| Class B | Closed | 1C | Nov 3, 2014 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICESSECTION 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 1C, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4H | Oct 6, 2014 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE MORTISE LOCK ON DOOR ( ADDRESS IS 334 BEACH 53RD STREET) IN THE ENTRANCE LOCATED AT APT 4H, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 4B | Sep 18, 2014 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 4B, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 4B | Sep 18, 2014 | REMOVE BARS OR GATES FROM FIRE ESCAPE WINDOW · EGRESS§ 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM WINDOW TO FIRE ESCAPE OR PROVIDE APPROVED TYPE GATE ,, LOCATED AT APT 4B, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 4B | Sep 18, 2014 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR WHICH IS MISSING LOCATED AT APT 4B, 2nd STORY, APARTMENT AT WEST , SECTION AT EAST |
| Class B | Closed | 4B | Sep 18, 2014 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). WHICH IS MISSING LOCATED AT APT 4B, 2nd STORY, APARTMENT AT WEST , SECTION AT EAST |
| Class B | ClosedRENT IMPAIRING | 4B | Sep 18, 2014 | REPAIR FLUSHING APPARATUS OF WATER CLOSET · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET , LOCATED AT APT 4B, 2nd STORY, APARTMENT AT WEST , SECTION AT EAST |
| Class B | Open | — | Sep 17, 2014 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE 7TH & 16 WOOD TREAD FROM BOTTOM STAIR AT PUBLIC HALL, 1st STORY |
| Class B | Open | — | Sep 17, 2014 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE FRONT YARD |
| Class B | Open | 3FL | Sep 17, 2014 | NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 3FL, 3rd STORY |
| Class B | Open | 3FL | Sep 17, 2014 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3FL, 3rd STORY |
| Class B | Open | 3FL | Sep 17, 2014 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE CRACKED GLASS AT LOWER & UPPER SASH WINDOW IN THE 1st ROOM FROM NORTH LOCATED AT APT 3FL, 3rd STORY |
| Class B | Open | 3FL | Sep 17, 2014 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ELECTRIC OUT LET AT EAST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 3FL, 3rd STORY |
| Class B | Open | 3FL | Sep 17, 2014 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FRAME AT DOOR IN THE 2nd ROOM FROM NORTH LOCATED AT APT 3FL, 3rd STORY |
| Class B | Open | 3FL | Sep 17, 2014 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WALLS & CEILING IN THE KITCHEN LOCATED AT APT 3FL, 3rd STORY |
| Class B | Open | 3FL | Sep 17, 2014 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE KITCHEN LOCATED AT APT 3FL, 3rd STORY |
| Class B | Open | 3FL | Sep 17, 2014 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD BASE CABINET AT SINK IN THE KITCHEN LOCATED AT APT 3FL, 3rd STORY |
| Class B | Open | 3FL | Sep 17, 2014 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION WASTE LINE UNDER SINK IN THE KITCHEN LOCATED AT APT 3FL, 3rd STORY |
| Class B | Open | 1 | Sep 3, 2014 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGESECTION 27-2026 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE CONNECTION WASTELINE AT SINK IN THE KITCHEN LOCATED AT APT 1, 1st STORY |
| Class B | Open | 1 | Sep 3, 2014 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGESECTION 27-2026 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE CONNECTION WASTELINE AT SINK IN THE KITCHEN LOCATED AT APT 1 |
| Class B | Closed | 2FL | Aug 29, 2014 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR EAST WALL IN THE 1st ROOM FROM EAST LOCATED AT APT 2FL, 2nd STORY |
| Class B | Closed | 2FL | Aug 29, 2014 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADMIN. CODE: REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS WASH BASIN IN THE BATHROOM LOCATED AT APT 2FL, 2nd STORY |
| Class B | Open | CELLAR | Jul 16, 2014 | DISCONTINUE ROOMS AT CELLAR · OCCUPANY OF BASEMENT AND CELLARSSECTION 27-2087 ADM CODE - DISCONTINUE USE OF ROOMS FOR LIVING, DISCONNECT PLUMBING FIXTURES WHERE ILLEGAL AND PROPERLY SEAL PIPE CONNECTIONS SHOWER STALL. WASHBASIN AND WATER CLOSET BOWL. IN THE ENTIRE APARTMENT LOCATED AT CELLAR APT CELLAR |
| Class B | Open | 1FL | Jul 11, 2014 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGESECTION 27-2026 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE CONNECTION SINK WASTE LINE IN THE KITCHEN LOCATED AT APT 1FL, 1st STORY |
| Class B | Open | 2 | Jul 11, 2014 | § 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE CAULKING AROUND TUB IN THE BATHROOM LOCATED AT APT 2, 2nd STORY§ 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE CAULKING AROUND TUB IN THE BATHROOM LOCATED AT APT 2, 2nd STORY |
| Class B | Open | 1FL | Jul 11, 2014 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLYSECTION 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE 3rd ROOM FROM EAST LOCATED AT APT 1FL, 1st STORY |
| Class B | Open | — | Jul 11, 2014 | REMOVE ACCUMULATION OR RUBBISH · CLEANINGSECTION 27-2010, 2011, 2012 ADMIN. CODE: REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE WEST YARD |
| Class B | Open | 2 | Jul 11, 2014 | REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRIC WIRE WEST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 2, 2nd STORY |
| Class B | Open | 2 | Jul 11, 2014 | REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRIC WIRE WEST WALL IN THE BATHROOM LOCATED AT APT 2, 2nd STORY |
| Class B | Open | 2 | Jul 11, 2014 | REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE§ 27-2026 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE CONNECTION SINK WASTE LINE IN THE KITCHEN LOCATED AT APT 2, 2nd STORY |
| Class B | Open | 1FL | Jul 11, 2014 | REPAIR PLASTER · MAINTENANCESECTION 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING IN THE 3rd ROOM FROM EAST LOCATED AT APT 1FL, 1st STORY |
| Class B | Open | 2 | Jul 11, 2014 | REPLACE · MAINTENANCE§ 27-2005 ADMIN. CODE: REPLACE WITH NEW THE MISSING ELECTRIC OUTLET COVERS THROUGHOUT IN THE ENTIRE APARTMENT LOCATED AT APT 2, 2nd STORY |
| Class B | Open | 1FL | Jul 11, 2014 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLYSECTION 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER IN THE 1st ROOM FROM EAST LOCATED AT APT 1FL, 1st STORY |
| Class B | Closed | 2F | Jun 26, 2014 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES ON WEST WALL IN THE BATHROOM LOCATED AT APT 2F, 2nd STORY, APARTMENT AT NORTH |
| Class B | Closed | 2F | Jun 26, 2014 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 2F, 2nd STORY, APARTMENT AT NORTH |
| Class B | Closed | 2F | Jun 26, 2014 | NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 2F, 2nd STORY, APARTMENT AT NORTH |
| Class B | Closed | — | Jun 26, 2014 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDING PLASTER SOUTH WALL AT PUBLIC HALL STAIRS, 2nd STORY |
| Class B | Closed | 2F | Jun 26, 2014 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 2F, 2nd STORY, APARTMENT AT NORTH |
| Class B | Closed | 2F | Jun 26, 2014 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 2F, 2nd STORY, APARTMENT AT NORTH |
| Class B | Closed | 2F | Jun 26, 2014 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 2F, 2nd STORY, APARTMENT AT NORTH |
| Class B | Closed | 2F | Jun 26, 2014 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2F, 2nd STORY, APARTMENT AT NORTH |
| Class B | Closed | 2F | Jun 26, 2014 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR UNDER RADIATOR IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2F, 2nd STORY, APARTMENT AT NORTH |
| Class B | Open | 1 | Jun 20, 2014 | REPAIR PLASTER · MAINTENANCESECTION 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING IN THE 4th ROOM FROM EAST LOCATED AT APT 1, 1st STORY |
| Class B | Open | 1 | Jun 20, 2014 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONSECTION 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY |
| Class B | Open | 1 | Jun 20, 2014 | NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICESSECTION 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY |
| Class B | Open | 1 | Jun 20, 2014 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONSECTION 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY |
| Class B | Closed | 30 | May 27, 2014 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND NORTH WALL IN THE BATHROOM LOCATED AT APT 30, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 30 | May 27, 2014 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING AND NORTH WALL IN THE BATHROOM LOCATED AT APT 30, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH |
| Class B | ClosedRENT IMPAIRING | 30 | May 27, 2014 | REPLACE DEFECTIVE SINK, WATER CLOSET, WASH TUB · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REPLACE THE BROKEN OR DEFECTIVE BATHTUB IN THE BATHROOM LOCATED AT APT 30, 3rd STORY, 5th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 30 | May 27, 2014 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CLOSET CEILING IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 30, 3rd STORY, 5th APARTMENT FROM WEST AT NORTH |