| Class A | Closed | 3B | Sep 29, 2021 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AND CEILING IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | ClosedRENT IMPAIRING | 3B | Sep 29, 2021 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK ABOVE CEILING IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3B | Sep 24, 2021 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class A | Closed | 3B | Sep 24, 2021 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AND CEILING IN THE ENTIRE APARTMENT LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class A | Closed | 3B | Sep 24, 2021 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AND CEILING IN THE 2nd ROOM FROM EAST LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3B | Sep 24, 2021 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | 3B | Sep 24, 2021 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK THROUGH CEILING IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 3B | Sep 24, 2021 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND WEST WALL IN THE FOYER LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | May 14, 2021 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE DOOR AT BUILDING ENTRANCE , 1st STORY |
| Class B | Closed | — | May 3, 2021 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE KNOB AT BUILDING ENTRANCE DOOR , 1st STORY |
| Class B | ClosedRENT IMPAIRING | — | May 3, 2021 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING AT PUBLIC HALL, 3rd STORY |
| Class B | Closed | — | May 3, 2021 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT THE CEILING AT PUBLIC HALL, 3rd STORY |
| Class A | Closed | — | May 3, 2021 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING AT PUBLIC HALL, 3rd STORY |
| Class A | Closed | — | Apr 15, 2021 | POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. |
| Class A | Closed | — | Apr 15, 2021 | POST GAS LEAK NOTICE · POSTING/SIGNAGE§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED |
| Class A | Closed | — | Apr 15, 2021 | POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Apr 15, 2021 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Apr 15, 2021 | POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY |
| Class A | Open | — | Apr 6, 2021 | FILE ANNUAL BEDBUG REPORT · FILING: BEDBUGS(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS. |
| Class B | Closed | — | Mar 11, 2021 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE DOOR KNOB AT BULDING ENTRANCE |
| Class B | Closed | — | Feb 25, 2021 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE GLASS PANELS AT FRONT ENTRANCE DOOR TO BUILDING , 1st STORY |
| Class B | Closed | — | Feb 25, 2021 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PLEXI-GLASS PANELS INSTALLED AT FRONT ENTRANCE DOOR TO BUILDING , 1st STORY |
| Class A | Closed | — | Jan 19, 2021 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT BUILDING ENTRANCE DOOR AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Jan 19, 2021 | PROVIDE LIGHT - Not Less that 60 Watt incadescent · ARTIFICIAL LIGHTING§ 27-2039 ADM CODE PROVIDE ADEQUATE LIGHT OF NOT LESS THAN 60 WATTS INCANDESCENT OR EQUIVALENT ILLUMINATION AT 2ND STORY AT PUBLIC HALL |
| Class B | Closed | — | Jan 19, 2021 | PROVIDE LIGHT - Not Less that 60 Watt incadescent · ARTIFICIAL LIGHTING§ 27-2039 ADM CODE PROVIDE ADEQUATE LIGHT OF NOT LESS THAN 60 WATTS INCANDESCENT OR EQUIVALENT ILLUMINATION AT 3RD STORY AT PUBLIC HALL |
| Class B | Closed | — | Nov 23, 2020 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES ..LARGE TREE LIMB AT 2ND STORY BALCONY AT 1st FIRE ESCAPE FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | — | Nov 16, 2020 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING AT PUBLIC HALL, 3rd STORY |
| Class B | Closed | — | Nov 16, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 3rd STORY |
| Class A | Closed | — | Nov 16, 2020 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING AT PUBLIC HALL, 3rd STORY |
| Class B | Closed | — | Nov 16, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 2nd STORY |
| Class A | Closed | — | Nov 16, 2020 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING AT PUBLIC HALL, 2nd STORY |
| Class A | Closed | — | Nov 12, 2020 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING AT THE BULKHEAD STY TO ROOF. AT PUBLIC HALL, 3rd STORY |
| Class B | Closed | — | Nov 12, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE THE CEILING WITH FIRE RETARDING MATERIALS AT THE BULK HEAD TO ROOF. AT PUBLIC HALL, 3rd STORY |
| Class A | Closed | — | Nov 12, 2020 | CLEANSE · CLEANING§ 27-2011 ADM CODE CLEANSE TO THE SATISFACTION OF THIS DEPARTMENT THE THE FLOORS, LANDINGS AND STAIRS AT ALL STY'S AT PUBLIC HALL |
| Class B | ClosedRENT IMPAIRING | — | Nov 12, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF SHOPPING CARTS,SHOE AND OTHER HOUSE HOLD ITEMS AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Nov 12, 2020 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES FLOWER POTS AND OTHER HOUSE HOLD ITEMS 1ST BALCONY AT BUILDING FRONT AT FIRE ESCAPE, 2nd STORY |
| Class B | ClosedRENT IMPAIRING | — | Nov 12, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF SHOPPING CARTS, CARD BOARD BOXES AND OTHER HOUSE HOLD ITEMS AT PUBLIC HALL, 3rd STORY |
| Class B | Closed | — | Nov 6, 2020 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE REAR YARD |
| Class B | Closed | — | Nov 6, 2020 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE NORTH COURT |
| Class B | ClosedRENT IMPAIRING | — | Oct 27, 2020 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF LADDER AND CONSTRUCTION MATERIAL AT BULKHEAD |
| Class A | Closed | — | Oct 21, 2020 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT BULKHEAD CEILING |
| Class B | Closed | — | Oct 21, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING AT PUBLIC HALL, 2nd STORY |
| Class A | Closed | — | Oct 21, 2020 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CEILING AT PUBLIC HALL, 2nd STORY |
| Class C | ClosedRENT IMPAIRING | — | Oct 21, 2020 | REMOVE ILLEGAL FASTENING · EGRESS§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF SLIDE BOLT ARRANGED FOR PADLOCK INSTALLED AT METAL GATE AT BUILDING EAST YARD |
| Class B | ClosedRENT IMPAIRING | — | Oct 21, 2020 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER BULKHEAD CEILING |
| Class C | Closed | — | Oct 21, 2020 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 2007 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS AT ROOF BULKHEAD |
| Class B | Closed | — | Oct 21, 2020 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT BULKHEAD CEILING |
| Class C | Closed | — | Jan 15, 2019 | PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM BOILER ROOM DOOR LOCKED AT CELLAR AT CELLAR |
| Class C | ClosedRENT IMPAIRING | 3B | Jan 14, 2019 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | ClosedRENT IMPAIRING | 3B | Dec 26, 2018 | INADEQUATE HOT WATER · HEAT AND HOT WATER§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 3B, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |