| Class C | ClosedRENT IMPAIRING | 8A | Apr 9, 2026 | REMOVE OBSTUCTION FROM WATER CLOSET · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS FROM WATER CLOSET ... IN THE BATHROOM LOCATED AT APT 8A, 8th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | — | Apr 9, 2026 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM |
| Class C | ClosedRENT IMPAIRING | 8B | Mar 30, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 4th APARTMENT FROM WEST AT NORTH |
| Class C | Closed | — | Mar 30, 2026 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM |
| Class C | Closed | — | Mar 5, 2026 | DOOR NOT SELF-CLOSING · EGRESS§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING [FLOOR] AT 2ND DOOR FROM WEST AT DOOR FROM STREET TO VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class C | ClosedRENT IMPAIRING | 8B | Mar 2, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 4th APARTMENT FROM WEST AT NORTH |
| Class C | ClosedRENT IMPAIRING | 8A | Mar 2, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8A , 8th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | — | Mar 2, 2026 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM |
| Class C | Closed | — | Feb 19, 2026 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOM |
| Class C | ClosedRENT IMPAIRING | 4J | Feb 19, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 4J, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Feb 2, 2026 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM LOCKED AT BOILER ROOM |
| Class C | Closed | — | Feb 2, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT BUILDING ENTRANCE DOOR FROM VESTIBULE TO PUBLIC HALL AT PUBLIC HALL, 1st STORY |
| Class C | Closed | 1F | Feb 2, 2026 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1F, 1st STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class C | ClosedRENT IMPAIRING | 1F | Feb 2, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 1F, 1st STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Feb 2, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR AT BUILDING ENTRANCE FROM STREET TO VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Feb 2, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AND ITS ASSEMBLY AT BUILDING ENTRANCE DOOR FROM VESTIBULE TO PUBLIC HALL AT PUBLIC HALL, 1st STORY |
| Class C | Closed | 1F | Feb 2, 2026 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1F, 1st STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Jan 22, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE [HINGE] DOOR FROM STREET TO VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 6B | Jan 22, 2026 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE 4TH UPPER WALL CABINET DRAWER FROM NORTH AT EAST WALL IN THE KITCHEN LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''EAST'' |
| Class A | Closed | — | Jan 22, 2026 | POST A SIGN · POSTING/SIGNAGE§ 27-2022 ADM CODE POST A SIGN INDICATING HOURS OF COLLECTION AND METHOD OF COLLECTION OF WASTE MATERIAL WHERE DUMBWAITER SERVICE IS NOT PROVIDED. AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Jan 22, 2026 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES AT PUBLIC HALL, 6th STORY |
| Class C | Closed | 6B | Jan 22, 2026 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''EAST'' |
| Class B | Closed | — | Jan 22, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AND ITS ASSEMBLYS AT 2ND DOOR FROM WEST AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 6B | Jan 22, 2026 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''EAST'' |
| Class B | Closed | 6B | Jan 22, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RETURN BUZZER INTERCOM SYSTEM FROM THE BUILDING ENTRANCE DOOR TO THE APARTMENT WALL PANEL AT SOUTH WALL IN THE FOYER LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''EAST'' |
| Class C | Closed | — | Jan 22, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE [LATCH SET] 2ND DOOR FROM WEST AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 6B | Jan 22, 2026 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''EAST'' |
| Class B | Closed | 6B | Jan 22, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RUBBER GASKET AT REFRIGERATOR DOOR IN THE KITCHEN LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''EAST'' |
| Class B | Closed | 6B | Jan 22, 2026 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE 2ND, AND 3RD UPPER WALL CABINET DOOR FROM NORTH AT EAST WALL IN THE KITCHEN LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''EAST'' |
| Class B | Closed | — | Jan 22, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE HEAVY DUTY LATCH AND ASSEMBLY AT BUILDING ENTRANCE DOOR , 1st STORY |
| Class A | Closed | — | Jan 22, 2026 | POST GAS LEAK NOTICE · POSTING/SIGNAGE§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY |
| Class C | Closed | 6B | Jan 22, 2026 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''EAST'' |
| Class B | ClosedRENT IMPAIRING | 8D | Jan 20, 2026 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 8D, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | — | Jan 15, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE [LATCH SET]2ND DOOR FROM WESTAT DOOR FROM STREET TO VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Jan 15, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AND ITS ASSEMBLYS AT 2ND DOOR FROM WEST AT DOOR FROM STREET TO VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Jan 12, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SHATTERED GLASS AT LOWER PANEL AT VESTIBULE DOOR , 1st STORY |
| Class B | Closed | — | Jan 8, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 7th STORY, SECTION ''D-G'', AT WEST |
| Class B | Closed | — | Jan 8, 2026 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 7th STORY, SECTION ''D-G'', AT WEST |
| Class C | ClosedRENT IMPAIRING | 7D | Jan 8, 2026 | INADEQUATE HEAT · HEAT AND HOT WATER§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 7D, 7th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''D-G'', AT NORTH |
| Class C | ClosedRENT IMPAIRING | 7D | Jan 8, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 7D, 7th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''D-G'', AT NORTH |
| Class C | Closed | — | Jan 8, 2026 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM LOCKED DOOR AT BOILER ROOM |
| Class C | ClosedRENT IMPAIRING | 4C | Jan 5, 2026 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 4C, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''A-D'', AT EAST |
| Class C | Closed | — | Jan 5, 2026 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM LOCKED DOOR AT BOILER ROOM |
| Class C | Closed | — | Dec 29, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT CLOSER ARM, AT BUILDING'S ENTRANCE DOOR (FROM STREET TO VESTIBULE) , 1st STORY |
| Class C | ClosedRENT IMPAIRING | 8B | Dec 29, 2025 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 4th APARTMENT FROM WEST AT NORTH |
| Class C | ClosedRENT IMPAIRING | 8B | Dec 29, 2025 | INADEQUATE HEAT · HEAT AND HOT WATER§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''AB'', AT EAST |
| Class C | ClosedRENT IMPAIRING | 8B | Dec 29, 2025 | INADEQUATE HEAT · HEAT AND HOT WATER§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 4th APARTMENT FROM WEST AT NORTH |
| Class C | Closed | — | Dec 29, 2025 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM LOCKED DOOR AT BOILER ROOM |
| Class C | ClosedRENT IMPAIRING | 8B | Dec 29, 2025 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''AB'', AT EAST |
| Class C | ClosedRENT IMPAIRING | 8B | Dec 18, 2025 | INADEQUATE HEAT · HEAT AND HOT WATER§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE 3rd ROOM FROM EAST LOCATED AT APT 8B, 8th STORY, 3rd APARTMENT FROM WEST AT NORTH |