| Class B | Open | 3U | Feb 20, 2026 | REMOVE BARS OR GATES FROM FIRE ESCAPE WINDOW · EGRESS§ 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM WINDOW TO FIRE ESCAPE OR PROVIDE APPROVED TYPE GATE IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 3U, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''M-L'', AT WEST |
| Class B | Open | 3U | Feb 20, 2026 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3U, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''M-L'', AT WEST |
| Class B | Open | 3U | Feb 20, 2026 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3U, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''M-L'', AT WEST |
| Class B | Open | — | Jan 13, 2026 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT FIRE DOOR AT NORTH WALL LEADING TO STAIR A AT PUBLIC HALL, 3rd STORY, SECTION AT WEST |
| Class B | Open | — | Apr 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH ASSEMBLY ON COMPACTOR CLOSET DOOR AT PUBLIC HALL, 6th STORY, SECTION ''M-Y'', AT WEST |
| Class B | Open | 4B | Apr 4, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4B, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT EAST |
| Class B | Open | 4B | Apr 4, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4B, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT EAST |
| Class B | Closed | — | Mar 14, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT COMPACTOR DOOR , BASEMENT STORY |
| Class B | Closed | — | Feb 5, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT DOOR AT COMPACTOR CLOSET, 1st STORY, SECTION AT EAST |
| Class B | Closed | — | Nov 12, 2024 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES FLOWER POTS AT 5TH STORY BALCONY AT WEST 2 STACK AT BUILDING FRONT AT FIRE ESCAPE |
| Class B | Closed | — | Nov 7, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH ASSEMBLY ON COMPACTOR CLOSET DOOR PUBLIC HALL AT CELLAR, 1st STORY, SECTION ''A-L'', AT EAST |
| Class B | Closed | — | Aug 29, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING BY ELEVATOR AT PUBLIC HALL, 6th STORY ORIGINAL VIOLATION 16937906 ISSUED 26-APR-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 5N | Aug 19, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROXIMATELY 5 SQ FT OF MOLD AT NORTH WALL IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 5N, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT SOUTH ORIGINAL VIOLATION 16901764 ISSUED 18-APR-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Closed | 5N | Aug 19, 2024 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROXIMATELY 3 SQ FT OF MOLD AT NORTH WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 5N, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT SOUTH ORIGINAL VIOLATION 16901766 ISSUED 18-APR-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | ClosedRENT IMPAIRING | — | May 1, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING BY ELEVATOR AT PUBLIC HALL, 6th STORY |
| Class B | Closed | — | May 1, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING BY ELEVATOR AT PUBLIC HALL, 6th STORY |
| Class B | ClosedRENT IMPAIRING | — | Apr 30, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL, 6th STORY |
| Class B | Closed | — | Apr 30, 2024 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES CONSISTING OF FLOWER POTS AT 5TH STORY BALCONY CENTER STACK AT BUILDING FRONT AT FIRE ESCAPE |
| Class B | Closed | — | Apr 29, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 6th STORY, SECTION AT EAST |
| Class B | ClosedRENT IMPAIRING | — | Apr 29, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AND NORTH WALL AT FIRE STAIRS, LABELED 'B' AT PUBLIC HALL, 6th STORY, SECTION AT EAST |
| Class B | Closed | — | Apr 29, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT NORTH AND EAST WALL AT FIRE STAIRS, LABELED 'B' AT PUBLIC HALL, 6th STORY, SECTION AT EAST |
| Class B | ClosedRENT IMPAIRING | — | Apr 29, 2024 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL, 6th STORY, SECTION AT EAST |
| Class B | Closed | — | Apr 4, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH ASSEMBLY AT COMPACTOR CLOSET DOOR EAST SECTION A-L AT PUBLIC HALL, 1st STORY |
| Class B | Closed | — | Mar 15, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE DOOR LATCH ASSEMBLY AT COMPACTOR CLOSET, 6th STORY, SECTION ''EAST'' |
| Class B | Closed | — | Mar 11, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AT PUBLIC HALL, 6th STORY, SECTION AT EAST |
| Class B | Closed | 3H | Sep 20, 2022 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE SECURITY DOOR IN THE ENTRANCE LOCATED AT APT 3H, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 3R | Feb 6, 2018 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE ... IN THE ENTRANCE LOCATED AT APT 3R, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3R | Feb 6, 2018 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). INOPERATIVE LOCATED AT APT 3R, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3R | Feb 6, 2018 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPERATIVE LOCATED AT APT 3R, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1B | Aug 21, 2017 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE TO THE APT IN THE ENTRANCE LOCATED AT APT 1B, 1st STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1B | Jun 13, 2017 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1B, 1st STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1B | Jun 13, 2017 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1B, 1st STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2U | Dec 18, 2014 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT 2U, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2U | Dec 18, 2014 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 2U, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2U | Dec 18, 2014 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE LOCATED AT APT 2U, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 2U | Dec 18, 2014 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES LOCATED AT APT 2U, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6B | Sep 27, 2011 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND WALLS IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT APT 6B, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 6B | Sep 27, 2011 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND EAST WALL IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 6B, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 6B | Jan 20, 2010 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE - IN THE ENTRANCE LOCATED AT APT 6B, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 6B | Jan 20, 2010 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st LIVING ROOM FROM EAST AT SOUTH LOCATED AT APT 6B, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | ClosedRENT IMPAIRING | 6B | Jan 20, 2010 | LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE 2nd BEDROOM FROM EAST AT SOUTH LOCATED AT APT 6B, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 3R | Dec 1, 2009 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 3R, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3R | Dec 1, 2009 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR (MISSING) IN THE ENTIRE APARTMENT LOCATED AT APT 3R, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3R | Dec 1, 2009 | NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE PRIVATE HALLWAY LOCATED AT APT 3R, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 3R | Dec 1, 2009 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 3R, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 6U | Aug 6, 2008 | ABATE THE NUISANCE · MAINTENANCE§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF CONCEALED WATER LEAK AT CEILING AND WEST WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 6U, 6th STORY |
| Class B | Closed | 6U | Aug 6, 2008 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND WEST WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 6U, 6th STORY |
| Class B | Closed | 6U | Aug 6, 2008 | RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE UPPER AND LOWER SASH WINDOW IN THE BATHROOM LOCATED AT APT 6U, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1H | Apr 9, 2008 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WALLS AND CEILING IN THE BATHROOM LOCATED AT APT 1H, 1st STORY, 6th APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1B | Sep 18, 2007 | REPAIR · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE INOPERATIVE MECHANICAL VENTILATION IN THE BATHROOM LOCATED AT APT 1B, 1st STORY, 5th APARTMENT FROM EAST AT SOUTH |