| Class B | Open | — | Dec 15, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL AT NORTHWEST , 1st STORY |
| Class B | Open | D006 | Dec 15, 2025 | REMOVE VERMIN · EXTERMINATION & RODENT ERADICATION566 (B) 27-2021.4 HMC: ABATE THE NUISANCE CONSISTING OF PESTS. EVIDENCE OF KNATTS IN THE ENTIRE APARTMENT LOCATED AT APT D006, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | D006 | Dec 2, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES INOPERABLE IN THE ENTIRE APARTMENT LOCATED AT APT D006, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | D006 | Nov 25, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS THAT IS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT BSMT-APT D006, 1st BSMT-APT FROM SOUTH AT WEST , SECTION ''D'' |
| Class B | Open | D006 | Nov 25, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES THAT IS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT BSMT-APT D006, 1st BSMT-APT FROM SOUTH AT WEST , SECTION ''D'' |
| Class B | OpenRENT IMPAIRING | B905 | Nov 24, 2025 | REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN WASTELINE AT WASHBASIN IN THE 1st BATHROOM FROM NORTH LOCATED AT APT B905, 9th STORY, 5th APARTMENT FROM NORTH AT EAST , SECTION ''B'' |
| Class B | Open | B905 | Nov 24, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT B905, 9th STORY, 5th APARTMENT FROM NORTH AT EAST , SECTION ''B'' |
| Class B | Open | B905 | Nov 24, 2025 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT B905, 9th STORY, 5th APARTMENT FROM NORTH AT EAST , SECTION ''B'' |
| Class B | Open | B905 | Nov 24, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT B905, 9th STORY, 5th APARTMENT FROM NORTH AT EAST , SECTION ''B'' |
| Class B | OpenRENT IMPAIRING | D006 | Nov 18, 2025 | REPAIR FLUSHING APPARATUS OF WATER CLOSET · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET .. IN THE BATHROOM LOCATED AT APT D006, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | D314 | Nov 12, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT SOUTH WALL IN THE 1st BATHROOM FROM NORTH LOCATED AT APT D314 LOWER LEVEL, 3rd STORY, 6th APARTMENT FROM WEST AT NORTH , SECTION ''D'' ORIGINAL VIOLATION 18089923 ISSUED 09-JUL-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b). |
| Class B | Open | D314 | Nov 12, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT EAST WALL IN THE 1st BATHROOM FROM NORTH LOCATED AT APT D314 LOWER LEVEL, 3rd STORY, 6th APARTMENT FROM WEST AT NORTH , SECTION ''D'' ORIGINAL VIOLATION 18089931 ISSUED 09-JUL-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b). |
| Class B | Open | A318 | Nov 10, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER WINDOW SASH 1ST WINDOW AT WEST. IN THE 4th ROOM FROM EAST LOCATED AT APT A318, 3rd STORY, 18th APARTMENT FROM NORTH AT EAST |
| Class B | Open | A318 | Nov 10, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RUBBER GASKET SEAL AT LOWER REFRIGERATOR DOOR IN THE KITCHEN LOCATED AT APT A318, 3rd STORY, 18th APARTMENT FROM NORTH AT EAST |
| Class B | Open | D001 | Oct 10, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT D001, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | D006 | Sep 29, 2025 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS WASTELINE AT WASH BASIN IN THE BATHROOM LOCATED AT APT D006, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | B903 | Sep 23, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT B903, 9th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''WEST'' |
| Class B | Open | B903 | Sep 22, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE COUNTER BALANCE LOWER SASH AT WINDOW AT SOUTH WALL IN THE KITCHEN LOCATED AT APT B903, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Open | B903 | Sep 22, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WALL CABINET AT SOUTH WALL IN THE KITCHEN LOCATED AT APT B903, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Open | — | Sep 22, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 3rd STORY |
| Class B | Open | B903 | Sep 22, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE BASE CABINET AT SOUTH WALL DOOR IN THE KITCHEN LOCATED AT APT B903, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Open | B903 | Sep 18, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT WEST WALL OVER DOOR FRAME IN THE ENTRANCE LOCATED AT APT B903, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Open | B903 | Sep 18, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT B903, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Open | B903 | Sep 18, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT B903, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | OpenRENT IMPAIRING | D006 | Sep 2, 2025 | REPAIR FLUSHING APPARATUS OF WATER CLOSET · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET IN THE BATHROOM LOCATED AT BSMT-APT D006, 1st BSMT-APT FROM SOUTH AT WEST |
| Class B | Open | D006 | Sep 2, 2025 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE WASHBASIN TO THE NORTH WALL IN THE BATHROOM LOCATED AT BSMT-APT D006, 1st BSMT-APT FROM SOUTH AT WEST |
| Class B | Open | D006 | Aug 29, 2025 | REMOVE VERMIN · EXTERMINATION & RODENT ERADICATION566 (B) 27-2021.4 HMC: ABATE THE NUISANCE CONSISTING OF PESTS. EVIDENCE OF FLIES IN THE ENTIRE APARTMENT LOCATED AT APT D006, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | D006 | Aug 29, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE VENTILATION SYSTEM AT EAST WALL IN THE BATHROOM LOCATED AT APT D006, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | D001FL | Aug 25, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ.FT AT NORTH WALL IN THE KITCHEN LOCATED AT APT D001FL, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | D001FL | Aug 25, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AND NORTH WALL IN THE KITCHEN LOCATED AT APT D001FL, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | D001FL | Aug 25, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGHT FIXTURE AT NORTH WALL IN THE ENTRANCE LOCATED AT APT D001FL, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | D001FL | Aug 25, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE VENTILATION SYSTEM AT NORTH WALL IN THE KITCHEN LOCATED AT APT D001FL, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | D001FL | Aug 25, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING , NORTH AND WEST WALLS IN THE KITCHEN LOCATED AT APT D001FL, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | D302 | Aug 20, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING GREATER THAN 10SQ FT (20SQFT) IN THE BATHROOM LOCATED AT APT D302 UPPER LEVEL, 3rd STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | D310 | Aug 20, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING GREATER THAN 10SQ FT (20SQFT) IN THE 1st BATHROOM FROM NORTH LOCATED AT APT D310 LOWER LEVEL, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Open | D313 | Aug 20, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING GREATER THAN 10SQ FT (15SQFT) IN THE 1st BATHROOM FROM NORTH LOCATED AT APT D313 LOWER LEVEL, 3rd STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Open | D006 | Jul 31, 2025 | REMOVE VERMIN · EXTERMINATION & RODENT ERADICATION566 (B) 27-2021.4 HMC: ABATE THE NUISANCE CONSISTING OF PESTS. EVIDENCE OF FLIES IN THE ENTIRE APARTMENT LOCATED AT APT D006, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | D006 | Jul 31, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 1st ROOM FROM EAST LOCATED AT APT D006, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | D006 | Jul 31, 2025 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE WASH BASIN AT NORTH WALL IN THE BATHROOM LOCATED AT APT D006, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | — | Jul 31, 2025 | REMOVE VERMIN · EXTERMINATION & RODENT ERADICATION566 (B) 27-2021.4 HMC: ABATE THE NUISANCE CONSISTING OF PESTS. EVIDENCE OF FLIES , 1st STORY |
| Class B | Open | D006 | Jul 31, 2025 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB NORTH WALL IN THE BATHROOM LOCATED AT APT D006, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | D006 | Jul 25, 2025 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE WASH BASIN IN THE BATHROOM LOCATED AT BSMT-APT D006, 1st BSMT-APT FROM SOUTH AT WEST |
| Class B | Open | D006 | Jul 25, 2025 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL OUTLET COVERS IN THE BATHROOM LOCATED AT APT D006, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | D006 | Jul 25, 2025 | REMOVE VERMIN · EXTERMINATION & RODENT ERADICATION566 (B) 27-2021.4 HMC: ABATE THE NUISANCE CONSISTING OF PESTS. EVIDENCE OF FLIES IN THE ENTIRE APARTMENT LOCATED AT APT D006, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | — | Jul 14, 2025 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL SAFETY OUTLET COVER AT SOUTH WALL AT PUBLIC HALL, 9th STORY, SECTION ''D'' |
| Class B | Open | — | Jul 14, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 3rd STORY, SECTION ''D'' |
| Class B | Open | — | Jul 14, 2025 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL SAFETY OUTLET COVER AT SOUTH WALL AT BASEMENT STORY AT PUBLIC HALL, SECTION ''D'' |
| Class B | Open | — | Jul 14, 2025 | REMOVE VERMIN · EXTERMINATION & RODENT ERADICATION566 (B) 27-2021.4 HMC: ABATE THE NUISANCE CONSISTING OF PESTS. EVIDENCE OF FLIES AT BASEMENT STORY AT PUBLIC HALL, SECTION ''D'' |
| Class B | Open | — | Jul 14, 2025 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL SAFETY OUTLET COVERS AT SOUTH WALL AT BASEMENT STORY AT PUBLIC HALL, SECTION ''D'' |
| Class B | Open | — | Jul 14, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 3rd STORY, SECTION ''D'' |