| Class C | Closed | — | Sep 13, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT COMPACTOR CLOSET, 5th STORY |
| Class B | Open | 1 | Sep 9, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 1 | Sep 9, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR THE CEILING IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 1 | Sep 9, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | 1 | Sep 9, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR THE CEILING IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Open | — | Sep 9, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MAILBOX AT BUILDING FRONT |
| Class C | Closed | 1 | Sep 9, 2024 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2073 ADM CODE - PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class C | Closed | 1 | Sep 9, 2024 | PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES . IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class A | Closed | — | Sep 5, 2024 | POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY |
| Class C | Closed | 415 | Sep 5, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOCK AND LATCH SET AT APARTMENT ENTRANCE DOOR IN THE ENTRANCE LOCATED AT APT 415, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | ClosedRENT IMPAIRING | — | Sep 5, 2024 | REMOVE ILLEGAL FASTENING · EGRESS§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF AN UNACCEPTABLE ELECTROMAGNETIC LOCKING DEVICE INSTALLED AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Sep 5, 2024 | PROVIDE · MAINTENANCE§ 27-2005 ADM CODE PROVIDE SECURITY IN THE EVENT OF A POWER OUTAGE BY MEANS OF AN ACCEPTABLE MECHANICAL HEAVY DUTY LOCK AND LATCH SET AT VESTIBULE DOOR AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Sep 3, 2024 | DISCONTINUE ROOMS AT CELLAR · OCCUPANY OF BASEMENT AND CELLARS§ 27-2087 ADM CODE - DISCONTINUE USE OF ROOMS FOR LIVING, DISCONNECT PLUMBING FIXTURES WHERE ILLEGAL AND PROPERLY SEAL PIPE CONNECTIONS SINK AT SOUTH AT CELLAR |
| Class B | Closed | — | Aug 29, 2024 | FILE PLANS & OBTAIN C/O TO LEGALIZE CONVERSION FROM PD TO MD · CONVERSIONS§ 9, 170, 171, 300, 301, 302 M.D.LAW-FILE PLANS AND APPLICATION AND OBTAIN A CERTIFICATE OF OCCUPANCY TO LEGALIZE THE CONVERSION FROM A PRIVATE DWELLING TO MULTIPLE DWELLING USE IF LAWFULLY FEASIBLE OR RESTORE TO LAWFUL OCCUPANCY |
| Class A | Closed | — | Aug 22, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT NORTH WALL HALLWAY LABELED STAIR A NEAR ELEVATOR, AT PUBLIC HALL, 1st STORY, SECTION ''A'' |
| Class C | Closed | — | Aug 21, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AND DOOR COMPACTOR CLOSET DOOR AT PUBLIC HALL, 6th STORY |
| Class B | Closed | 6B | Aug 21, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING INSIDE CLOSET IN THE PRIVATE HALLWAY LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | 6B | Aug 21, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK CEILING INSIDE CLOSET IN THE PRIVATE HALLWAY LOCATED AT APT 6B, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Open | — | Aug 21, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL CEILING COMPACTOR CLOSET AT PUBLIC HALL, 6th STORY |
| Class A | Closed | — | Aug 21, 2024 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CEILING COMPACTOR CLOSET AT PUBLIC HALL, 6th STORY |
| Class B | Closed | 410 | Aug 20, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING. IN THE KITCHEN LOCATED AT APT 410, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 410 | Aug 20, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING. IN THE BATHROOM LOCATED AT APT 410, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 410 | Aug 20, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING. IN THE BATHROOM LOCATED AT APT 410, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | — | Aug 20, 2024 | IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 603 | Aug 20, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK SOUTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 603, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 603 | Aug 20, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR SOUTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 603, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 410 | Aug 20, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING. IN THE KITCHEN LOCATED AT APT 410, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class A | Closed | 110 | Aug 19, 2024 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT 110, 1st STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class A | Closed | — | Aug 9, 2024 | POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. |
| Class A | Closed | — | Aug 9, 2024 | POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Aug 9, 2024 | POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Aug 9, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT BUILDING ENTRANCE DOOR AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Aug 9, 2024 | POST GAS LEAK NOTICE · POSTING/SIGNAGE§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY |
| Class A | Closed | — | Aug 9, 2024 | POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX AT PUBLIC HALL, 1st STORY |
| Class C | Closed | — | Aug 9, 2024 | POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM AT PUBLIC HALL, 1st STORY |
| Class B | ClosedRENT IMPAIRING | 6B | Aug 8, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING, CLOSET IN THE PRIVATE HALLWAY LOCATED AT APT 6B, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Aug 8, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER, CEILING AT COMPACTOR CLOSET, 4th STORY |
| Class B | ClosedRENT IMPAIRING | 6B | Aug 8, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 6B, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class B | ClosedRENT IMPAIRING | — | Aug 8, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER SKYLIGHT AT PUBLIC HALL, 4th STORY |
| Class B | Closed | 6B | Aug 8, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 6B, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST |
| Class A | Closed | — | Aug 8, 2024 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT EAST WALL AT PUBLIC HALL, 4th STORY |
| Class C | Closed | — | Aug 8, 2024 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR AND FRAME, AT COMPACTOR CLOSET, 4th STORY |
| Class C | Closed | 1R | Aug 2, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR AT CEILING IN THE KITCHEN LOCATED AT APT 1R, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1R | Aug 2, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1R, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1R | Aug 2, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE UPPER WOOD CABINETS MOUNTED AT NORTH WALL IN THE KITCHEN LOCATED AT APT 1R, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 1R | Aug 2, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADMIN. CODE: REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE KITCHEN LOCATED AT APT 1R, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1R | Aug 2, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR AT ALL WALLS IN THE KITCHEN LOCATED AT APT 1R, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 1R | Jul 31, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADMIN. CODE: REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 1R, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Closed | 1R | Jul 31, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR AT CEILING IN THE KITCHEN LOCATED AT APT 1R, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class A | Closed | — | Jul 25, 2024 | POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX SIGN MISSING ON WALL AT PUBLIC HALL, 1st STORY |