING VESTIBULE DOOR , 1st STORY |
| Class C | ClosedRENT IMPAIRING | BLDG | Dec 2, 2024 | INADEQUATE HEAT · HEAT AND HOT WATER§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT BLDG, 1st STORY |
| Class C | Closed | — | Dec 2, 2024 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM |
| Class C | ClosedRENT IMPAIRING | — | Nov 26, 2024 | REMOVE RODENT · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF RODENTS RAT DROPPINGS AT REAR YARD |
| Class B | Closed | 1C | Nov 21, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ.FT OF MOLD AT CEILING IN THE BATHROOM LOCATED AT APT 1C, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 17135958 ISSUED 23-JUL-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class C | Closed | 1C | Nov 19, 2024 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1C, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | — | Nov 19, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT COMPACTOR CLOSET DOOR AT 6TH STORY |
| Class B | Closed | 1C | Nov 19, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQFT AT CEILING AND NORTH WALL IN THE BATHROOM LOCATED AT APT 1C, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | — | Nov 19, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET AT HOPPER DOOR AT 6TH STORY |
| Class B | Closed | — | Nov 19, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT HOPPER DOOR AT 6TH STORY |
| Class C | Closed | — | Nov 19, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET AT COMPACTOR CLOSET DOOR AT 6TH STORY |
| Class B | ClosedRENT IMPAIRING | 6F | Nov 14, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 6F, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6F | Nov 14, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 6F, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6F | Nov 14, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND NORTH WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 6F, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6F | Nov 14, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 6F, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 6F | Nov 14, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH IN THE ENTRANCE LOCATED AT APT 6F, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6F | Nov 14, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT NORTH WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 6F, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 6F | Nov 14, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL FLOOR TILES AT WALKING AREA CUT HAZARD IN THE PRIVATE HALLWAY LOCATED AT APT 6F, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 4F | Nov 14, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THEN 10 SQ FT AT WEST WALL WEST WALL IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 17115311 ISSUED 15-JUL-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 1C | Nov 7, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE (SPRING BALANCE) LOWER SASH (HARD TO CLOSE) IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 1C, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class A | Closed | 1C | Nov 7, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FT AT CEILING IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 1C, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 1C | Nov 7, 2024 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1C, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6G | Oct 28, 2024 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION WASTELINE AT WASH BASIN IN THE 2nd BATHROOM FROM NORTH LOCATED AT APT 6G, 6th STORY, 4th APARTMENT FROM WEST AT NORTH |