| Class B | Closed | G31 | Oct 8, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT G31, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''G'' |
| Class A | Closed | G31 | Oct 8, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE BATHROOM LOCATED AT APT G31, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''G'' |
| Class B | Closed | G31 | Oct 8, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT G31, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''G'' |
| Class C | Closed | G31 | Oct 8, 2025 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT G31, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''G'' |
| Class C | Open | — | Oct 8, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MORTISE LOCK AT BUILDING ENTRANCE DOOR , 1st STORY, SECTION ''G'' |
| Class B | Closed | G31 | Oct 8, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOM FROM BUILDING ENTRANCE TO NORTH WALL IN THE FOYER LOCATED AT APT G31, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''G'' |
| Class C | Closed | — | Oct 8, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE MASONRY TREAD AT 4TH TREAD FROM BOTTOM AT PUBLIC HALL STAIRS, 4th STORY, SECTION ''J'' |
| Class C | Open | G31 | Oct 8, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT G31, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''G'' |
| Class A | Closed | J22 | Oct 6, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT THE SOUTH WALL IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT J22, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | J22 | Oct 6, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT J22, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Open | J22 | Oct 6, 2025 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT J22, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class A | Closed | J22 | Oct 6, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT THE CEILING IN THE BATHROOM LOCATED AT APT J22, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class A | Open | J22 | Oct 6, 2025 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE KITCHEN , THE 3rd ROOM FROM NORTH AT WEST, THE BATHROOM , THE FOYER LOCATED AT APT J22, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | J22 | Oct 6, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT J22, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | J22 | Oct 6, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT J22, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Open | J22 | Oct 6, 2025 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT J22, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Open | G12 | Sep 29, 2025 | ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT G12, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | G12 | Sep 29, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT G12, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Open | G12 | Sep 29, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR IN THE ENTRANCE LOCATED AT APT G12, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | G12 | Sep 29, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT G12, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Open | G12 | Sep 29, 2025 | ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATIONHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT G12, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | G12 | Sep 29, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING IN THE BATHROOM LOCATED AT APT G12, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class A | Closed | G12 | Sep 29, 2025 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE BATHROOM LOCATED AT APT G12, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Closed | G12 | Sep 29, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT THE CEILING IN THE BATHROOM LOCATED AT APT G12, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | G12 | Sep 29, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREAT THEN 10SQ FEET AT THE CEILING AND ALL WALLS CEILING IN THE BATHROOM LOCATED AT APT G12, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | H11 | Sep 23, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOM SYSTEM FROM BUILDING ENTRANCE TO EAST WALL IN THE FOYER LOCATED AT APT H11, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | H11 | Sep 23, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK WEST WALL IN THE KITCHEN LOCATED AT APT H11, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | H11 | Sep 23, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT H11, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Open | H11 | Sep 23, 2025 | MAKE DOORS SELF-CLOSING · EGRESS§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR IN THE ENTRANCE LOCATED AT APT H11, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | H11 | Sep 23, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND WEST WALL IN THE BATHROOM LOCATED AT APT H11, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class A | Closed | H11 | Sep 23, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET AT CEILING AND EAST WALL IN THE BATHROOM LOCATED AT APT H11, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class C | Open | H11 | Sep 23, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING AND EAST WALL IN THE BATHROOM LOCATED AT APT H11, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | H11 | Sep 23, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WEST WALL IN THE KITCHEN LOCATED AT APT H11, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | H11 | Sep 23, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT H11, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH |
| Class B | Open | H13 | Sep 15, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT H13, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class B | Open | H13 | Sep 15, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT H13, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class A | Closed | H13 | Sep 15, 2025 | RESET WATER CLOSET BOWL · SEWERS AND DRAINAGE§ 27-2026 ADM CODE RESET, SO AS TO SECURE A PROPER AND TIGHT CONNECTION, THE WATER CLOSET BOWL BUZZER INTERCOM FROM THE BUILDING ENTRANCE TO RETURN BUZZER AT SOUTH WALL IN THE FOYER LOCATED AT APT H13, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST |
| Class C | Open | G52 | Aug 25, 2025 | INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1, WG TO REPLACE = 0, WG TO REPAIR = 1 IN THE ENTIRE APARTMENT LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class C | Open | G52 | Aug 25, 2025 | LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st CLOSET FROM NORTH AT EAST WALL DOOR FRAME, 1st DOOR FRAME FROM EAST AT SOUTH WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class C | Open | G52 | Aug 25, 2025 | LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM NORTH AT EAST WALL, 1st WINDOW FRAME FROM SOUTH AT WEST WALL IN THE KITCHEN LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class C | Open | G52 | Aug 25, 2025 | CORRECT THE LEAD-BASED PAINT TESTED INCONCLUSIVE OR POSTIVE FOR METAL/CERAMIC SUBSTRATE · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS XRF TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 AND IS PRESUMED LEAD PAINT AS SET FORTH IN (28 RCNY §11-07(b)) AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE-USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2) 1st DOOR FRAME FROM NORTH AT EAST WALL IN THE FOYER LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Open | G52 | Aug 25, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOWER SASH SPRING BALANCE AT 1ST WINDOW FROM WEST AT NORTH WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class C | Open | G52 | Aug 25, 2025 | LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st CLOSET FROM EAST AT SOUTH WALL DOOR FRAME, 1st DOOR FRAME FROM SOUTH AT WEST WALL, 1st WINDOW FRAME FROM WEST AT NORTH WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class C | Open | G52 | Aug 25, 2025 | LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM EAST AT SOUTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class C | Open | G52 | Aug 25, 2025 | LEAD-BASED PAINT HAZARD - DURING UNIT VACANCY · LEAD-BASED PAINT§ 27-2056.7, 27-2056.8, 27-2056.9 ADM CODE -CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY PERFORMING ACTIVITIES NECESSARY TO ABATE TESTED LEAD-BASED PAINT FROM REQUIRED WINDOW AND/OR DOOR FRICTION SURFACES FOR APARTMENT AND MAKE FLOORS SMOOTH AND CLEANABLE, POSITIVE LEAD-BASED PAINT IN AN APARTMENT WITH A CHILD UNDER SIX LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class A | Open | G52 | Aug 25, 2025 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT NORTH WALL, 1st CLOSET FROM NORTH AT EAST WALL DOOR, SOUTH WALL, WEST WALL, 1st WINDOW FRAME FROM SOUTH AT WEST WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class A | Open | G52 | Aug 25, 2025 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT 1st DOOR FROM NORTH AT EAST WALL, 1st CLOSET FROM EAST AT SOUTH WALL DOOR, 2nd CLOSET FROM EAST AT SOUTH WALL DOOR IN THE FOYER LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class C | Open | G52 | Aug 25, 2025 | LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM NORTH AT EAST WALL, 1st WINDOW FRAME FROM SOUTH AT WEST WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class A | Open | G52 | Aug 25, 2025 | PAINT METAL · PAINTING§ 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION AT 1st RISER FROM SOUTH AT WEST WALL IN THE KITCHEN LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class A | Open | G52 | Aug 25, 2025 | PAINT · PAINTING§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE BATHROOM LOCATED AT APT G52, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |