| Class B | ClosedRENT IMPAIRING | 7J | Apr 8, 2025 | REPAIR LEAKY PIPES · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE WATER SUPPLY PIPE UNDER SINK BASE CABINET IN THE KITCHEN LOCATED AT APT 7J, 7th STORY, 6th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6G | Apr 8, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK ABOVE CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 6G, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6G | Apr 8, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 6G, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6G | Apr 8, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 6G, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Open | 4D | Apr 7, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 10 SQFT AT NORTH WALL AND WEST WALL IN THE BATHROOM LOCATED AT APT 4D, 4th STORY, 4th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4B | Apr 7, 2025 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL WALL OUTLET COVER PLATE AT SOUTH WALL IN THE 1st ROOM FROM EAST LOCATED AT APT 4B, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION AT EAST |
| Class B | Closed | 4B | Apr 7, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT SINK BASE CABINET BOTTOM INTERIOR (LESS THAN 10 SQ.FT.) IN THE KITCHENETTE LOCATED AT APT 4B, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 17740696 ISSUED 06-MAR-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 4D | Apr 7, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 4D, 4th STORY, 4th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Mar 31, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT NORTH WALL AT PUBLIC HALL, 6th STORY, SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | 7A | Mar 31, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE ENTRANCE LOCATED AT APT 7A, 7th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''ABCHIJ'', 2nd FROM SOUTH AT WEST |
| Class B | Closed | — | Mar 31, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT EAST WALL AT BUILDING VESTIBULE LEADING TO 1ST STORY PUBLIC HALL , 1st STORY |
| Class B | Closed | — | Mar 31, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE 2ND, 3RD AND 4TH LIGHT FIXTURES FROM THE EAST AT CEILING AT PUBLIC HALL, 3rd STORY, SECTION AT EAST |
| Class B | Closed | 7A | Mar 31, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BUZZER AND RETURN VOICE INTERCOM SYSTEM FROM BUILDING ENTRANCE UP TO PANEL AT NORTH WALL IN THE ENTRANCE LOCATED AT APT 7A, 7th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''ABCHIJ'', 2nd FROM SOUTH AT WEST |
| Class B | Closed | 7A | Mar 31, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE ENTRANCE LOCATED AT APT 7A, 7th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''ABCHIJ'', 2nd FROM SOUTH AT WEST |
| Class B | Closed | 6E | Mar 31, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | 6E | Mar 31, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | 6E | Mar 31, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT WINDOW SILL IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | 6E | Mar 31, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT EAST, SOUTH, AND WEST WALLS IN THE ENTRANCE LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | 6E | Mar 31, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | 6E | Mar 31, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT EAST, SOUTH, AND WEST WALLS IN THE ENTRANCE LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | 6E | Mar 31, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | 6E | Mar 31, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT WINDOW SILL IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | — | Mar 31, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT NORTH WALL AT PUBLIC HALL, 6th STORY, SECTION ''EFG'', 1st FROM SOUTH AT WEST |
| Class B | Closed | 11F | Mar 26, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 11F, 11th STORY, 3rd APARTMENT FROM WEST AT NORTH , SECTION AT WEST |
| Class B | Closed | 9D | Mar 26, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 4th ROOM FROM EAST LOCATED AT APT 9D, 9th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 9D | Mar 26, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 4th ROOM FROM EAST LOCATED AT APT 9D, 9th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 9D | Mar 26, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE FOYER LOCATED AT APT 9D, 9th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 11F | Mar 26, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 11F, 11th STORY, 3rd APARTMENT FROM WEST AT NORTH , SECTION AT WEST |
| Class B | Closed | 9D | Mar 26, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE FOYER LOCATED AT APT 9D, 9th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | — | Mar 25, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT NORTH WALL AT (WEST SECTION) AT PUBLIC HALL, 6th STORY |
| Class B | Closed | — | Mar 25, 2025 | PROVIDE LIGHT - Not Less that 60 Watt incadescent · ARTIFICIAL LIGHTING§ 27-2039 ADM CODE PROVIDE ADEQUATE LIGHT OF NOT LESS THAN 60 WATTS INCANDESCENT OR EQUIVALENT ILLUMINATION AT PUBLIC HALL CEILING 6TH STORY (WEST SECTION) AT PUBLIC HALL, 6th STORY |
| Class B | Closed | 4A | Mar 24, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 4A, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | — | Mar 24, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE AT COMPACT CLOSET AT PUBLIC HALL 3RD STORY AT COMPACTOR CLOSET, 3rd STORY |
| Class B | Closed | 4A | Mar 24, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGHT FIXTURE AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 4A, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 10H | Mar 24, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT EAST WALL, WEST WALL IN THE BATHROOM LOCATED AT APT 10H, 20th STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 10H | Mar 24, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE VENT AT CEILING IN THE BATHROOM LOCATED AT APT 10H, 20th STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | 10H | Mar 24, 2025 | INADEQUATE HOT WATER SUPPLY (VOLUME) · WATER SUPPLY§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES AT BATHTUB IN THE BATHROOM LOCATED AT APT 10H, 20th STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | — | Mar 24, 2025 | PROVIDE GARGABE CANS · COLLECTION OF WASTE§ 27-2021 ADM CODE PROVIDE SUFFICIENT, PROPER AND SEPARATE METAL RECEPTACLES FOR THE DEPOSIT OF GARBAGE, RUBBISH AND OTHER WASTE MATERIAL AND ARRANGE FOR COLLECTION AND DISPOSAL OF SUCH MATERIAL. |
| Class B | Closed | — | Mar 24, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE OBSERVED EVIDENCE OF GARBAGE ACCUMALATION AT JANITOR CLOSET AT COMPACT CLOSET AT PUBLIC HALL 13TH STORY AT COMPACTOR CLOSET, 13th STORY |
| Class B | Closed | — | Mar 20, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AND IT'S ASSEMBLIES AT STAIR B DOOR AT PUBLIC HALL STAIRS, 11th STORY |
| Class B | Closed | — | Mar 20, 2025 | PROVIDE LIGHT - Not Less that 60 Watt incadescent · ARTIFICIAL LIGHTING§ 27-2039 ADM CODE PROVIDE ADEQUATE LIGHT OF NOT LESS THAN 60 WATTS INCANDESCENT OR EQUIVALENT ILLUMINATION AT PUBLIC HALL, 13th STORY |
| Class B | Closed | 5F | Mar 20, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE SILICONE CAULKING AROUND BATHTUB IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 5F | Mar 20, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PORCELAIN ENAMEL FINISH BY METHOD OF REGLAZING AT BATHTUB IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | — | Mar 20, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AND IT'S ASSEMBLIES AT STAIR B DOOR AT PUBLIC HALL STAIRS, 5th STORY |
| Class B | Closed | 4D | Mar 17, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 4D, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION AT EAST |
| Class B | Closed | 4D | Mar 17, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 4D, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION AT EAST |
| Class B | Closed | 11B | Mar 17, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 11B, 11th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION AT EAST |
| Class B | Closed | 11B | Mar 17, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 11B, 11th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION AT EAST |
| Class B | Closed | — | Mar 14, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE GLASS PANE AT BLDG. ENTRANCE DOOR, |
| Class B | Closed | — | Mar 14, 2025 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF OFFENSIVE ODORS EMANATING AT PUBLIC HALL, 1st STORY |