| Class B | OpenRENT IMPAIRING | 9B | May 15, 2026 | REMOVE ILLEGAL FASTENING · EGRESS§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING SLIDE BOLT WITH EYE INSTALLED ON FIRE RATED DOOR IN THE ENTRANCE LOCATED AT APT 9B, 9th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT WASH/BASIN IN THE BATHROOM LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE HANDLE AND LOCK AT WEST WINDOW IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE 4th BATHROOM FROM NORTH LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT METAL BASEBOARD HEATER COVERS AT WEST IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT WASH BASIN IN THE 4th BATHROOM FROM NORTH LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WINDOW HANDLE AND LOCK AT WEST IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT METAL BASEBOARD HEATER COVERS AT WEST IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE BASEWOOD CABINET AT SINK IN THE KITCHEN LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WINDOW HANDLE AND LOCK AT WEST IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 8B | Mar 23, 2026 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT METAL BASEBOARD HEATER COVERS AT WEST IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jan 12, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jan 12, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jan 12, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jan 12, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jan 12, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jan 12, 2026 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jan 12, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND NORTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jan 12, 2026 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND WEST WALL IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5B | Dec 15, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WASH BASIN VANITY CABINET IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | — | Dec 15, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT STAIRWELL ''B'' AT FIRE STAIRS, 9th STORY |
| Class B | Closed | 5B | Dec 15, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE A/C UNIT SLOT COVER AT WEST WALL IN THE 4th ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 5B | Oct 9, 2025 | REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN AT WASTELINE AT WASH BASIN IN THE 2nd BATHROOM LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 7D | Jul 23, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7D, 7th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 7D | Jul 23, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7D, 7th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 7F | Dec 6, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7F, 7th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 7F | Dec 6, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE RECAULK AROUND BATHTUB IN THE BATHROOM LOCATED AT APT 7F, 7th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 7F | Dec 6, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7F, 7th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 5B | Oct 22, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT THE CEILING APPROXIMATELY 1 SQ.FT. IN THE 2nd BATHROOM FROM NORTH AT EAST LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 17066695 ISSUED 22-JUN-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 9C | Jun 24, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5B | Jun 24, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING (2) WINDOW SASH HANDLES IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | — | Jun 24, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING DOOR HANDLES ON THE SELF-CLOSING AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORY |
| Class B | Open | 9C | Jun 24, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOM SYSTEM FROM BUILDING ENTRANCE TO NORTH WALL IN THE FOYER LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jun 24, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING IN THE 2nd ROOM FROM NORTH LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5B | Jun 24, 2024 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT WASH BASIN IN THE 2nd BATHROOM FROM NORTH AT EAST LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5B | Jun 24, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE DOOR HANDLE IN THE ENTRANCE LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5B | Jun 24, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING RADIATOR COVER IN THE 3rd ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 9C | Jun 24, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE WEST WALL, AND THE CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5B | Jun 24, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING RADIATOR COVER IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Jun 24, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9A | May 22, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... 1 SQFT AT THE CEILING IN THE 2nd ROOM FROM NORTH LOCATED AT APT 9A, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 16613150 ISSUED 22-JAN-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 7D | Apr 10, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL LIGHT FIXTURE AT NORTH WALL IN THE BATHROOM LOCATED AT APT 7D, 7th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 9A | Jan 30, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOCK AT WINDOW AT WEST IN THE 1st ROOM FROM NORTH LOCATED AT APT 9A, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | OpenRENT IMPAIRING | 9A | Jan 23, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK ABOVE THE CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT 9A, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9A | Jan 23, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT THE CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 9A, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9A | Jan 23, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK ABOVE THE CEILING IN THE 2nd ROOM FROM NORTH LOCATED AT APT 9A, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9A | Jan 23, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT THE CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT 9A, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9A | Jan 23, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK ABOVE THE CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT 9A, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9A | Jan 23, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT THE CEILING IN THE 2nd ROOM FROM NORTH LOCATED AT APT 9A, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 9C | Nov 20, 2023 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT WEST WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 9C, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST |