| Class B | Open | — | Dec 29, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CONCRETE FLOOR AT ''STAIRWELL C'' AT PUBLIC HALL STAIRS, 4th STORY, SECTION ''SOUTH '' |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | OpenRENT IMPAIRING | — | Dec 29, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT PUBLIC HALL, 6th STORY, SECTION ''SOUTH'' |
| Class B | Closed | — | Dec 29, 2025 | PROVIDE LIGHT - Not Less that 60 Watt incadescent · ARTIFICIAL LIGHTING§ 27-2039 ADM CODE PROVIDE ADEQUATE LIGHT OF NOT LESS THAN 60 WATTS INCANDESCENT OR EQUIVALENT ILLUMINATION AT CEILING AT PUBLIC HALL, 2nd STORY, SECTION ''SOUTH '' |
| Class B | Closed | 3E | Dec 29, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT DOOR IN THE ENTRANCE LOCATED AT APT 3E, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Open | 6J | Dec 29, 2025 | ADJUST DOOR TO PREVENT GAP - FIRE CODE/EGRESS · EGRESS28 RCNY § 25-171; & 67 (7)(B) MDL; NYC FIRE CODE § 703.1.3; NYC FIRE CODE § 703.2: ADJUST DOOR TO PREVENT GAPS BETWEEN THE TOP AND SIDE EDGES OF DOOR AND DOOR JAMB EXCEEDING THE MAXIMUM ALLOWABLE CLEARANCE OF 1/8 OF AN INCH AND MAXIMUM ALLOWABLE CLEARANCE OF 3/4 OF AN INCH BETWEEN THE DOOR BOTTOM AND SILL AT DOOR IN THE ENTRANCE LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING IN THE 4th ROOM FROM NORTH LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL LIGHT FIXTURE AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 3E | Dec 29, 2025 | REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE REGLAZE ENAMEL PORCELAIN AT BATHTUB IN THE BATHROOM LOCATED AT APT 3E, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Open | — | Dec 29, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE FLOOR AT PUBLIC HALL, 2nd STORY, SECTION ''SOUTH '' |
| Class B | OpenRENT IMPAIRING | — | Dec 29, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT SECTION NORTH AT PUBLIC HALL, 6th STORY, SECTION ''NORTH'' |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT DOOR IN THE ENTRANCE LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | — | Dec 29, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE FLOOR AT SOUTH SECTION AT PUBLIC HALL, 1st STORY |
| Class B | Open | — | Dec 29, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE FLOOR AT SECTION NORTH AT PUBLIC HALL, 1st STORY |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING IN THE KITCHEN LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 1J | Dec 29, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 5X | Dec 29, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 5X, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH'' |
| Class B | Open | 5X | Dec 29, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 5X, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH'' |
| Class B | Open | 1J | Dec 29, 2025 | TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 11 SQ FT AT WINDOW RECESS AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 1J | Dec 29, 2025 | REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 1J | Dec 29, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | OpenRENT IMPAIRING | — | Dec 29, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT SECTION SOUTH AT PUBLIC HALL, 1st STORY |
| Class B | OpenRENT IMPAIRING | — | Dec 29, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT ''STAIRWELL C'' AT PUBLIC HALL STAIRS, 4th STORY, SECTION ''SOUTH '' |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL LIGHT FIXTURE AT CEILING IN THE FOYER LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 6J | Dec 29, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOWER SASH COUNTER BALANCE AT 1ST WINDOW FROM NORTH AT EAST IN THE 4th ROOM FROM NORTH LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Closed | 1J | Dec 29, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT NORTH WALL IN THE FOYER LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | — | Dec 29, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE FLOOR AT PUBLIC HALL, 6th STORY, SECTION ''NORTH'' |
| Class B | Open | 1J | Dec 29, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MECHANICAL STOPPER AT BATHTUB IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | 1J | Dec 29, 2025 | REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | — | Dec 29, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE FLOOR AT ''STAIRWELL C'' AT PUBLIC HALL STAIRS, 4th STORY, SECTION ''SOUTH '' |
| Class B | Open | 1J | Dec 29, 2025 | ADJUST DOOR TO PREVENT GAP - FIRE CODE/EGRESS · EGRESS28 RCNY § 25-171; & 67 (7)(B) MDL; NYC FIRE CODE § 703.1.3; NYC FIRE CODE § 703.2: ADJUST DOOR TO PREVENT GAPS BETWEEN THE TOP AND SIDE EDGES OF DOOR AND DOOR JAMB EXCEEDING THE MAXIMUM ALLOWABLE CLEARANCE OF 1/8 OF AN INCH AND MAXIMUM ALLOWABLE CLEARANCE OF 3/4 OF AN INCH BETWEEN THE DOOR BOTTOM AND SILL AT DOOR IN THE ENTRANCE LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' |
| Class B | Open | — | Dec 29, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE RUBBISH AT PUBLIC HALL, 6th STORY, SECTION ''SOUTH'' |
| Class B | OpenRENT IMPAIRING | — | Dec 29, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT ''STAIRWELL C'' AT PUBLIC HALL STAIRS, 6th STORY, SECTION ''SOUTH'' |
| Class B | OpenRENT IMPAIRING | — | Dec 29, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT PUBLIC HALL, 4th STORY, SECTION ''SOUTH '' |
| Class B | OpenRENT IMPAIRING | — | Dec 29, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT SECTION NORTH AT PUBLIC HALL, 1st STORY |
| Class B | OpenRENT IMPAIRING | — | Dec 29, 2025 | REMOVE ENCUMBRANCES · EGRESS§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT PUBLIC HALL, 2nd STORY, SECTION ''SOUTH '' |
| Class B | Open | 3E | Dec 29, 2025 | ADJUST DOOR TO PREVENT GAP - FIRE CODE/EGRESS · EGRESS28 RCNY § 25-171; & 67 (7)(B) MDL; NYC FIRE CODE § 703.1.3; NYC FIRE CODE § 703.2: ADJUST DOOR TO PREVENT GAPS BETWEEN THE TOP AND SIDE EDGES OF DOOR AND DOOR JAMB EXCEEDING THE MAXIMUM ALLOWABLE CLEARANCE OF 1/8 OF AN INCH AND MAXIMUM ALLOWABLE CLEARANCE OF 3/4 OF AN INCH BETWEEN THE DOOR BOTTOM AND SILL AT DOOR IN THE ENTRANCE LOCATED AT APT 3E, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'' |
| Class B | Open | 6W | Dec 15, 2025 | ADJUST DOOR TO PREVENT GAP - FIRE CODE/EGRESS · EGRESS28 RCNY § 25-171; & 67 (7)(B) MDL; NYC FIRE CODE § 703.1.3; NYC FIRE CODE § 703.2: ADJUST DOOR TO PREVENT GAPS BETWEEN THE TOP AND SIDE EDGES OF DOOR AND DOOR JAMB EXCEEDING THE MAXIMUM ALLOWABLE CLEARANCE OF 1/8 OF AN INCH AND MAXIMUM ALLOWABLE CLEARANCE OF 3/4 OF AN INCH BETWEEN THE DOOR BOTTOM AND SILL AT . IN THE ENTRANCE LOCATED AT APT 6W, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''SOUTH'' |
| Class B | OpenRENT IMPAIRING | 6W | Dec 15, 2025 | REPAIR LEAKY PIPES · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE WATER SUPPLY PIPE UNDER WASHBASIN IN THE BATHROOM LOCATED AT APT 6W, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''SOUTH'' |
| Class B | OpenRENT IMPAIRING | 6U | Nov 17, 2025 | REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN WASTE LINE UNDER SINK IN THE KITCHEN LOCATED AT APT 6U, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH'' |
| Class B | Open | — | Nov 17, 2025 | REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WIRED GLASS PANE ON DOOR LEADING TO FIRE STAIRS ''D'' AT CELLAR |
| Class B | Open | — | Nov 17, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE COMPACTOR CLOSET AT PUBLIC HALL, 3rd STORY, SECTION ''SOUTH'' |
| Class B | Open | 3S | Nov 17, 2025 | REPAIR LEAKY FAUCETS · WATER SUPPLY§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 3S, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''SOUTH'' |
| Class B | Open | — | Nov 17, 2025 | REPLACE · MAINTENANCE§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING WOOD BASEBOARD AT EAST AND NORTH WALLS AT CELLAR |
| Class B | Open | — | Nov 17, 2025 | REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE COMPACTOR CLOSET AT PUBLIC HALL, 6th STORY, SECTION ''SOUTHSOUTH'' |
| Class B | OpenRENT IMPAIRING | 6U | Nov 17, 2025 | INADEQUATE COLD WATER · WATER SUPPLY§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF COLD WATER FOR THE FIXTURES AT SINK IN THE KITCHEN LOCATED AT APT 6U, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH'' |
| Class B | Closed | — | Nov 17, 2025 | REMOVE ENCUMBRANCE · EGRESS§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES FLOWER POTS ON 2ND STORY BALCONY AT 2ND FIRE ESCAPE FROM NORTH AT BUILDING FRONT |