| Class B | Closed | 603 | Jun 21, 2023 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX. 12 SQ.FT. AT NORTH WALL IN THE BATHROOM LOCATED AT APT 603, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 603 | Jun 21, 2023 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 603, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 603 | Jun 21, 2023 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 603, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 113 | Jun 1, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL AND RETURN BUZZER SYSTEM FROM VESTIBULE BUILDING TO WEST WALL IN THE PRIVATE HALLWAY LOCATED AT APT 113, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 111 | Jun 1, 2023 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND SOUTH WALL IN THE BATHROOM LOCATED AT APT 111, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 111 | Jun 1, 2023 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INNER GLASS AT LOWER WONDOW SASH IN THE BATHROOM LOCATED AT APT 111, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 111 | Mar 9, 2023 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 111, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Mar 9, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Mar 9, 2023 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 113 | Oct 3, 2022 | PROVIDE LIGHT - Not Less that 60 Watt incadescent · ARTIFICIAL LIGHTING§ 27-2039 ADM CODE PROVIDE ADEQUATE LIGHT OF NOT LESS THAN 60 WATTS INCANDESCENT OR EQUIVALENT ILLUMINATION TO ROOM EAST 1 IN THE 1st ROOM FROM EAST LOCATED AT APT 113, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Sep 6, 2022 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES FLOWER POTS ON 2ND AND 5TH STORIES BALCONY STACK FROM SOUTH AT EAST( REAR) AT FIRE ESCAPE |
| Class B | Closed | — | Aug 10, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT VESTIBULE AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 314 | Jun 8, 2022 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 314 | May 31, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE MORTISE DOOR LOCK IN THE ENTRANCE LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | — | May 31, 2022 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF OVERGROWN VEGETATION PREVENTING DROP LADDER FROM FULL EXTENDING DOWN AT WEST STACK AT BUILDING FRONT AT FIRE ESCAPE |
| Class B | Closed | 314 | May 31, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CAULKING AROUND BATHTUB IN THE BATHROOM LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 314 | May 31, 2022 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 314 | May 31, 2022 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 314 | May 31, 2022 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | — | Apr 12, 2022 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF METAL LADDER AT BULKHEAD STAIRS . AT PUBLIC HALL, 6th STORY, SECTION ''EAST'' |
| Class B | ClosedRENT IMPAIRING | — | Mar 16, 2022 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF METAL LADDER AT PUBLIC HALL STAIRS, 6th STORY |
| Class B | Closed | 312 | Mar 14, 2022 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 312, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 312 | Mar 14, 2022 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 312, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 113 | Feb 28, 2022 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION AT WASTELINE UNDER SINK IN THE KITCHEN LOCATED AT APT 113, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | 113 | Feb 28, 2022 | REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN AT SINK IN THE KITCHEN LOCATED AT APT 113, 1st STORY |
| Class B | Closed | 314 | Jan 31, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL TILE FLOOR IN THE KITCHEN LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''south'' |
| Class B | ClosedRENT IMPAIRING | 314 | Jan 31, 2022 | REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN WASTE LINE AT BATHTUB IN THE BATHROOM LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''south'' |
| Class B | Closed | 314 | Jan 31, 2022 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT HOT AND COLD WATER FIXTURES AT BATH TUB IN THE BATHROOM LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''south'' |
| Class B | Closed | 314 | Jan 31, 2022 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION AT WASTELINE AT SINK IN THE KITCHEN LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''south'' |
| Class B | Closed | 607 | Jan 26, 2022 | PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT CEILING IN THE KITCHEN LOCATED AT APT 607, 6th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | — | Jan 26, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AT PUBLIC HALL, 6th STORY |
| Class B | Closed | 607 | Jan 26, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT EAST WALL IN THE BATHROOM LOCATED AT APT 607, 6th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 607 | Jan 26, 2022 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 607, 6th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 607 | Jan 26, 2022 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 607, 6th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 607 | Jan 26, 2022 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 607, 6th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 314 | Jan 19, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE INTERCOM SYSTEM FROM BUILDING ENTRANCE TO RETURN BOX AT WEST WALL IN THE FOYER LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''south'' |
| Class B | ClosedRENT IMPAIRING | 113 | Jan 18, 2022 | REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN SINK WASTE LINE IN THE KITCHEN LOCATED AT APT 113, 1st STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 113 | Jan 18, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FORMICA COUNTER TOP IN THE KITCHEN LOCATED AT APT 113, 1st STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 113 | Jan 13, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE BUZZER AT EAST WALL IN THE FOYER LOCATED AT APT 113, 1st STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 314 | Jan 12, 2022 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE VINYLE FLOOR TILE IN THE KITCHEN LOCATED AT APT 314, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 314 | Jan 12, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE INOPERATIVE BELL BUZZER FROM BUILDING FRONT ENTRANCE TO BOX AT EAST WALL IN THE FOYER LOCATED AT APT 314, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 314 | Jan 12, 2022 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION AT SINK WASTELINE IN THE KITCHEN LOCATED AT APT 314, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 314 | Jan 12, 2022 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE KITCHEN LOCATED AT APT 314, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 113 | Jan 10, 2022 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE BELL BUZZA SYSTEM IN THE ENTIRE APARTMENT LOCATED AT APT 113, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 314 | Jan 3, 2022 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT NORTH WALL APPROX 1 SQFT IN THE BATHROOM LOCATED AT APT 314, 3rd STORY, 3rd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 14521880 ISSUED 01-SEP-21 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 113 | Dec 30, 2021 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION WASTE LINE AT SINK IN THE KITCHEN LOCATED AT APT 113, 1st STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 113 | Dec 30, 2021 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE UPPER CABINETS AT NORTH WALL IN THE KITCHEN LOCATED AT APT 113, 1st STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 113 | Dec 30, 2021 | PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT CEILING IN THE BATHROOM LOCATED AT APT 113, 1st STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 113 | Dec 30, 2021 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE COUNTERTOP AT BASE CABINET, EAST WALL IN THE KITCHEN LOCATED AT APT 113, 1st STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 113 | Dec 30, 2021 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE COUNTERTOP AT SINK IN THE KITCHEN LOCATED AT APT 113, 1st STORY, 3rd APARTMENT FROM WEST AT NORTH |