| Class B | ClosedRENT IMPAIRING | — | Sep 24, 2020 | PROVIDE A JANITOR · JANITORIAL SERVICES§ 27-2053 ADM CODE PROVIDE DWELLING WITH A JANITOR OR RESPONSIBLE PERSON OR JANITORIAL SERVICE. |
| Class B | Closed | — | Sep 24, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT NORTH WALL AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Sep 24, 2020 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT NORTH WALL AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Aug 19, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT EAST WALL LAUNDRY ROOM |
| Class B | Closed | — | Aug 19, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT ENTRANCE TO LAUNDRY ROOM |
| Class B | Closed | — | Aug 19, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING IN LAUNDRY ROOM |
| Class B | Closed | — | Aug 3, 2020 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE EXTRACTOR AT COMMUNITY WATER CLOSET AT LAUNDRY ROOM |
| Class B | ClosedRENT IMPAIRING | 12L | Aug 3, 2020 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 12L, 12th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 12L | Aug 3, 2020 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILINGS IN THE ENTIRE APARTMENT LOCATED AT APT 12L, 12th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 12L | Aug 3, 2020 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE KITCHEN LOCATED AT APT 12L, 12th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 3E | Jul 9, 2020 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX. 4 SQ. FT. AT THE NORTH WALL IN THE BATHROOM LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 13644278 ISSUED 10-MAR-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 3E | Mar 11, 2020 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ROTTEN WOOD FLOOR AT BASE CABINET IN THE KITCHEN LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3E | Mar 11, 2020 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT THE CEILING, NORTH WALL IN THE BATHROOM LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3E | Mar 11, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE REGLAZE PORCELAIN PAINTED BATHTUB IN THE BATHROOM LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Feb 25, 2020 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE WIRE GLASS AT 9TH STORY SOUTH STAIRWELL EXIT DOOR AT WEST WALL. AT PUBLIC HALL |
| Class B | Closed | — | Feb 19, 2020 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE WIRE GLASS AT FIREPROOF DOOR STAIR A AT PUBLIC HALL, 9th STORY |
| Class B | Closed | 11F | Feb 7, 2020 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 11F, 11th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | 12L | Feb 7, 2020 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE KITCHEN LOCATED AT APT 12L, 12th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 12L | Feb 7, 2020 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 12L, 12th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 12L | Feb 7, 2020 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE KITCHEN LOCATED AT APT 12L, 12th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 11F | Feb 7, 2020 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 11F, 11th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Feb 6, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE EAST WALL WITH FIRE RETARDANT MATERIAL AT PUBLIC HALL, 9th STORY |
| Class B | Closed | — | Feb 6, 2020 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE WIRED GLASS AT DOOR AT PUBLIC HALL, 9th STORY |
| Class B | Closed | 6L | Jan 30, 2020 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR THAT IS DEFECTIVE LOCATED AT APT 6L, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6L | Jan 30, 2020 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). THAT IS DEFECTIVE LOCATED AT APT 6L, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6L | Jan 30, 2020 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE VENTILATION SYSTEM IN THE BATHROOM LOCATED AT APT 6L, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 10G | Jan 28, 2020 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GASKET AS REFRIGERATOR DOOR IN THE KITCHEN LOCATED AT APT 10G, 10th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 10G | Jan 28, 2020 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). INOPERABLE IN THE ENTIRE APARTMENT LOCATED AT APT 10G, 10th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 10G | Jan 28, 2020 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT WEST AND NORTH WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 10G, 10th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 10G | Jan 28, 2020 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPERABLE IN THE ENTIRE APARTMENT LOCATED AT APT 10G, 10th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 10G | Jan 28, 2020 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND WEST WALL IN THE BATHROOM LOCATED AT APT 10G, 10th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 5K | Jan 13, 2020 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATH TUB IN THE BATHROOM LOCATED AT APT 5K, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | — | Dec 23, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE PARKING LOT WEST WALL AT BASEMENT |
| Class B | Closed | — | Dec 23, 2019 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PLASTIC TARPS TIED TO SPRINKLER SYSTEM PIPES AT PARKING LOT AT BASEMENT |
| Class B | Closed | — | Nov 14, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE THE EAST WALL AT 2ND 3RD 5TH AND 6TH STORIES AT PUBLIC HALL |
| Class B | Closed | 7L | Oct 15, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 7L, 7th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 7L | Oct 15, 2019 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 7L, 7th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | — | Oct 4, 2019 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE AREA OF ENTRY INTO THE BUILDING AT GARAGE |
| Class B | Closed | — | Oct 4, 2019 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING SAFETY COVERS AT ALL OUTLETS AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Jul 2, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDENT MATERIAL AT CEILING AT LAUNDRY ROOM |
| Class B | Closed | 2H | Apr 29, 2019 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 2007 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS ... IN THE BATHROOM LOCATED AT APT 2H, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2H | Apr 29, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE EAST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 2H, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2H | Apr 29, 2019 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE MECHANICAL VENTILATION SYSTEM AT WEST WALL IN THE BATHROOM LOCATED AT APT 2H, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | — | Apr 26, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Apr 26, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT LOBBY, 1st STORY |
| Class B | Closed | — | Apr 26, 2019 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL OUTLET SAFETY COVERS/CAPS AT PUBLIC HALLS AT PUBLIC HALL |
| Class B | Closed | — | Apr 19, 2019 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE FIREPROOF SELF-CLOSING DOOR AND DOOR FRAME TO REAR AT PUBLIC HALL, SECTION AT WEST |
| Class B | ClosedRENT IMPAIRING | — | Apr 19, 2019 | PROVIDE A JANITOR · JANITORIAL SERVICES§ 27-2053 ADM CODE PROVIDE DWELLING WITH A JANITOR OR RESPONSIBLE PERSON OR JANITORIAL SERVICE. |
| Class B | Closed | 12L | Mar 1, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE KITCHEN LOCATED AT APT 12L, 12th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 12L | Mar 1, 2019 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE KITCHEN LOCATED AT APT 12L, 12th STORY, 1st APARTMENT FROM SOUTH AT WEST |