Class BOpen
Apr 28, 2021
REMOVE ACCUMULATION OR RUBBISH · CLEANING
§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE DISUSED CARDBOARD AND PLASTIC BAGS AT FRONT YARD
Class BClosedRENT IMPAIRING
Apr 8, 2021
REMOVE ENCUMBRANCES · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION MATERIALS AT PUBLIC HALL, 1st STORY
Class BClosed
Mar 16, 2021
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE WOOD PLYWOOD AT THE APRON AT THE SIDEWALK SHED ON EAST
Class BClosed
Mar 5, 2021Apt 205
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE DEFECTIVE LOCKING DEVICE AT DOOR IN THE ENTRANCE LOCATED AT APT 205, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
Mar 3, 2021Apt C3
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF UNLAWFUL USE OF ROOM FOR LIVING PURPOSES AT LOWER LEVEL OF DUPLEX APARTMENT IN THE 2nd ROOM FROM EAST LOCATED AT APT C3, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BClosed
Mar 3, 2021Apt C3
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF ELECTRIC WIRE EXPOSE AT CEILING IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT C3, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BOpen
Feb 26, 2021Apt 2
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH WINDOW, SOUTH WALL IN THE 3rd ROOM FROM NORTH LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BOpen
Feb 26, 2021Apt 2
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BOpen
Feb 26, 2021Apt 2
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH WINDOW, NORTH WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Feb 25, 2021
DISCONTINUE ROOMING UNIT · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS
§ 27-2077 ADM CODE DISCONTINUE THE ROOMING UNIT AT 3RD ROOM FROM NORTH AT CELLAR, SECTION AT NORTHWEST
Class BClosed
Feb 25, 2021Apt C5
DISCONTINUE ROOMING UNIT · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS
§ 27-2077 ADM CODE DISCONTINUE THE ROOMING UNIT IN THE 4th ROOM FROM NORTH AT WEST LOCATED AT APT C5, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Feb 25, 2021Apt C5
DISCONTINUE ROOMING UNIT · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS
§ 27-2077 ADM CODE DISCONTINUE THE ROOMING UNIT IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT C5, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosedRENT IMPAIRING
Feb 25, 2021
REMOVE ENCUMBRANCES · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF BICYCLES AND OTHER HOUSE HOLD ITMES AT PUBLIC HALL, 1st STORY
Class BOpen
Feb 25, 2021
DISCONTINUE ROOMS AT CELLAR · ILLEGAL OCCUPANCY OF BASEMENT AND CELLARS
§ 27-2081 ADM CODE DISCONTINUE USE OF ROOMS FOR LIVING, DISCONNECT PLUMBING FIXTURES AND PROPERLY SEAL PIPE CONNECTIONS AT WATER CLOSET, WASH BASIN AND SHOWER STALL AT CELLAR, SECTION AT NORTHWEST
Class BClosed
Feb 25, 2021Apt C5
DISCONTINUE ROOMING UNIT · MINIMUM ROOM SIZES AND OCCUPANCY REGULATIONS
§ 27-2077 ADM CODE DISCONTINUE THE ROOMING UNIT IN THE 1st ROOM FROM NORTH LOCATED AT APT C5, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Feb 18, 2021Apt 206
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 206, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH
Class BClosed
Feb 18, 2021Apt 206
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE LOCATED AT APT 206, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 18, 2021Apt 1B
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 1B, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BOpen
Feb 18, 2021Apt 1B
REMOVE BARS OR GATES FROM NON FIRE ESCAPE WINDOW · EGRESS
§ 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM AT LEAST 1 WINDOW OR PROVIDE APPROVED TYPE GATE ... IN THE ENTIRE APARTMENT LOCATED AT APT 1B, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BOpen
Feb 18, 2021Apt 1B
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 1B, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BOpen
Feb 18, 2021Apt 1B
REPLACE · MAINTENANCE
§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING METAL-COVER AT BASEBOARD RADIATOR AT NORTH WALL IN THE KITCHEN LOCATED AT APT 1B, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 16, 2021Apt 1
REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION AT WASTE LINE OF SINK IN THE KITCHEN LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosedRENT IMPAIRING
Feb 8, 2021
REMOVE ENCUMBRANCES · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT PUBLIC HALL, 1st STORY
Class BOpen
Feb 2, 2021Apt 1B
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 1B, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 2, 2021Apt 1B
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 1B, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Jan 11, 2021Apt 1
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Jan 11, 2021Apt 1
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Jan 11, 2021Apt 1
REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION AT WASTELINE UNDER WASBASIN IN THE BATHROOM LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Dec 11, 2020Apt 2C
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTER BALANCES AT LOWER SASHES, 2 WINDOWS AT EAST WALL IN THE 3rd ROOM FROM NORTH AT EAST LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 11, 2020Apt 2C
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH, 2ND WINDOW FROM NORTH AT EAST WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 11, 2020Apt 2C
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 11, 2020Apt 2C
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 11, 2020Apt 2C
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT WEST WALL IN THE 2nd BATHROOM FROM NORTH LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 11, 2020Apt 2C
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT SOUTH WALL APPROX. 12 SQUARE FEET AND AT EAST WALL APPROX. 4 SQUARE FEET , TOTAL 16 SQUARE FEET IN THE 3rd ROOM FROM NORTH AT EAST LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosedRENT IMPAIRING
Dec 11, 2020Apt 2C
REPAIR FLUSHING APPARATUS OF WATER CLOSET · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET IN THE 2nd BATHROOM FROM NORTH LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 7, 2020Apt 5J
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING, APPRX. 2 SQ FT IN THE BATHROOM LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 13755216 ISSUED 05-AUG-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE ''''27-2017.3a(3)(a) or (b).
Class BClosed
Nov 2, 2020
PROVIDE · MAINTENANCE
§ 27-2005 ADM CODE PROVIDE A MECHANICAL HEAVY DUTY LOCK AND LATCH SET AT BUILDING ENTRANCE DOOR AT PUBLIC HALL, 1st STORY
Class BClosedRENT IMPAIRING
Sep 28, 2020
REMOVE ENCUMBRANCES · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF PARTITION WALLS AND CEILING AT WEST OF REAR YARD YARD
Class BClosed
Sep 18, 2020
REMOVE ACCUMULATION OR RUBBISH · CLEANING
§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE BUILDING FRONT YARD
Class BClosed
Aug 27, 2020Apt 3B
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). -DEFECTIVE- IN THE ENTIRE APARTMENT LOCATED AT APT 3B, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Aug 27, 2020Apt 3B
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR -DEFECTIVE- IN THE ENTIRE APARTMENT LOCATED AT APT 3B, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Jul 22, 2020
REMOVE ACCUMULATION OR RUBBISH · CLEANING
§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE FRONT BUILDING YARD
Class BClosed
Jul 6, 2020Apt 421
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPERABLE IN THE ENTIRE APARTMENT LOCATED AT APT 421, 4th STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Jul 6, 2020Apt 421
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES FLOOR IN THE BATHROOM LOCATED AT APT 421, 4th STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Jun 29, 2020Apt 811
REMOVE VERMIN · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF VERMIN FLIES IN THE ENTIRE APARTMENT LOCATED AT APT 811, 8th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Jun 8, 2020
PROVIDE GARGABE CANS · COLLECTION OF WASTE
§ 27-2021 ADM CODE PROVIDE SUFFICIENT, PROPER AND SEPARATE METAL RECEPTACLES FOR THE DEPOSIT OF GARBAGE, RUBBISH AND OTHER WASTE MATERIAL AND ARRANGE FOR COLLECTION AND DISPOSAL OF SUCH MATERIAL.
Class BClosed
May 13, 2020Apt 1
ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Apr 20, 2020Apt 1
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 1, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Apr 20, 2020Apt 1
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 1, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Apr 20, 2020Apt 1
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRE AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 1, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH