| Class A | Closed | — | Nov 9, 2018 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AT PUBLIC HALL, 1st STORY |
| Class B | ClosedRENT IMPAIRING | — | Nov 9, 2018 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF CONSISTING OF STROLLERS AND SCOOTERS AT THE WEST SECTION AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Nov 9, 2018 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM UNACCEPTABLE ON PAPER AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Nov 9, 2018 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE WEST WALL AT PUBLIC HALL STAIRS, 3rd STORY |
| Class A | Closed | — | Sep 28, 2018 | IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR .. AT PUBLIC HALL |
| Class A | Closed | — | Sep 28, 2018 | POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX ... AT PUBLIC HALL |
| Class A | Closed | — | Sep 28, 2018 | POST SIGN INDICATING NAME AND ADDRESS OF JANITOR, ETC. · POSTING/SIGNAGE§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL |
| Class A | Closed | — | Sep 28, 2018 | POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. AT PUBLIC HALL |
| Class A | Closed | — | Jul 5, 2018 | POST GAS LEAK NOTICE · POSTING/SIGNAGE§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Jun 21, 2018 | POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Jun 15, 2018 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM ... AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Jun 15, 2018 | POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY |
| Class C | Closed | B4 | Jun 15, 2018 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1; WG TO REPLACE = 0; WG TO REPAIR = 1; IN THE 4th ROOM FROM EAST LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | — | Jun 15, 2018 | POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX ... AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | May 16, 2018 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF AIR CONDITIONERS PROTRUDING BEYOIND WINDOW SILL AT 2ND AND 3RD STORIES FIRE ESCAPE BALCONIES AT FRONT BUILDING NORTH STACK |
| Class C | Closed | — | May 2, 2018 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING HAND RAIL ON SOUTH WALL AT PUBLIC HALL, 1st STORY, SECTION AT SOUTH |
| Class A | Closed | — | May 2, 2018 | POST GAS LEAK NOTICE · POSTING/SIGNAGE§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED |
| Class A | Closed | — | May 2, 2018 | POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD., 1st STORY |
| Class C | Closed | — | May 2, 2018 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING HAND RAIL ON NORTH WALL AT PUBLIC HALL, 1st STORY, SECTION AT NORTH |
| Class B | Closed | — | Apr 27, 2018 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE STEEL LINTELS ABOVE WINDOWS AT NORTH SIDE OF BUILDING , ALL STORIES |
| Class C | Closed | — | Apr 24, 2018 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE 3 PANES WIRE GLASS IN SKY LIGHT AT PUBLIC HALL STAIRS BULKHEAD , 4th STORY, SECTION AT SOUTH |
| Class B | Closed | — | Apr 24, 2018 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 2007, 204.1 HMC CODE: ARRANGE AND MAKE SELF-CLOSING THE DOORS ROOF DOOR , SECTION AT NORTH |
| Class C | Closed | — | Apr 24, 2018 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE 6 PANES WIRE GLASS AT SKYLIGHT, PUBLIC HALL STAIRS BULKHEAD , 4th STORY, SECTION AT NORTH |
| Class A | Closed | — | Apr 24, 2018 | PAINT METAL · PAINTING§ 27-2014 ADM CODE AND DEPT. RULES AND REGULATIONS. SCRAPE AND REMOVE RUST SCALES AND PAINT WITH 2 COATS OF PAINT FIRE ESCAPES AT FRONT OF BUILDING ALL STORIES , NORTH AND SOUTH STACKS |
| Class A | Closed | — | Apr 24, 2018 | PAINT METAL · PAINTING§ 27-2014 ADM CODE AND DEPT. RULES AND REGULATIONS. SCRAPE AND REMOVE RUST SCALES AND PAINT WITH 2 COATS OF PAINT FIRE ESCAPES AT REAR OF BUILDING, ALL STORIES , NORTH AND SOUTH STACKS |
| Class A | Closed | — | Apr 24, 2018 | PAINT METAL · PAINTING§ 27-2014 ADM CODE AND DEPT. RULES AND REGULATIONS. SCRAPE AND REMOVE RUST SCALES AND PAINT WITH 2 COATS OF PAINT FIRE ESCAPES AT NORTH SIDE OF BUILDING , ALL STORIES, EAST AND WEST STACKS |
| Class A | Closed | — | Apr 24, 2018 | PAINT METAL · PAINTING§ 27-2014 ADM CODE AND DEPT. RULES AND REGULATIONS. SCRAPE AND REMOVE RUST SCALES AND PAINT WITH 2 COATS OF PAINT FIRE ESCAPES AT CENTER COURT , ALL SORIES NORTH AND SOUTH STACKS |
| Class B | Closed | — | Apr 24, 2018 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE STEEL LINTELS ABOVE 4TH., 5TH., 6TH., 7TH., 8TH., 9TH., 10TH.,AND 11 TH.,WINDOWS FROM SOUTH AT FRONT OF BUILDING , 1st STORY |
| Class B | Closed | — | Apr 24, 2018 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE ERODED MOTAR JOINTS AT BRICKS FROM GROUND UP TO TOP OF PARAPET WALL , NORTH SIDE OF BUILDING . |
| Class C | Closed | — | Apr 24, 2018 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE WIRE GLASS IN LOWER SASH OF WINDOW AT PUBLIC HALL, 3rd STORY, SECTION AT NORTH |
| Class C | ClosedRENT IMPAIRING | — | Apr 24, 2018 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK ABOVE CEILING AT PUBLIC HALL, 4th STORY |
| Class B | Closed | — | Apr 24, 2018 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDING CEILING AT PUBLIC HALL, 4th STORY |
| Class A | Closed | — | Apr 24, 2018 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CEILING AT PUBLIC HALL, 4th STORY |
| Class B | Closed | B3 | Apr 11, 2018 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT B3, 2nd STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION AT NORTH |
| Class A | Closed | — | Apr 9, 2018 | POST GAS LEAK NOTICE · POSTING/SIGNAGE§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY |
| Class B | Closed | B4 | Mar 16, 2018 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILE AT WEST WALL IN THE BATHROOM LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | B4 | Mar 16, 2018 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD SILL IN THE BATHROOM LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | B4 | Mar 16, 2018 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE REGLAZE TUB IN THE BATHROOM LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | B4 | Mar 16, 2018 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT BASEBOARD AT WEST WALL, 1st WINDOW FRAME FROM WEST AT NORTH WALL, 1st WINDOW FRAME FROM NORTH AT EAST WALL, BASEBOARD AT EAST WALL, 2nd WINDOW FRAME FROM NORTH AT EAST WALL, 3rd WINDOW FRAME FROM NORTH AT EAST WALL, 1st DOOR FRAME FROM SOUTH AT WEST WALL IN THE 1st ROOM FROM EAST LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | B4 | Mar 16, 2018 | LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st RADIATOR FROM NORTH AT EAST WALL IN THE 1st ROOM FROM EAST LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | B4 | Mar 16, 2018 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class C | Closed | B4 | Mar 16, 2018 | LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM EAST AT SOUTH WALL, 1st DOOR FRAME FROM EAST AT SOUTH WALL, 1st DUMB WAITER FROM EAST AT SOUTH WALL IN THE FOYER LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | B4 | Mar 16, 2018 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE KITCHEN , THE 4th ROOM FROM EAST, THE BATHROOM LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | B4 | Mar 16, 2018 | PAINT METAL · PAINTING§ 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION AT 1st RISER FROM NORTH AT EAST WALL IN THE 1st ROOM FROM EAST LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | — | Mar 16, 2018 | POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Mar 16, 2018 | POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Mar 16, 2018 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM SIGN MISSING ON WALL AT PUBLIC HALL, 1st STORY |
| Class B | Closed | B4 | Mar 16, 2018 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT NORTH WALL, WEST WALL, SOUTH WALL, CEILING IN THE 4th ROOM FROM EAST LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | B4 | Mar 16, 2018 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT WEST WALL, NORTH WALL, EAST WALL, SOUTH WALL, CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | B4 | Mar 16, 2018 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING, NORTH WALL, 1st WINDOW FRAME FROM WEST AT NORTH WALL, WEST WALL, SOUTH WALL, EAST WALL IN THE BATHROOM LOCATED AT APT B4, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH |