| Class B | Open | 4F | Sep 15, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Open | 4F | Sep 15, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Open | 4F | Sep 15, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Open | 4F | Sep 15, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE AT NORTH WALL IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 4K | Sep 15, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 4K, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 4K | Sep 15, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4K, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1H | Sep 15, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQUARE FEET AT CEILING, EAST WALL, AND SOUTH WALL IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT WEST |
| Class B | Closed | — | Sep 15, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE 1ST OUTER COURT FROM EAST AT SOUTH (BUILDING FRONT). |
| Class B | Closed | — | Sep 15, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING, NORTH WALL, AND WEST WALL AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Sep 15, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | 1H | Sep 15, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING, EAST WALL, AND SOUTH WALL IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT WEST |
| Class B | Closed | 1H | Sep 15, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT WEST |
| Class B | Closed | — | Sep 15, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT EAST WALL AT PUBLIC HALL, 1st STORY, SECTION AT NORTH |
| Class B | Closed | — | Sep 15, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCHSET AT DOOR LEADING TO STAIRCASE AT PUBLIC HALL STAIRS, 4th STORY, SECTION AT NORTH |
| Class B | Open | 4F | Sep 15, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL BUZZER RETURN SYSTEM PANEL AT NORTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST |
| Class B | Closed | — | Sep 15, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT DOOR AT COMPACTOR CLOSET DOOR , 1st STORY |
| Class B | Closed | — | Sep 12, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Sep 10, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING, NORTH AND WEST WALL , 1st STORY |
| Class B | Closed | — | Sep 10, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING, NORTH AND WEST WALL , 1st STORY |
| Class B | Closed | — | Sep 3, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AT PUBLIC HALL, 1st STORY |
| Class B | Open | 3K | Aug 11, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE PRIVATE HALLWAY LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3K | Aug 11, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ.FT AT EAST, SOUTH AND WEST WALLS AND CEILING IN THE BATHROOM LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3K | Aug 11, 2025 | SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE WALL CABINET AT NORTH WALL IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | ClosedRENT IMPAIRING | — | Aug 11, 2025 | F/E ADJUST THE DROP LADDER · EGRESS§ 27-2005 ADM CODE FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS OFF GRAVITY HOOK AT 2ND FROM WEST AT NORTH, BUILDING FRONT AT FIRE ESCAPE |
| Class B | Closed | 3K | Aug 11, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 2N | Aug 5, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT EAST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 2N, 2nd STORY, 4th APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 17810107 ISSUED 05-APR-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Open | — | Aug 5, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT THE WOODEN FLOOR AT CELLAR AT LAUNDRY ROOM ORIGINAL VIOLATION 17810115 ISSUED 05-APR-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Open | 5S | Aug 5, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 5S, 5th STORY, 1st APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 17810117 ISSUED 05-APR-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Open | 5J | Aug 5, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT CEILING IN THE BATHROOM LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 17810112 ISSUED 05-APR-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Open | 3K | Jul 25, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''EAST'' |
| Class B | Open | 3K | Jul 25, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE EAST WALL, SOUTH WALL, WEST WALL, CEILING IN THE BATHROOM LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''EAST'' |
| Class B | Closed | 3K | Jul 25, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''EAST'' |
| Class B | Closed | 3K | Jul 25, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''EAST'' |
| Class B | Open | 3K | Jul 25, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BASE CABINET AT WASHBASIN IN THE BATHROOM LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''EAST'' |
| Class B | Closed | 2N | Jun 27, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ. FT AT CEILING AND EAST WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 2N, 2nd STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT EAST |
| Class B | Closed | — | Jun 10, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND EAST WALLS ( NEAR RADIATOR ) AT PUBLIC HALL, 1st STORY |
| Class B | Open | 5S | Jun 9, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET AT WEST WALL IN THE BATHROOM LOCATED AT APT 5S, 5th STORY, 1st APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 17664963 ISSUED 31-JAN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 3A | Jun 6, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3A | Jun 6, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 5J | May 27, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET AT CEILING AND NORTH WALL IN THE BATHROOM LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH ORIGINAL VIOLATION 17650332 ISSUED 26-JAN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Open | 5S | May 27, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET AT SOUTH WALL AND CEILING IN THE BATHROOM LOCATED AT APT 5S, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT EAST ORIGINAL VIOLATION 17649872 ISSUED 25-JAN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | — | Apr 7, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOODEN FLOOR AT CELLAR AT LAUNDRY ROOM |
| Class B | Closed | 5J | Apr 7, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 2N | Apr 7, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT EAST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 2N, 2nd STORY, 4th APARTMENT FROM WEST AT NORTH |
| Class B | Open | 3K | Apr 7, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL FLOOR TILES IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5J | Apr 7, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT WEST WALL IN THE BATHROOM LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 2P | Mar 5, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 2P, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH , SECTION ''K-T'', AT EAST |
| Class B | Open | 2P | Mar 5, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 2P, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH , SECTION ''K-T'', AT EAST |
| Class B | Closed | 4T | Feb 24, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4T, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''K-T'' |
| Class B | Closed | 4T | Feb 24, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4T, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''K-T'' |