| Class B | Closed | 3G | Jul 31, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 3G, 3rd STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2D | Jul 31, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 2D, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2D | Jul 31, 2019 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE LOCATED AT APT 2D, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 1H | Jul 31, 2019 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT APARTMENT ENTRANCE LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1H | Jul 31, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1H | Jul 31, 2019 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 2J | Jun 28, 2019 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE WINDOW FRAME IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 2J | Jun 28, 2019 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2J | Jun 28, 2019 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPPERABLE LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2J | Jun 28, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). INOPPERABLE LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2J | Jun 28, 2019 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CLOSET IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2J | Jun 28, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CLOSET CEILING IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 2J | Jun 28, 2019 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT WALLS AND CEILING IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2J | Jun 28, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WEST WALL AND CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 2J | Jun 28, 2019 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING IN THE BATHROOM LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 2J | Jun 28, 2019 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2J, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3G | Jun 19, 2019 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE LOCATED AT APT 3G, 3rd STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3G | Jun 19, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 3G, 3rd STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 5F | May 28, 2019 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | 5F | May 28, 2019 | REPAIR FLUSHING APPARATUS OF WATER CLOSET · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET IN THE 3rd BATHROOM FROM EAST AT NORTH LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 5F | May 28, 2019 | CLEANSE · CLEANING§ 27-2011 ADM CODE CLEANSE TO THE SATISFACTION OF THIS DEPARTMENT THE MOLD ON TILES AND GROUT AT BATHTUB IN THE 4th BATHROOM FROM EAST AT NORTH LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 5F | May 28, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 3rd BATHROOM FROM EAST AT NORTH LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 5F | May 28, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 3rd BATHROOM FROM EAST AT NORTH LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5F | May 28, 2019 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING WATER CLOSET TANK COVER IN THE 3rd BATHROOM FROM EAST AT NORTH LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 5F | May 28, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5F | May 28, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 5F | May 28, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE SOUTH WALL IN THE 3rd ROOM FROM EAST AT SOUTH LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 5F | May 28, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 5F | May 28, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE KITCHEN LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5F | May 28, 2019 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE WOOD BASE CABINET AT SINK IN THE KITCHEN LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 5F | May 28, 2019 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 5F | May 28, 2019 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5F | May 28, 2019 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). INOPERABLE IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5F | May 28, 2019 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPERABLE IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | — | May 17, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CELLING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | May 17, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDING PLASTER AT CELLING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 5G | May 3, 2019 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE ... IN THE ENTRANCE LOCATED AT APT 5G, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5G | May 3, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE ENTIRE APARTMENT LOCATED AT APT 5G, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 5G | May 3, 2019 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 5G, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 5G | May 3, 2019 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 5G, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | 5G | May 3, 2019 | REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN WASH BASIN IN THE BATHROOM LOCATED AT APT 5G, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | 5G | May 3, 2019 | REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN BATHTUB DRAIN LINE IN THE BATHROOM LOCATED AT APT 5G, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1H | Apr 30, 2019 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 1F | Apr 26, 2019 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE MORTISE LOCK AND ITS ASSEMBLY AT DOOR IN THE ENTRANCE LOCATED AT APT 1F, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION AT WEST |
| Class A | Closed | — | Apr 26, 2019 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT PUBLIC HALL, 1st STORY |
| Class C | Closed | 5B | Apr 26, 2019 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 5B, 5th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 5B | Apr 26, 2019 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PAINTED SPRINKLER HEAD IN THE 4th ROOM FROM EAST LOCATED AT APT 5B, 5th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 5B | Apr 26, 2019 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE ... IN THE ENTRANCE LOCATED AT APT 5B, 5th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | — | Apr 26, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 7G | Apr 25, 2019 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 2nd ROOM FROM EAST LOCATED AT APT 7G, 7th STORY, 3rd APARTMENT FROM WEST AT NORTH |