| Class B | Closed | 9G | Dec 29, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 9G, 9th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 11T | Dec 29, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AND EAST WALL IN THE BATHROOM LOCATED AT APT 11T, 11th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 9G | Dec 29, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 9G, 9th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 11T | Dec 29, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING IN THE BATHROOM LOCATED AT APT 11T, 11th STORY, 2nd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 14F | Dec 26, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 14F, 13th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 9A | Dec 26, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE DOOR LOCK AT ENTRANCE DOOR IN THE FOYER LOCATED AT APT 9A, 9th STORY, 4th APARTMENT FROM NORTH AT EAST |
| Class B | Closed | 12U | Dec 26, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 12U, 12th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 14F | Dec 26, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 14F, 13th STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 12U | Dec 26, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 12U, 12th STORY, 3rd APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 16F | Dec 22, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT SOUTH WALL. IN THE BATHROOM LOCATED AT APT 16F, 15th STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 1D | Oct 24, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MECHANICAL VENTILATION SYSTEM AT CEILING IN THE KITCHEN LOCATED AT APT 1D, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1C | Oct 24, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1C, 1st STORY, 6th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 1C | Oct 24, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1C, 1st STORY, 6th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 10T | Oct 20, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQFT AT CEILING IN THE BATHROOM LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 18051069 ISSUED 18-JUN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b). |
| Class B | Closed | 5L | Oct 17, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE VENTILATION SYSTEM AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 5L, 5th STORY, 6th APARTMENT FROM WEST AT NORTH |
| Class B | Open | 5T | Oct 16, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BROKEN GLASS AT 2ND WINDOW LOWER SASH FROM EAST AT SOUTH IN THE 3rd ROOM FROM EAST LOCATED AT APT 5T, 5th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5T | Oct 16, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR PANEL AT FLOOR CABINET AT SINK IN THE KITCHEN LOCATED AT APT 5T, 5th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 5T | Oct 16, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE 2ND CABINET DOOR AT FLOOR CABINET AT SINK IN THE KITCHEN LOCATED AT APT 5T, 5th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 5T | Oct 16, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5T, 5th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 5T | Oct 16, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5T, 5th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 2F | Aug 18, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT THE CEILING IN THE BATHROOM LOCATED AT APT 2F, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | 2F | Aug 18, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 2F, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Class B | Closed | — | Jul 21, 2025 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 2nd STORY |
| Class B | Open | 1B | Jul 8, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQFT AT NORTH WALL, EAST WALL, SOUTH WALL IN THE BATHROOM LOCATED AT APT 1B, 1st STORY, 5th APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 17745540 ISSUED 05-MAR-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Class B | Open | 10T | Jun 27, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE RUBBER GASKET ON REFRIGERATR DOOR IN THE KITCHEN LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 10T | Jun 27, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 10T | Jun 27, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 10T | Jun 20, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MORTISE LOCK AT DOOR IN THE ENTRANCE LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 10T | Jun 20, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 10T | Jun 20, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 10T | May 12, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 10T | May 12, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 10T | May 12, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 10T, 10th STORY, 2nd APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | 1B | Mar 10, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10SQFT AT CEILING, WEST WALL IN THE BATHROOM LOCATED AT APT 1B, 1st STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | — | Feb 26, 2025 | REFIT DOORS ETC. · EGRESS§ 27-2005 HMC: REFIT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 5th STORY |
| Class B | Closed | — | Dec 4, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AT VESTIBULE DOOR TO PUBLIC HALL , 1st STORY |
| Class B | Open | 12V | Nov 25, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND SOUTH WALL IN THE BATHROOM LOCATED AT APT 12V, 12th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 12V | Nov 25, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE RUBBER GASKET AT REFRIGERATOR IN THE KITCHEN LOCATED AT APT 12V, 12th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 12V | Nov 25, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 12V, 12th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 12V | Nov 25, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 2nd ROOM FROM EAST LOCATED AT APT 12V, 12th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5A | Nov 25, 2024 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE BATHROOM LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''A-H'', AT WEST |
| Class B | Open | 12V | Nov 25, 2024 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 12V, 12th STORY, 4th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5A | Nov 15, 2024 | ABATE THE NUISANCE OF BEDBUGS · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF BEDBUGS IN THE ENTIRE APARTMENT LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT EAST |
| Class B | Closed | 7H | Nov 7, 2024 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7H, 7th STORY |
| Class B | Closed | 7H | Nov 7, 2024 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7H, 7th STORY |
| Class B | Closed | 5A | Sep 5, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MECHANICAL VENTILATION SYSTEM AT WEST WALL IN THE KITCHEN LOCATED AT APT 5A, 5th STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Open | 5A | Sep 5, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MECHANICAL VENTILATION SYSTEM AT EAST WALL IN THE BATHROOM LOCATED AT APT 5A, 5th STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5A | Sep 3, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL FLOOR TILES IN THE KITCHEN LOCATED AT APT 5A, 5th STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5A | Sep 3, 2024 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RUBBER GASKET TOP AND BOTTOM DOOR IN THE KITCHEN LOCATED AT APT 5A, 5th STORY, 5th APARTMENT FROM EAST AT SOUTH |
| Class B | Closed | 5A | Sep 3, 2024 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE FOYER LOCATED AT APT 5A, 5th STORY, 5th APARTMENT FROM EAST AT SOUTH |