| Class B | Closed | 2D | Oct 21, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). THAT IS MISSING LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 2D | Oct 21, 2019 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR THAT IS MISSING LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 1H | Oct 21, 2019 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING PROXIMATELY 15 SQ FT IN THE BATHROOM LOCATED AT APT 1H, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 1H | Sep 12, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING, SOUTH AND WEST WALLS IN THE BATHROOM LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 1H | Sep 12, 2019 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF FREE STANDING RADIATOR, ( DISCONECTED ) IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 1H | Sep 12, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING IN THE BATHROOM LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 1G | Aug 26, 2019 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOUSEHOLD ITEMS OBSTRUCTING FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1G | Aug 26, 2019 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER SASH AT FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2D | Aug 13, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 2D | Aug 13, 2019 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING APPR. 2 SQ FT , EAST WALL APPR. 4 SQ FT, NORTH WALL 8 SQ FT AND WEST WALL APPR. 2 SQ FT IN THE BATHROOM LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 2D | Aug 13, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT ALL WALLS AND CEILING IN THE BATHROOM LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 2D | Aug 13, 2019 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 2D | Aug 13, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3K | Jul 31, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 3K | Jul 31, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND SOUTH WALL IN THE FOYER LOCATED AT APT 3K, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 3K | Jul 31, 2019 | REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF LIGHT FIXTURE AT CEILING IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 4D | Jul 22, 2019 | PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AN INOPERATING ELECTRIC WALL OUTLET AT THE NORTH WALL IN THE KITCHEN IN THE KITCHEN LOCATED AT APT 4D, 4th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4D | Jul 22, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL TILED WOOD FLOOR IN THE 2nd ROOM FROM EAST LOCATED AT APT 4D, 4th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4D | Jul 22, 2019 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE THE BATHROOM DOOR IN THE BATHROOM LOCATED AT APT 4D, 4th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | — | Jul 22, 2019 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE PUBLIC HALL CEILING , 6th STORY, SECTION ''NORTH'' |
| Class B | Closed | 1H | Jul 22, 2019 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE SPRING BALANCE FOR UPPER AND LOWER SASH WINDOWS IN THE 1st ROOM FROM EAST LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH |
| Class B | Closed | 6I | Jun 3, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 2nd ROOM FROM EAST LOCATED AT APT 6I, 6th STORY, 6th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Jun 3, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING OF NORTH SIDE BULKHEAD. |
| Class B | Closed | 6I | Jun 3, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). (MISSING) LOCATED AT APT 6I, 6th STORY, 6th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 6I | Jun 3, 2019 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR (MISSING) LOCATED AT APT 6I, 6th STORY, 6th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 6I | Jun 3, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 2nd ROOM FROM EAST LOCATED AT APT 6I, 6th STORY, 6th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 6I | Jun 3, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING AND EAST WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 6I, 6th STORY, 6th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 6I | Jun 3, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AND EAST WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 6I, 6th STORY, 6th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 5G | Jun 3, 2019 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... (APPROX. 12 SQ. FEET) AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 5G, 5th STORY, 4th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 5G | Jun 3, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 5G, 5th STORY, 4th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 5G | Jun 3, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 5G, 5th STORY, 4th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 5H | May 17, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 5H, 5th STORY, 5th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 5H | May 17, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 2nd ROOM FROM EAST LOCATED AT APT 5H, 5th STORY, 5th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 5G | May 6, 2019 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 5G, 5th STORY, 4th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 5G | May 6, 2019 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AROUND BATHTUB APPROX 10 SQ FT IN THE BATHROOM LOCATED AT APT 5G, 5th STORY, 4th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3K | Apr 1, 2019 | REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXTENTION CORDS AT EAST WALL ELECTRICAL OUTLET IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1H | Mar 20, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 1st ROOM FROM EAST LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 1H | Mar 20, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 2nd ROOM FROM EAST LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3C | Jan 16, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PORCELAIN ENAMEL GLAZE AT BATH TUB IN THE BATHROOM LOCATED AT APT 3C, 3rd STORY, 6th APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 3C | Jan 16, 2019 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER SASH WINDOW IN THE BATHROOM LOCATED AT APT 3C, 3rd STORY, 6th APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1G | Dec 26, 2018 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1G | Dec 26, 2018 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | — | Dec 18, 2018 | F/E ADJUST THE DROP LADDER · EGRESS§ 27-2005 ADM CODE FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS THE CENTER STACK AT BUILDING FRONT |
| Class B | Closed | 1G | Dec 3, 2018 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1G | Dec 3, 2018 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF FURNITURE OBSTRUCTING FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1G | Dec 3, 2018 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 6F | Nov 13, 2018 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 6F, 6th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH'' |
| Class B | Closed | 2D | Sep 19, 2018 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE REFRIGERATOR DOOR GASKET IN THE KITCHEN LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3A | Aug 16, 2018 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 3A, 3rd STORY, 4th APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 3A | Aug 16, 2018 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 2nd ROOM FROM EAST LOCATED AT APT 3A, 3rd STORY, 4th APARTMENT FROM SOUTH AT WEST |