| Class A | Closed | 5N | Oct 20, 2015 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE 1st ROOM FROM EAST, THE 3rd BATHROOM FROM EAST AT NORTH, THE 4th BATHROOM FROM EAST AT NORTH LOCATED AT APT 5N, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2Y | Oct 19, 2015 | REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF MISSING OUTLET COVER AT SOUTH AND WEST WALL IN THE 3rd ROOM FROM NORTH AT EAST LOCATED AT APT 2Y, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2Y | Oct 19, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT WEST WALL IN THE 1st BATHROOM FROM NORTH AT EAST LOCATED AT APT 2Y, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1X | Oct 19, 2015 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1X, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT WEST |
| Class B | Closed | 1X | Oct 19, 2015 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1X, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT WEST |
| Class A | Closed | 1X | Oct 19, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT EAST WALL IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 1X, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT WEST |
| Class B | Closed | 1X | Oct 19, 2015 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... APPX 12 SQ FT AT IN THE BATHROOM LOCATED AT APT 1X, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT WEST |
| Class A | Closed | 1X | Oct 19, 2015 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE BATHROOM , THE KITCHEN , THE 1st ROOM FROM NORTH AT EAST, THE 2nd ROOM FROM NORTH AT EAST, THE 3rd ROOM FROM NORTH LOCATED AT APT 1X, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT WEST |
| Class B | Closed | 3U | Oct 15, 2015 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... (BLDG 1711) 10 SQ FT AT CEILING IN THE BATHROOM LOCATED AT APT 3U, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH , 2nd SECTION FROM EAST AT SOUTHEAST |
| Class C | Closed | 2B | Oct 15, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE 1st BATHROOM FROM EAST LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''(120)'', 2nd FROM EAST AT SOUTHEAST |
| Class A | Closed | 3U | Oct 15, 2015 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE KITCHEN , THE 1st ROOM FROM EAST AT NORTH, THE 2nd ROOM FROM EAST AT NORTH, THE 3rd ROOM FROM EAST, THE BATHROOM LOCATED AT APT 3U, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH , 2nd SECTION FROM EAST AT SOUTHEAST |
| Class B | Closed | 6N | Oct 15, 2015 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE ELECTRIC OUTLET COVER AT SOUTH WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 6N, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 4V | Oct 15, 2015 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING, EAST AND NORTH WALLS (BLDG 1711) IN THE BATHROOM LOCATED AT APT 4V, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH , 2nd SECTION FROM EAST AT SOUTHEAST |
| Class C | Closed | 4V | Oct 15, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK ACTIVE WATER LEAK AT CEILING AND EAST WALL (BLDG 1711) IN THE BATHROOM LOCATED AT APT 4V, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH , 2nd SECTION FROM EAST AT SOUTHEAST |
| Class C | Closed | 2B | Oct 15, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE 2nd BATHROOM FROM EAST LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''(120)'', 2nd FROM EAST AT SOUTHEAST |
| Class B | Closed | 2B | Oct 15, 2015 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st BATHROOM FROM EAST LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''(120)'', 2nd FROM EAST AT SOUTHEAST |
| Class B | Closed | 1B | Oct 15, 2015 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILE FLOOR IN THE 1st BATHROOM FROM EAST LOCATED AT APT 1B, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''(120)'', 2nd FROM EAST AT SOUTHEAST |
| Class B | Closed | 1B | Oct 15, 2015 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILE FLOOR IN THE 2nd BATHROOM FROM EAST LOCATED AT APT 1B, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''(120)'', 2nd FROM EAST AT SOUTHEAST |
| Class A | Closed | 4W | Oct 14, 2015 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WINDOW FRAME AT NORTH IN THE 3rd ROOM FROM NORTH AT EAST LOCATED AT APT 4W, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6N | Oct 14, 2015 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6N, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6N | Oct 14, 2015 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR SOUTH WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 6N, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6E | Oct 14, 2015 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE KITCHEN LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6E | Oct 14, 2015 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPERATIVE LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6E | Oct 14, 2015 | NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 6N | Oct 14, 2015 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 6N, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6E | Oct 14, 2015 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 4W | Oct 14, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 3rd ROOM FROM NORTH AT EAST LOCATED AT APT 4W, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6E | Oct 14, 2015 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 6E, 6th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 1C | Oct 13, 2015 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE 1st BATHROOM , THE 2nd BATHROOM , THE 1st ROOM FROM NORTH AT WEST, THE PRIVATE HALLWAY LOCATED AT APT 1C, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''(120)'', 2nd FROM EAST AT SOUTHEAST |
| Class B | ClosedRENT IMPAIRING | 1C | Oct 13, 2015 | REPAIR FLUSHING APPARATUS OF WATER CLOSET · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET , IN THE 1st BATHROOM LOCATED AT APT 1C, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''(120)'', 2nd FROM EAST AT SOUTHEAST |
| Class B | ClosedRENT IMPAIRING | 6H | Oct 8, 2015 | REPAIR LEAKY PIPES · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE WATER SUPPLY PIPE AT WATER CLOSET, IN THE BATHROOM LOCATED AT APT 6H, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4K | Oct 8, 2015 | NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 4K, 4th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 4K | Oct 8, 2015 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4K, 4th STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 2YY | Oct 8, 2015 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 9; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 2YY, 2nd STORY, 5th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 2XX | Oct 8, 2015 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT CEILING. APPROX 4 SQ FT IN THE BATHROOM LOCATED AT APT 2XX, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2XX | Oct 8, 2015 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT SOUTH WALL, APPROX 3 SQ FT IN THE BATHROOM LOCATED AT APT 2XX, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2XX | Oct 8, 2015 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE UNHINGED CABINET DOORS AT SINK IN THE KITCHEN LOCATED AT APT 2XX, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2XX | Oct 8, 2015 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT EAST WALL, APP0X 3 SQ FT IN THE BATHROOM LOCATED AT APT 2XX, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2XX | Oct 8, 2015 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2XX, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2XX | Oct 8, 2015 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2XX, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1O | Oct 6, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 2nd PRIVATE HALLWAY LOCATED AT APT 1O, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1O | Oct 6, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st BATHROOM LOCATED AT APT 1O, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1O | Oct 6, 2015 | REMOVE BARS OR GATES FROM NON FIRE ESCAPE WINDOW · EGRESS§ 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM AT LEAST 1 WINDOW OR PROVIDE APPROVED TYPE GATE .. LOCATED AT APT 1O, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class A | Closed | 1O | Oct 6, 2015 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE 1st ROOM FROM NORTH AT WEST, THE 1st BATHROOM , THE 2nd BATHROOM , THE 1st PRIVATE HALLWAY , THE 2nd PRIVATE HALLWAY , THE 2nd ROOM FROM NORTH AT WEST, THE 3rd ROOM FROM NORTH AT WEST, THE 3rd ROOM FROM NORTH AT EAST, THE 3rd ROOM FROM NORTH AT CENTER LOCATED AT APT 1O, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1O | Oct 6, 2015 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT SOUTH WALL IN THE 1st PRIVATE HALLWAY LOCATED AT APT 1O, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6H | Oct 5, 2015 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT EAST WALL, (APPROX 2 SQUARE FEET) IN THE 3rd ROOM FROM NORTH LOCATED AT APT 6H, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 6H | Oct 5, 2015 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 2007, 204.1 HMC CODE: ARRANGE AND MAKE SELF-CLOSING THE DOORS ... IN THE ENTRANCE LOCATED AT APT 6H, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 6H | Oct 5, 2015 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION AT SINK WASTELINE, IN THE KITCHEN LOCATED AT APT 6H, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 6H | Oct 5, 2015 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING, IN THE ENTIRE APARTMENT LOCATED AT APT 6H, 6th STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Oct 2, 2015 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE TOTAL OF 18 MAILBOXES AT PUBLIC HALL, 1st STORY |