| Class C | OpenRENT IMPAIRING | 2A | May 5, 2026 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE IN THE KITCHEN LOCATED AT APT 2A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | Open | 2A | May 5, 2026 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF SCALDING WATER ABOVE 130 DEGREES IN THE ENTIRE APARTMENT LOCATED AT APT 2A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | OpenRENT IMPAIRING | 2C | Apr 17, 2026 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE |
| Class C | Open | — | Apr 17, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE UPPER WINDOW SASH COUNTERBALANCE AT NORTH WINDOW. AT PUBLIC HALL STAIRS |
| Class C | OpenRENT IMPAIRING | 3D | Apr 8, 2026 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE IN THE KITCHEN LOCATED AT APT 3D, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 3D | Apr 8, 2026 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 3D | Apr 8, 2026 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | Open | 3D | Apr 8, 2026 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 3D, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | OpenRENT IMPAIRING | 2F | Apr 6, 2026 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE IN THE KITCHEN LOCATED AT APT 2F, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class C | OpenRENT IMPAIRING | 2F | Apr 6, 2026 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT RANGE IN THE KITCHEN LOCATED AT APT 2F, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 1G | Feb 12, 2026 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 1O SQ FT AT CEILING IN THE 4th ROOM FROM NORTH LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST ORIGINAL VIOLATION 18297972 ISSUED 14-OCT-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b). |
| Class C | OpenRENT IMPAIRING | 2A | Nov 3, 2025 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES NO GAS AT RANGE IN THE KITCHEN LOCATED AT APT 2A, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class C | OpenRENT IMPAIRING | 4A | Oct 22, 2025 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES GAS RANGE IN THE KITCHEN LOCATED AT APT 4A, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 2F | Oct 20, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE MARBLE SADDLE IN THE ENTRANCE LOCATED AT APT 2F, 2nd STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class C | Open | 2F | Oct 20, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 2F, 2nd STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 2F | Oct 20, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2F, 2nd STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 2F | Oct 20, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2F, 2nd STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class C | OpenRENT IMPAIRING | 2F | Oct 20, 2025 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES RANGE IN THE KITCHEN LOCATED AT APT 2F, 2nd STORY, 3rd APARTMENT FROM SOUTH AT WEST |
| Class A | Open | 1G | Oct 15, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | OpenRENT IMPAIRING | 3A | Oct 15, 2025 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT GAS RANGE IN THE KITCHEN LOCATED AT APT 3A, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Class B | Open | 1G | Oct 15, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 4th ROOM FROM NORTH LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1G | Oct 15, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 4th ROOM FROM NORTH LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1G | Oct 15, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT NORTH WALL IN THE FOYER LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | OpenRENT IMPAIRING | 1G | Oct 15, 2025 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES AT GAS RANGE IN THE KITCHEN LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | OpenRENT IMPAIRING | 5B | Oct 14, 2025 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES RANGE IN THE KITCHEN LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | OpenRENT IMPAIRING | 2D | Oct 14, 2025 | INADEQUATE HOT WATER SUPPLY (VOLUME) · WATER SUPPLY§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES , IN THE ENTIRE APARTMENT LOCATED AT APT 2D, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | OpenRENT IMPAIRING | 2D | Oct 14, 2025 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES RANGE IN THE KITCHEN LOCATED AT APT 2D, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | Open | 1G | Oct 14, 2025 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF AIR CONDITION UNIT INSTALLED ON WINDOW TO FIRE ESCAPE IN THE 1st ROOM FROM NORTH LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1G | Oct 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH ASSEMBLY ON DOOR IN THE ENTRANCE LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | OpenRENT IMPAIRING | 2D | Oct 14, 2025 | INADEQUATE COLD WATER · WATER SUPPLY§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF COLD WATER FOR THE FIXTURES , IN THE ENTIRE APARTMENT LOCATED AT APT 2D, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | Open | 1G | Oct 14, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH IN THE ENTRANCE LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1G | Oct 14, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 1G | Oct 14, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 2D | Oct 14, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2D, 2nd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class C | OpenRENT IMPAIRING | 1G | Oct 14, 2025 | NO GAS · KITCHEN AND KITCHENETTES§ 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES RANGE IN THE KITCHEN LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | OpenRENT IMPAIRING | — | Jul 24, 2025 | F/E ADJUST THE DROP LADDER · EGRESS§ 27-2005 ADM CODE FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS SOUTH STACK BUILDING FRONT AT FIRE ESCAPE |
| Class C | OpenRENT IMPAIRING | — | Jul 24, 2025 | REMOVE ILLEGAL FASTENING · EGRESS§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING SLIDE BOLT INSTALLED ON NORTH WALL BULKHEAD DOOR TO ROOF CAPABLE OF BEING PADLOCKED AT PUBLIC HALL, 5th STORY |
| Class C | OpenRENT IMPAIRING | — | Jul 24, 2025 | REMOVE ILLEGAL FASTENING · EGRESS§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING SLIDE BOLT INSTALLED ON SOUTH WALL BULKHEAD DOOR TO ROOF CAPABLE OF BEING PADLOCKED AT PUBLIC HALL, 5th STORY |
| Class C | Open | — | Jul 24, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES ON SOUTH WALL BULKHEAD DOOR TO ROOF AT PUBLIC HALL, 5th STORY |
| Class C | OpenRENT IMPAIRING | — | Jul 24, 2025 | F/E ADJUST THE DROP LADDER · EGRESS§ 27-2005 ADM CODE FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS NORTH STACK BUILDING FRONT AT FIRE ESCAPE |
| Class C | Open | — | Jul 24, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES ON NORTH WALL DOOR THAT LEADS TO BOILER ROOM AREA AT CELLAR |
| Class C | Open | 1G | Sep 20, 2021 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Open | 1G | Sep 20, 2021 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | 5A | Oct 2, 1990 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE FRONT ENTRANCE DOOR TO 5 STY APT 5A. , SECTION '' '' |
| Class B | Open | 5A | Oct 2, 1990 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE BELL SYSTEM AT FRONT ENTRANCE TO 5 STY APT 5A. , SECTION '' '' |
| Class B | Open | 5A | Oct 2, 1990 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING KITCHEN SINK CABINET AT KITCHEN 5 STY APT 5A. , SECTION '' '' |
| Class B | Open | 5A | Oct 2, 1990 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE KNOBS ON GAS BURNER AT KITCHEN 5 STY APT 5A. , SECTION '' '' |