| Class B | Closed | — | Jan 11, 2021 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF AIR CONDITIONER PROTRUDING AT WINDOW SILL ON 2ND STORY BALCONY NORTHWEST STACK, BUILDING FRONT |
| Class B | ClosedRENT IMPAIRING | — | Jan 7, 2021 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSE HOLD ITEMS AT PUBLIC HALL, 2nd STORY |
| Class B | ClosedRENT IMPAIRING | — | Dec 31, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION MATERIALS AT BULKHEAD AT PUBLIC HALL STAIRS, 4th STORY |
| Class B | ClosedRENT IMPAIRING | — | Dec 31, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION MATERIALS AT PUBLIC HALL, 4th STORY |
| Class B | Closed | — | Dec 7, 2020 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCKSET AT ENTRANCE DOOR TO BUILDING AT PUBLIC HALL, 1st STORY |
| Class B | ClosedRENT IMPAIRING | — | Nov 23, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF A WOODEN WORK PLATFORM ERECTED AT PUBLIC HALL STAIRS, 4th STORY |
| Class B | Closed | — | Sep 8, 2020 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE AIR CONDITIONER BRACKETS AT 4TH AND 3RD STORIES BUILDING FRONT |
| Class B | Closed | — | Sep 8, 2020 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES FLOWER POTS AT 4TH STORY BALCONY NORTHWEST STACK, BUILDING FRONT AT FIRE ESCAPE |
| Class B | Closed | D3 | Sep 8, 2020 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT D3, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | D3 | Sep 8, 2020 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT D3, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | — | Sep 8, 2020 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF AIR CONDITIONER PROTRUDING AT WINDOW SILL ON 4TH AND 3RD STORY BALCONIES NORTHEAST STACK, BUILDING FRONT AT FIRE ESCAPE |
| Class B | Closed | — | Aug 31, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING AT PUBLIC HALL, 4th STORY |
| Class B | ClosedRENT IMPAIRING | — | Aug 31, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSTRUCTION MATERIALS AT BULKHEAD STAIRS , 4th STORY |
| Class B | ClosedRENT IMPAIRING | — | Aug 31, 2020 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL, 4th STORY |
| Class B | Closed | — | Aug 31, 2020 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE WIRE GLASS PANE AT 2ND UPPER SASH, 1ST WINDOW FROM NORTH AT WEST WALL AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Jun 23, 2020 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS PANE AT BUILDING ENTRANCE DOOR AT PUBLIC HALL, 1st STORY |
| Class B | ClosedRENT IMPAIRING | — | Jun 22, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT PUBLIC HALL, 4th STORY |
| Class B | ClosedRENT IMPAIRING | — | Jun 22, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF A REFRIGERATOR AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Jun 22, 2020 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE WIRE GLASS AT BUILDING ENTRANCE DOOR AT WEST WALL , 1st STORY |
| Class B | Closed | — | Jun 22, 2020 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE INNER COURT |
| Class B | Closed | — | Jun 3, 2020 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS PANE AT ENTRANCE DOOR OF BUILDING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Feb 26, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND SOUTH WALL WEST WALL AT BULKHEAD TO ROOF |
| Class B | ClosedRENT IMPAIRING | — | Feb 26, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSE HOLD ITEMS AT PUBLIC HALL, 4th STORY |
| Class B | Closed | — | Feb 21, 2020 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF AN A/C UNIT AT THE 3RD STORY BALCONY OF THE WEST STACK AT THE FRONT OF THE BUILDING |
| Class B | Closed | — | Feb 21, 2020 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF AN A/C UNIT AT THE 4TH STORY BALCONY OF THE EAST STACK AT THE FRONT OF THE BUILDING |
| Class B | Closed | — | Feb 18, 2020 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE HANDRAIL AT PUBLIC HALL STAIRS, 1st STORY |
| Class B | Closed | — | Feb 18, 2020 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING HANDRAIL AT EAST WALL AT VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class B | Closed | C6 | Feb 18, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CAULKING AROUND TUB BASE IN THE BATHROOM LOCATED AT APT C6, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | C6 | Feb 18, 2020 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE AT SOUTH WALL IN THE BATHROOM LOCATED AT APT C6, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | D4 | Jan 28, 2020 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT D4, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | D4 | Jan 28, 2020 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT D4, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | A6 | Jan 10, 2020 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE (INOPERATIVE) ELECTRICAL LIGHT FIXTURE AT THE CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT A6, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | D4 | Jan 10, 2020 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... 10 SQ,FT AT WINDOW SILL 1st WINDOW FRAME FROM EAST AT SOUTH WALL, 2nd WINDOW FRAME FROM EAST AT SOUTH WALL IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT D4, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | A6 | Jan 10, 2020 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE BASE CABINET AT THE WASH BASIN IN THE BATHROOM LOCATED AT APT A6, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | A6 | Jan 10, 2020 | REPLACE DEFECTIVE SINK, WATER CLOSET, WASH TUB · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPLACE THE BROKEN OR DEFECTIVE WASH BASIN IN THE BATHROOM LOCATED AT APT A6, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | D4 | Jan 9, 2020 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... 10 Q,FT AT WINDOW SILL 1st WINDOW FRAME FROM WEST AT NORTH WALL, 2nd WINDOW FRAME FROM WEST AT NORTH WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT D4, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | — | Nov 6, 2019 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS ( BICYCLES) AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Aug 16, 2019 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE MAIL BOXES AT PUBLIC HALL, 1st STORY |
| Class B | Closed | C6 | Aug 13, 2019 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCKING DEVICE MECHANISM ON DOOR IN THE ENTRANCE LOCATED AT APT C6, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Apr 8, 2019 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE AT CEILING AT PUBLIC HALL, 4th STORY |
| Class B | ClosedRENT IMPAIRING | — | Apr 8, 2019 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING BULKHEAD AT PUBLIC HALL, 4th STORY |
| Class B | Closed | — | Nov 7, 2018 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE RUBBER TREAD ON 3RD STEP UP FROM BOTTOM IN VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class B | ClosedRENT IMPAIRING | — | Oct 30, 2018 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF GARBAGE AT PUBLIC HALL, 4th STORY |
| Class B | ClosedRENT IMPAIRING | — | Oct 29, 2018 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF LARGE DRESSER CABINET AT PUBLIC HALL, 2nd STORY |
| Class B | Closed | — | Jul 13, 2018 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF AIR CONDITIONER PROTRUDING BEYOND WINDOW SILL AT 3RD STY FIRE ESCAPE BALCONY AT INNER YARD STACK AT FIRE ESCAPE |
| Class B | Closed | — | Jul 13, 2018 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE BULKHEAD DOOR LEADING TO THE ROOF AT PUBLIC HALL, 4th STORY |
| Class B | ClosedRENT IMPAIRING | — | Jun 28, 2018 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF STOVE AND WOOD DOORS PRESENTLY LOCATED AT PUBLIC HALL, 2nd STORY |
| Class B | Closed | — | Jun 28, 2018 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES ..FLOWER POTS AT 4TH STORY BALCONY AT 2nd FIRE ESCAPE FROM EAST AT NORTH |
| Class B | Closed | B5 | Apr 3, 2018 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR THAT IS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B5, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | B5 | Apr 3, 2018 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). THAT IS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B5, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST |