| Class C | Closed | 2C | Mar 4, 2024 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 7G | Mar 4, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 7G, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 206 | Mar 4, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOM AT EAST WALL IN THE FOYER LOCATED AT APT 206, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 2C | Feb 28, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 2C | Feb 28, 2024 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 2C | Feb 28, 2024 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 2C | Feb 28, 2024 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF SCALDING HOT WATER EXCEEDING ALLOWABLE TEMP OF 130 DEGREES IN THE KITCHEN LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2C | Feb 28, 2024 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE RADIATOR COVER AT EAST WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 2C | Feb 28, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT NORTH WALL (APPROX 1 SQ FT) IN THE BATHROOM LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Feb 28, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE FIRE DOOR AT SOUTH WALL AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 2C | Feb 28, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING DOOR KNOB IN THE ENTRANCE LOCATED AT APT 2C, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 1 | Feb 20, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE .. IN THE ENTRANCE LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6C | Feb 5, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER WINDOW SASH IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 6C, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 7G | Feb 1, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7G, 7th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 7G | Feb 1, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX 30 SQ FT AT NORTH WALL AND CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 7G, 7th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 7G | Feb 1, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND NORTH WALL IN THE 1st ROOM FROM EAST LOCATED AT APT 7G, 7th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 7G | Feb 1, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7G, 7th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 422 | Jan 26, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BROKEN RADIATOR IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 422, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 422 | Jan 26, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OBSERVED EVIDENCE OF WATER LEAK IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 422, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | — | Jan 15, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING AT METER ROOM, 1st STORY ORIGINAL VIOLATION 16225781 ISSUED 11-SEP-23 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 7D | Jan 8, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT EAST WALL AND CEILING IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 7D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 7D | Jan 8, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 7D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class A | Closed | — | Jan 8, 2024 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AND NORTH WALL AT PUBLIC HALL, 6th STORY |
| Class B | ClosedRENT IMPAIRING | 7D | Jan 8, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 7D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | 7D | Jan 8, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 7D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | — | Jan 8, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL, 6th STORY |
| Class B | Closed | — | Jan 8, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND NORTH WALL AT PUBLIC HALL, 6th STORY |
| Class B | Closed | 7D | Jan 8, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND EAST WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 7D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Closed | — | Jan 8, 2024 | DOOR NOT SELF-CLOSING · EGRESS§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING PERMANENTLY INSTALLED KICKSTAND AT 2ND FIRE DOOR FROM EAST PREVENTING IT FROM BEING SELF CLOSING AT BASEMENT AT PUBLIC HALL |
| Class B | Closed | 7D | Jan 8, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 7D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Closed | — | Jan 8, 2024 | DOOR NOT SELF-CLOSING · EGRESS§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING PERMANENTLY INSTALLED KICKSTAND AT 1ST FIRE DOOR FROM EAST PREVENTING IT FROM BEING SELF CLOSING AT BASEMENT AT PUBLIC HALL |
| Class B | Closed | 1A | Jan 3, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROXIMATELY 4 SQUARE FEET AT THE CEILING AND WEST WALL IN THE KITCHENETTE LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 16198594 ISSUED 31-AUG-23 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 1A | Dec 11, 2023 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1A | Dec 7, 2023 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE CABINET AT SINK BASIN IN THE KITCHEN LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 309 | Dec 7, 2023 | INADEQUATE HOT WATER SUPPLY (VOLUME) · WATER SUPPLY§ 27-2024 ADMIN. CODE: PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES .. IN THE ENTIRE APARTMENT LOCATED AT APT 309, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1 | Dec 6, 2023 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT NORTH WALL IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1 | Dec 6, 2023 | REMOVE VERMIN · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF VERMIN FLIES AND GNATS IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1 | Dec 6, 2023 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT SOUTH WALL IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 1 | Dec 6, 2023 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX 35 SQFT AGGREGATE (15 SQFT AT EAST WALL, 15 SQFT AT NORTH WALL, APPROX 2 SQFT AT SOUTH WALL, AND 3 SQFT AT CEILING) EAST WALL IN THE PRIVATE HALLWAY LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 1 | Dec 6, 2023 | INADEQUATE HEAT · HEAT AND HOT WATER§ 27-2029 ADMIN. CODE: PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 1 | Dec 6, 2023 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE 3rd ROOM FROM EAST AT NORTH, THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1 | Dec 6, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILE IN THE BATHROOM LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 1 | Dec 6, 2023 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF HOT WATER EXCEEDS MAXIMUM ALLOWED TEMPERATURE OF 130 F AT ALL FIXTURES. WATER TEMPERATURE WAS FOUND TO BE 158 F AT THE KITCHEN SINK. THERMOMETER # 1121 IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1 | Dec 6, 2023 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1 | Dec 6, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE , REGLAZE THE BATH TUB IN THE BATHROOM LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1 | Dec 6, 2023 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT EAST WALL IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 1 | Dec 6, 2023 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX 4 SQFT AGGREGATE (2 SQFT AT EAST WALL AND 2 SQFT AT NORTH WALL) AT 1st CLOSET FROM NORTH AT EAST WALL WALL IN THE 3rd ROOM FROM EAST AT NORTH LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 108 | Dec 5, 2023 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROXIMATELY 2 SQUARE FEET AT WEST WALL, IN CLOSET 1ST FROM EAST AT SOUTH IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 108, 1st STORY, 7th APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 16140816 ISSUED 03-AUG-23 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class C | ClosedRENT IMPAIRING | 2 | Dec 4, 2023 | INADEQUATE HEAT · HEAT AND HOT WATER§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 2 | Dec 4, 2023 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOT WATER EXCEEDING THE MAXIMUM TEMPERATURE OF 130 DEGREES AT HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |