| Class B | Closed | 4C | Sep 30, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE BELL/BUZZER/INTERCOM SYSTEM FROM BUILDING STREET ENTRANCE TO NORTH2 ROOM LOCATED AT APT 4C, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class C | ClosedRENT IMPAIRING | 4C | Sep 30, 2022 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 4C, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4C | Sep 30, 2022 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE LOCATED AT APT 4C, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class C | Closed | 4C | Sep 30, 2022 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 4C, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class A | Closed | 4C | Sep 30, 2022 | RESET WATER CLOSET BOWL · SEWERS AND DRAINAGE§ 27-2026 ADM CODE RESET, SO AS TO SECURE A PROPER AND TIGHT CONNECTION, THE WATER CLOSET BOWL .. IN THE BATHROOM LOCATED AT APT 4C, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4C | Sep 30, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES IN THE KITCHENETTE LOCATED AT APT 4C, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4C | Sep 30, 2022 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT NORTH WALL IN THE KITCHENETTE LOCATED AT APT 4C, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4C | Sep 30, 2022 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). - MISSING LOCATED AT APT 4C, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class A | Closed | 5C | Sep 26, 2022 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 5C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 5C | Sep 26, 2022 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 5C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 5B | Jul 26, 2022 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX. 2 SQ FT AT THE WINDOW FRAME FROM NORTH AT EAST WALL, WINDOW FRAME FROM NORTH AT EAST WALL IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 15080943 ISSUED 25-MAR-22 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 5B | Jul 26, 2022 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX. 5 SQ FT AT THE NORTH WALL, WINDOW FRAME FROM WEST AT NORTH WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 15080944 ISSUED 25-MAR-22 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | — | Jun 28, 2022 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE FIRE RATED DOOR AT BUILDING ENTRANCE |
| Class B | Closed | — | Jun 9, 2022 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS PANE AT VESTUBULE DOOR IN THE PUBLIC HALL AT BASEMENT |
| Class C | Closed | — | Jun 9, 2022 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT ENTRANCE TO FIRE STAIRS AT PUBLIC HALL, 2ND FROM SOUTH AT WEST AT BASEMENT |
| Class C | Closed | — | Jun 9, 2022 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT FRONT ENTRANCE TO BUILDING AT BASEMENT |
| Class C | Closed | — | Jun 9, 2022 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT ENTRANCE TO FIRE STAIRS, 2ND FROM SOUTH AT WEST AT PUBLIC HALL, 1st STORY |
| Class C | Closed | 5B | May 31, 2022 | LEAD-BASED PAINT HAZARD- PRESUMED PAINT · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING IN THE FOYER LOCATED AT APT 5B, 4th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Closed | 5B | May 31, 2022 | LEAD-BASED PAINT HAZARD- PRESUMED PAINT · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING IN THE BATHROOM LOCATED AT APT 5B, 4th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class A | Closed | — | May 27, 2022 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | May 27, 2022 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS PANE AT ENTRANCE SECOND VESTIBULE DOOR |
| Class A | Closed | — | May 27, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | May 27, 2022 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY |
| Class C | Closed | 5B | May 26, 2022 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 0; WG TO REPLACE = 1; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2E | Mar 29, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT WEST WALL IN THE BATHROOM LOCATED AT APT 2E, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | 2E | Mar 29, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE INOPERATIVE BELL AND RETURN BUZZER SYSTEM FROM EXTERIOR ENTRANCE DOOR TO EAST WALL IN THE FOYER LOCATED AT APT 2E, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Mar 29, 2022 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR AT ROOF BULKHEAD AT EAST AT PUBLIC HALL, 4th STORY |
| Class B | Closed | 2E | Mar 29, 2022 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 2E, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | — | Mar 29, 2022 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR AT ROOF BULKHEAD AT NORTH SIDE AT PUBLIC HALL, 4th STORY |
| Class B | Closed | — | Mar 29, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE MAILBOX LOCKS FOR UNIT 2C AND 2D AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Mar 29, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT ROOF BULKHEAD AT EAST AT PUBLIC HALL, 4th STORY |
| Class B | Closed | — | Mar 29, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT ALL WALLS AND CEILING ROOF BULKHEAD AT NORTH AT PUBLIC HALL, 4th STORY |
| Class A | Closed | — | Mar 29, 2022 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AND CEILING AT ROOF BULKHEAD AT NORTH AT PUBLIC HALL, 4th STORY |
| Class A | Closed | — | Mar 29, 2022 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AND ALL WALLS AT PUBLIC HALL, 4th STORY |
| Class B | Closed | — | Mar 29, 2022 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 3rd STORY |
| Class A | Closed | — | Mar 29, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 4th STORY |
| Class B | Closed | 2C | Mar 29, 2022 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2C | Mar 29, 2022 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | — | Mar 29, 2022 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CEILING AND ALL WALLS AT ROOF BULKHEAD AT PUBLIC HALL, 4th STORY |
| Class B | ClosedRENT IMPAIRING | — | Mar 29, 2022 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILNG AT PUBLIC HALL, 4th STORY |
| Class A | Closed | 2C | Mar 29, 2022 | REFIT DOORS ETC. · EGRESS§ 27-2005 ADM CODE REFIT APARTMENT ENTRACE DOOR IN THE ENTRANCE LOCATED AT APT 2C, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2E | Mar 29, 2022 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 2E, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | — | Mar 29, 2022 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELEVATOR MIRROR |
| Class C | Closed | 2D | Mar 29, 2022 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT APARTMENT IN THE ENTRANCE LOCATED AT APT 2D, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2C | Mar 29, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE INTERCOM AT EAST WALL TO BUILDING FRONT IN THE FOYER LOCATED AT APT 2C, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2C | Mar 29, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE DEFECTIVE MORTISE LOCK SET AT APARTMENT ENTRANCE DOOR. IN THE ENTRANCE LOCATED AT APT 2C, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | Closed | 2C | Mar 29, 2022 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 2C, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | — | Mar 29, 2022 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AND ALL WALLS AT PUBLIC HALL, 3rd STORY |
| Class A | Closed | — | Mar 29, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 3rd STORY |
| Class B | ClosedRENT IMPAIRING | — | Mar 29, 2022 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING, EAST AND WEST WALLS AT ROOF BULKHEAD AT EAST AT PUBLIC HALL, 4th STORY |