| Class B | Closed | 5D | Nov 26, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 5D, 5th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3E | Nov 26, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD SUB FLOOR IN THE KITCHEN LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 5F | Nov 26, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREAT THAN 10 SQ FEET AT NORTH AND EAST WALLS IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 6G | Nov 26, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ FEET AT CEILIING AND SOUTH WALL IN THE BATHROOM LOCATED AT APT 6G, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 1F | Nov 26, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1F, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3E | Nov 26, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING, ALL WALLS AND TRIM THROUGHOUT IN THE ENTIRE APARTMENT LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1F | Nov 26, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1F, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 5F | Nov 26, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 2F | Nov 26, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WINDOW COUNTER BALANCE AT UPPER SASH IN THE 1st ROOM FROM NORTH LOCATED AT APT 2F, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 6B | Nov 26, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREAATER THAN 10 SQUARE FEET AT WEST WINDOW FRAME IN THE BATHROOM LOCATED AT APT 6B, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5F | Nov 26, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING,NORTH AND EAST WALLS IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3E | Nov 26, 2024 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ESCUTCHEON PLATE AT RISER TOP IN THE BATHROOM LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1A | Nov 19, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT ALL CEILING, ALL WALL AND TRIM THROUGHOUT IN THE ENTIRE APARTMENT LOCATED AT APT 1A, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1A | Nov 19, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ FEET AT CEILING AND WEST WALL IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1A | Nov 19, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE 3rd ROOM FROM EAST LOCATED AT APT 1A, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1E | Nov 19, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 4th ROOM FROM NORTH LOCATED AT APT 1E, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1E | Nov 19, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE PRIVATE HALLWAY LOCATED AT APT 1E, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1A | Nov 19, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ FEET AT WEST AND NORTH WALLS IN THE 3rd ROOM FROM EAST LOCATED AT APT 1A, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1A | Nov 19, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ESCUTCHEON PLATE AT RISER BOTTOM IN THE KITCHEN LOCATED AT APT 1A, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE NORTH 2 WINDOW COUNTER BALANCE AT UPPER AND LOWER SASHES IN THE 4th ROOM FROM NORTH LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE NORTH 1 WINDOW COUNTER BALANCE AT UPPER AND LOWER SASHES IN THE 4th ROOM FROM NORTH LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE NORTH 2 WINDOW COUNTER BALANCE AT UPPER AND LOWER SASHES IN THE 1st ROOM FROM NORTH LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE NORTH 1 WINDOW COUNTER BALANCE AT UPPER AND LOWER SASHES IN THE 1st ROOM FROM NORTH LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1A | Nov 19, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1E | Nov 19, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WEST 2 WINDOW COUNTER BALANCES AT UPPER AND LOWER SASHES IN THE 1st ROOM FROM NORTH LOCATED AT APT 1E, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1E | Nov 19, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WEST 1 WINDOW COUNTER BALANCES AT UPPER AND LOWER SASHES IN THE 1st ROOM FROM NORTH LOCATED AT APT 1E, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1E | Nov 19, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ESCUTCHEON PLATE AT RISER TOP IN THE 1st ROOM FROM NORTH LOCATED AT APT 1E, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1E | Nov 19, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 1st ROOM FROM NORTH LOCATED AT APT 1E, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2E | Nov 19, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE DOOR BELL AT IN THE ENTRANCE LOCATED AT APT 2E, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1A | Nov 19, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD SADDLE IN THE KITCHEN LOCATED AT APT 1A, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 4C | Nov 15, 2024 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 4C, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 4C | Nov 15, 2024 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE ESCUTCHEON PLATE AT RISER CEILING IN THE KITCHEN LOCATED AT APT 4C, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 4C | Nov 15, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER SASH IN WEST WINDOW IN THE KITCHEN LOCATED AT APT 4C, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 4C | Nov 15, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOORING AT RISER IN THE 4th ROOM FROM NORTH LOCATED AT APT 4C, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 4C | Nov 15, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AROUND RISER IN THE 4th ROOM FROM NORTH LOCATED AT APT 4C, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 4C | Nov 15, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOORING IN THE KITCHEN LOCATED AT APT 4C, 4th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5F | Nov 15, 2024 | PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES OUTLET AT EAST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Nov 14, 2024 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE ENTIRE CELLAR |
| Class B | Closed | — | Nov 14, 2024 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE PUBLIC HALLWAYS ON ALL FLOORS |
| Class B | Closed | 5D | Nov 14, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT 5D, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | — | Nov 14, 2024 | REMOVE VERMIN · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF VERMIN MOSQUITOES |
| Class B | Closed | 2D | Nov 14, 2024 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ESCUTCHEON PLATE AT RISER TOP IN THE BATHROOM LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2D | Nov 14, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEIILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 5D | Nov 14, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5D, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 5D | Nov 14, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5D, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |