| Class B | Open | — | May 26, 2026 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDENT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY |
| Class B | Open | — | May 26, 2026 | ADJUST DOOR TO PREVENT GAP - FIRE CODE/EGRESS · EGRESS28 RCNY § 25-171; & 67 (7)(B) MDL; NYC FIRE CODE § 703.1.3; NYC FIRE CODE § 703.2: ADJUST DOOR TO PREVENT GAPS BETWEEN THE TOP AND SIDE EDGES OF DOOR AND DOOR JAMB EXCEEDING THE MAXIMUM ALLOWABLE CLEARANCE OF 1/8 OF AN INCH AND MAXIMUM ALLOWABLE CLEARANCE OF 3/4 OF AN INCH BETWEEN THE DOOR BOTTOM AND SILL AT AT FIRE DOOR AT PUBLIC HALL, 6th STORY, SECTION ''SOUTH'' |
| Class B | OpenRENT IMPAIRING | — | May 26, 2026 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION MATERIAL AT PUBLIC HALL, 4th STORY, SECTION ''SOUTH'' |
| Class B | Open | — | May 26, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AND ITS ASSEMBLY AT HOPPER CHUTE DOOR AT PUBLIC HALL, 5th STORY |
| Class B | Open | 1A | May 22, 2026 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1A | May 22, 2026 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PORCELAIN GLAZE FINISH AT BATHTUB IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1A | May 22, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL WALL OUTLET AT WEST WALL IN THE KITCHEN LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 3B | May 20, 2026 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3B, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 1A | May 20, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER THE 1st CLOSET FROM NORTH AT EAST WALL CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1A | May 20, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER THE CEILING IN THE KITCHEN LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1A | May 20, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE WEST WALL IN THE KITCHEN LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 2A | May 20, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ.FT. AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 2A, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 2A | May 20, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING AND NORTH WALL IN THE BATHROOM LOCATED AT APT 2A, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Closed | — | May 20, 2026 | CORRECT FAILURE TO MAINTAIN R RECORDS REGARDING T DEVICES · HEAT SENSOR PROGRAM§ 27-2033.3(E) CORRECT FAILURE TO MAINTAIN REQUIRED RECORDS REGARDING INTERNET CAPABLE TEMPERATURE REPORTING DEVICES AND SUBMIT SUCH RECORDS TO THE DEPARTMENT UPON REQUEST. DATA REQUESTED FOR THE PERIOD OF MARCH 2026 |
| Class B | Open | 1A | May 20, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE CLOSET DOOR AT NORTH IN THE FOYER LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 2A | May 20, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 2A, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 3B | May 20, 2026 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3B, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 3B | May 20, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 3B, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 9C | May 11, 2026 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF KEY OPERATED LOCK INSTALLED AT DOOR LEADING TO FIRE ESCAPE IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 9C, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''CENTER '' |
| Class B | Open | 9A | May 4, 2026 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 9A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH'' |
| Class B | Open | 10E | May 4, 2026 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 10E, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH'' |
| Class B | Open | 15A | May 4, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RUBBER GASKET SEAL AT LOWER DOOR AT REFRIGERATOR IN THE KITCHEN LOCATED AT APT 15A, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH'' |
| Class B | Open | 10E | May 4, 2026 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 10E, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH'' |
| Class B | Open | 8E | May 4, 2026 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT 8E, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''CENTER'' |
| Class B | Open | 3D | Apr 29, 2026 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 3D | Apr 29, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 3D, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 3D | Apr 29, 2026 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Open | 14D | Apr 28, 2026 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 14D, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH |
| Class B | Open | 14D | Apr 28, 2026 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 14D, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH |
| Class B | Open | 14D | Apr 28, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 14D, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH |
| Class B | Open | 15D | Apr 28, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 15D, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH |
| Class B | Closed | — | Apr 28, 2026 | CORRECT FAILURE TO MAINTAIN R RECORDS REGARDING T DEVICES · HEAT SENSOR PROGRAM§ 27-2033.3(E) CORRECT FAILURE TO MAINTAIN REQUIRED RECORDS REGARDING INTERNET CAPABLE TEMPERATURE REPORTING DEVICES AND SUBMIT SUCH RECORDS TO THE DEPARTMENT UPON REQUEST. DATA REQUESTED FOR THE PERIOD OF FEBRUARY 2026 |
| Class B | Open | 15D | Apr 22, 2026 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE PRIVATE HALLWAY LOCATED AT APT 15D, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH'' |
| Class B | Open | 15E | Apr 15, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 15E, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH |
| Class B | Open | 1D | Apr 15, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 1D, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''CENTER'' |
| Class B | Closed | 10E | Apr 15, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT HEAT SENSOR DEVICE FAILED TO MANTAIN LOCATED AT APT 10E, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT NORTH |
| Class B | Open | — | Apr 15, 2026 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY |
| Class B | Open | 1E | Apr 13, 2026 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1E, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''CENTER '' |
| Class B | Open | 1E | Apr 13, 2026 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1E, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''CENTER '' |
| Class B | Open | 1E | Apr 13, 2026 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF KEY OPERATED LOCK INSTALLED AT ROOM LEADING TO FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 1E, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''CENTER '' |
| Class B | Open | 4A | Apr 10, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL CEILINGS AND WALLS THROUGHOUT CRACKS AT WALLS THROUGHOUT APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 4A, 4th STORY, 4th APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8E | Apr 3, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT THE LOWER WINDOW SASH AT 1ST WINDOW FROM NORTH AT EAST WALL IN THE KITCHEN LOCATED AT APT 8E, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''CENTER'' |
| Class B | Open | 8E | Apr 3, 2026 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT 8E, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''CENTER'' |
| Class B | ClosedRENT IMPAIRING | — | Apr 3, 2026 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF WASH BASIN AND HOUSE HOLD ITEAMS AT PUBLIC HALL, 2nd STORY, SECTION ''NORTH'' |
| Class B | Open | 6E | Mar 27, 2026 | ADJUST DOOR TO PREVENT GAP - FIRE CODE/EGRESS · EGRESS28 RCNY § 25-171; & 67 (7)(B) MDL; NYC FIRE CODE § 703.1.3; NYC FIRE CODE § 703.2: ADJUST DOOR TO PREVENT GAPS BETWEEN THE TOP AND SIDE EDGES OF DOOR AND DOOR JAMB EXCEEDING THE MAXIMUM ALLOWABLE CLEARANCE OF 1/8 OF AN INCH AND MAXIMUM ALLOWABLE CLEARANCE OF 3/4 OF AN INCH BETWEEN THE DOOR BOTTOM AND SILL AT ,, IN THE ENTRANCE LOCATED AT APT 6E, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 3A | Mar 27, 2026 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD BASE BOARD AT WEST WALL IN THE 3rd ROOM FROM EAST AT NORTH LOCATED AT APT 3A, 1st STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Open | 17F | Mar 24, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 17F, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''CENTER '' |
| Class B | Open | 9F | Mar 24, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT HEAT SENSOR DEVICE INSTALLED INCORRECTLY LOCATED AT APT 9F, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''CENTER'' |
| Class B | Open | 4F | Mar 24, 2026 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF KEY OPERATED LOCK INSTALLED AT DOOR LEADING TO FIRE ESCAPE WINDOW IN THE 4th ROOM FROM EAST AT SOUTH LOCATED AT APT 4F, 6th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |
| Class B | Closed | 4F | Mar 24, 2026 | CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT HEAT SENSOR DEVICE INSTALLED INCORRECTLY LOCATED AT APT 4F, 6th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH |